Setting Parameters

 

The following explains how to set the parameters.

 

 

No matter where you are in monitor or setup mode, pressing the 

 key returns you to

operation mode. When setting the parameters in manual mode, pressing the key holds
manual mode and returns you to operation mode.

 

5-6

 

Key Lock and Password

 

Setting Key Lock

 

When key lock is activated, parameters cannot be changed but can displayed. Use the follow-
ing steps to set key lock.

 

Saving and entering a password

 

Use the following steps to save a password.

 

 

The authority of the passwords grows from "

 

PAS1

 

" to "

 

PAS2

 

" to "

 

PAS3

 

". The higher the author-

ity, the greater number of channels for display and settings.

Use the following steps to enter a password.

 

6

 

Parameter List

 

The following explains each channel parameter.
The list also shows the operational range of set values for parameters that are limited.

 

 

When the PV input lower limit (Pvb), PV input upper limit (PvF), or decimal place position
(Pvd) is changed, reconfigure all the initial parameter setting values.

 

 

When the parameter that has

 

 

 

 

on its Remarks column is changed, turn off the power

once, and then re-start the controller.

 

6-1

 

Operation (Ch1)

 

The following is a menu to operate the controller. Switchover between auto and manual control
output, switchover between RUN and standby, and other such functions.

 

6-2

 

PID (Ch2)

 

Sets parameters for controls such as PID.

1

 

Press and hold the 

 key in operation mode, or manual mode.

 

This switches you to the monitor mode Mv1.

2

 

Press and hold the 

 key in monitor mode

This switches you to the channel menu of setup mode.

3

Choose the channel with the 

 keys, then press and hold the 

 key.

This switches you to the parameter menu.

4

Choose the parameter with the 

 keys, then press the 

 key.

The set value flickers.

5

Choose the parameter with the 

 keys, then press the 

 key.

The set value is fixed.

1

Display the operation menu ("

oPE Ch 1

").

2

Display key lock ("

LoC

") and press the 

 key.

3

Set the value.

0 : No lock (all parameters can be changed. Initial value.)
1 : All lock (no parameters can be changed.)
2 : All lock without SV (only the SV can be changed.)

4

Press the 

 key to set the value.

1

Display the password menu ("

PAS Ch11

").

2

Display password 1 ("

PAS1

") and press the 

 key.

3

Set the password.

You can enter the hexadecimal value 0000 through FFFF.

4

Press the 

 key to set the value.

"

PAS2

" and "

PAS3

" can be saved in the same way.

1

In monitoring mode, display ("

PASS

") and press the 

 key.

2

Enter a saved password and press the 

 key.

You will be able to operate the equipment depending on the authority of your password.

Point

Each parameter channel and the authority of passwords 1 to 3

Note: When “

FEFE

”  (FEFE) is entered as “

PASS

”  (PASS), all of the channels “OPE ch” to

“DSP ch” can be displayed and set. This “super password” function is useful when
you forget the set passwords.

oPE ch

PAS1 permissions 
<"

PASS

" = "

PAS1

">

PAS2 permissions <"

PASS

" = "

PAS2

">

PAS3 permissions <"

PASS

" = "

PAS3

">

Pid ch

PLT ch

PrG ch

Mon ch

SET ch

SyS ch

ALM ch

CoM ch

PFb ch

PAS ch

dSP ch

Password 
level

Parameter
display symbol

Parameter name

Function

Setting range

Initial 
value

Remarks

"

man

" (MAn)

Switchover 
between auto and 
manual mode

Switchover between 
auto and manual 
modes

oFF (auto) / on 
(manual)

oFF

"

STbY

" (STby)

Switchover 
between RUN 
and standby

Switchover the 
operation mode 
between RUN and 
standby

oFF (RUN) / on 
(standby)

oFF

"

rEm

" (rEM)

Switchover 
between local 
and remote SV 
operation

Switchover between 
local and remote SV 
operation

LoCL (local) / rEM 
(remote)

LoCL

(Note1)

"

PrG

" (PrG)

Ramp soak 
control command

Changes ramp soak 
run states

oFF (stop)
rUn (run)
hLd (hold)

oFF

Displays End 
(when ending) 
or GS (during 
guaranty soak).

"

At

" (AT)

Auto-tuning run 
command

Runs auto-tuning.

oFF (stop/finish)
on (normal type)
Lo (low PV type)

oFF

"

LA[h

(LACh)

DO output latch 
release command

Cancels the DO 
latch state

oFF / rST
(latch resets)

oFF

(Note2)

"

Svn

" (Svn)

Currently 
selected SV No.

Choose the SV No. 
used for control

Sv0
Sv1
Sv2
Sv3
Sv4
Sv5
Sv6
Sv7
di (chooses SV 
according to di)

Sv0

(Note20)

"

PLn1

" (PLn1)

Currently 
selected PID No.

