
Service Manual for FNDX 5
08/2009 FR
1.1.1
BEFORE INSTALLATION
*)
Site preparation, e.g., water supply, drainage electrical supply must be completed prior installation.
1.1.2
LOCATION
*)
Processor can be installed "through-the-wall" or completely in the darkroom.
Required measurements can be taken from the processor specification sheet.
For "through-the-wall", a purpose built panel is required (optional accessory).
1.1.3
ELECTRICAL SUPPLY
*)
All electrical connections must meet national safety requirements. Correct fuses and electrical
requirement can be taken from the processor specification sheet.
1.1.4
WATER SUPPLY
*)
The processor must be connected to the local water supply by using a DVGW-approved system
separating device or pipe separating device.
*)
The cold water supply pipe must have a stopcock fitted connection to the processor and should be
done by using the 3/4" hose connector, supplied. Easy access to the stopcock should be provided as
it has to be opened and closed daily.
*)
A built in magnetic valve reduces water consumption to a maximum of 2.0 ltr./minute using pressure
and quantity control.
*)
It is recommended to run a second cold water supply with 2.5 meters of hosing to facilitate easy
cleaning of the racks and tanks (water supply kit - optional accessory).
Power cord with plug
CEE 3P+N+PE 16-6h
415V 16A
Main switch
Water connection and
drains in front of the
processor (see page 3)
Page 1