Choose the PID 
group No. used for 
control

Pid 0 (PID ch)
P

id

 

 1

(PID group No. 1)
P

id

 

 2

(PID group No. 2)
P

id

 

 3

(PID group No. 3)
P

id

 

 4

(PID group No. 4)
P

id

 

 5

(PID group No. 5)
P

id

 

 6

(PID group No. 6)
P

id

 

 7

(PID group No. 7)

 

di (chooses PID 
group according to di)

 

Pid0

"

 

AL1

 

" (AL1)

"

 

AL1L

 

" (AL1L)

"

 

AL1h

 

" (AL1h)

"

 

AL5

 

" (AL5)

"

 

AL5L

 

" (AL5L)

"

 

AL5h

 

" (AL5h)

AL1 set value
AL1L set value
AL1h set value

AL5 set value
AL5L set value
AL5h set value

Set the alarm value.

0 to 100% FS 
(absolute value 
alarm)
-100 to 100% FS 
(deviation alarm)

 

10°C

 

(Note3)

"

 

LoC

 

" (LoC)

Key lock

Sets the key lock to 
prevent wrong 
operation

 0 (no lock)
 1 (all lock)
 

 

2

 

 

 

(All but SV locked)

 

0

Parameter
display symbol

Parameter name

Function

Setting range

Initial 
value

 

Remarks

 

"

 

P

 

" (P)

Proportional band

Sets the 
proportional band 
of the PID 
parameter. Setting 
"0.0" will turn it to 
an ON/OFF control.

0.0 to 999.9%

5.0%

"

 

i

 

" (i)

Integration time

 

Sets the integration 
time of the PID 
parameter. Setting 
"0" will turn off 
integration.

 

0 to 3200 sec

240 sec

"

 

d

 

" (d)

Differential time

Sets the differential 
time of the PID 
parameter. Setting 
"0.0" will turn off 
derivation.

0.0 to 999.9 sec

60.0 sec

"

 

hyS

 

" (hyS)

ON/OFF control 
hysteresis

Sets the hysteresis 
width for the ON/
OFF control.

0 to 50% FS

1°C

"

 

[oL

 

" (CoL)

Cooling 
proportional band 
coefficient

Sets the cooling 
proportional band 
coefficient. Setting 
"0.0" will turn the 
cooling into an ON/
OFF control.

0.0 to 100.0

1.0

 

(Note4)

RST

Содержание PXG5

Страница 1: ...errors or failures may be caused Periodic maintenance is recommended for continuous and safe use of this equipment Some parts installed on this equipment have a limited life and or may deteriorate with age The warranty period for this unit including accessories is one year if the product is used properly 2 Caution 2 1 Cautions when Installing Please avoid installing in the following locations Loca...

Страница 2: ... relay If the output operation frequency is high selecting a SSR SSC drive output type is recommended Proportionate cycles Relay output 30 seconds or more SSR SSC drive output 1 second or more When inductive loads such as magnetic opening closing equip ment etc as relay output equipment are connected use of Z trap manufactured by Fuji Electric Device Technology Co Ltd is recommended in order to pr...

Страница 3: ...orque of about 0 8 N m Do not attach anything to unused terminals Do not use relay terminals PC loader interface PXG9 TOP TOP 13 24 37 48 61 72 49 60 1 12 25 36 waterproof packing panel terminal screw M3 96 96 79 5 10 2 91 5 115 5 MAX t 6 2 31 32 33 34 35 36 7 8 9 1 2 3 4 5 6 10 11 12 mounting fixture fastening torque 0 15 N m 25 26 27 28 29 30 Panel thickness 1 to 8 mm PC loader interface 25 36 1...

Страница 4: ...ance bulb input 33 34 35 36 Current voltage input Voltage mV input 33 34 35 36 Measurement value input 29 30 29 30 RSV2 input CT2 input 25 26 27 28 DIO COM DI3 DI5 DI4 Digital input 25 26 27 28 DIO COM DI3 DI5 DI4 Digital input 25 26 27 28 29 30 DIO COM DI3 DI5 DI4 DO4 DO5 Digital input output 5 6 Power supply Note 3 Note 1 Note 2 50 60Hz 31 32 DI COM DI1 3 4 3 4 3 4 5 6 1 2 DI COM DI1 3 4 1 2 RS4...

Страница 5: ...e SV display shows the input output values For more details on PASS PASS see 5 6 Key Lock and Password page 6 For more details on Note in the Remarks column see 6 Parameter List page 6 5 3 Basic Operations Pressing the key or the key switches between modes Pressing in monitor mode or setup mode allows you to choose menu items Changing SV set values Changing MV control output values 5 4 Operations ...

Страница 6: ...channel and the authority of passwords 1 to 3 Note When FEFE FEFE is entered as PASS PASS all of the channels OPE ch to DSP ch can be displayed and set This super password function is useful when you forget the set passwords oPE ch PAS1 permissions PASS PAS1 PAS2 permissions PASS PAS2 PAS3 permissions PASS PAS3 Pid ch PLT ch PrG ch Mon ch SET ch SyS ch ALM ch CoM ch PFb ch PAS ch dSP ch Password l...

Страница 7: ... Sets the integration time 0 to 3200 sec 240 sec d7 d7 Differential time 7 Sets the differential time 0 0 to 999 9 sec 60 0 sec hyS7 hyS7 ON OFF control hysteresis 7 Sets the hysteresis when using the ON OFF control 0 to 50 FS 1 C oL7 CoL7 Cooling proportional band 7 Sets the cooling proportional band 0 0 to 100 0 1 0 Note4 Parameter display symbol Parameter name Function Setting range Initial val...

Страница 8: ...SV input filter Sets the time constant for the RSV input filter 0 0 to 120 0 sec 0 0 sec Note1 fixed at 0 8bit PV input underflow 9bit PV input overflow 10bit underrange 11bit overrange 12bit RSV underrange 13bit RSV overrange 14bit range setting error 15bit EEPROM error 0bit PFB input underflow 1bit PFB input overflow RST RST RST RST 1r C1r OUT1 range Sets the range of the control output OUT1 0 5...

Страница 9: ...r alarm function bit2 non excitation output alarm function bit3 hold reset function RST PrCS PrCS Control target Allows you to select the control target SRV1 Servo control 1 SRV2 Servo control 2 PFB Position feedback control PFb Srv1 with PFB without PFB Note16 Stmd STMd Start mode Sets the operation mode when starting up Auto auto mode startup Man manual mode startup Rem remote mode startup STby ...

Страница 10: ...ou will need to run auto tuning to set the PID parameter when using fuzzy control Setting fuzzy PID control Display Parameter name Function Setting range Initial value Remarks PAS1 PAS1 Password1 setup Sets password 1 0000 to FFFF 0000 PAS2 PAS2 Password2 setup Sets password 2 0000 to FFFF 0000 PAS3 PAS3 Password3 setup Sets password 3 0000 to FFFF 0000 Display Parameter name Function Setting rang...

Страница 11: ...re changing back to self tuning 1 Display the system menu SYS Ch 7 2 Display the control parameter CTrL and choose PID2 Pid2 3 Press the key to set the value dead time t process value tuning SV lag time suppress overshoot ON OFF control equipment power t SV process value control loop close close open PV At set value Behavior Function oFF Stop Finish Stops or finishes auto tuning on Normal type The...

Страница 12: ...et CAL to 3 in step 3 above This setting will automatically open and close the valve to adjust it auto matically Caution To manually adjust the valve carry out step 1 through step 7 as written above If the valve is not connected or connected incorrectly it can still be adjusted but will not achieve accurate results There is no open circuit judgment function for the valve opening feed back signal C...

Страница 13: ...SV 1 2nd ramp 3rd ramp 4th ramp SV 2 SV 3 SV 4 Dis play Function Name Behavior ON OFF Judgment conditio n 0 No function Nothing happen 1 Switchover between standby ON OFF Switches between standby on and off Standby Standby Cancel Edge 2 Switchover between auto manual Switches between auto and manual control output Manual Auto Edge 3 Switchover between local remote Switches between local and remote...

Страница 14: ...ting DO1 to DO5 Function Wire burnout circuit alarm 41 Loop break alarm 1 44 Heater burnout alarm 1 Wire break short circuit alarm 47 Load short circuit alarm Dis play Function Name Behavior ON OFF Judgment conditio n Settings complete Using them as alarms 1 to 31 Using them as events 35 to 102 or timers 32 to 34 1 Setting the System Menu 2 Setting the Alarm Menu 3 Setting the alarm menu page 14 D...

Страница 15: ...2 Display hysteresis 1 A1hY and set the hysteresis 3 Display delay time 1 dLY1 and set the delay 4 Display delay time units 1 dL1U and set the units to minutes or seconds 5 Set the values for alarm 2 to alarm 5 as necessary 6 Press the key to set the value 1 Display the operation menu oPE Ch1 2 Set the alarm 1 set value AL1 or AL1L and AL1H The parameters displayed will vary according to the type ...

Страница 16: ...time SFTM and set the time 4 Press the key to set the value 5 Turn off the power once and then re start the controller to begin soft start When the soft start function is turned on the lower display will alternate show ing SoFT and SV Note Do not use auto tuning at the same time 1 Display the setup menu SET h 6 2 Display FALT output 1 set value FLo1 and set the output value For dual control set FL...

Страница 17: ...alue 1 Display the operation menu oPE Ch1 2 Display the selected PID number PLn1 and choose the PID No 3 Press the key to set the value 1 Display the palette menu PLT Ch 3 2 Display max selected PID number PL1M and set the PID number by choosing it with the user key 3 Display the user key function setting UKEy and set it to PID selection function 4 On the PV SV display pressing the user key will s...

Страница 18: ... 7 and STbY is ON Normal control The controller does not have to be restarted Parameters may not be displayed q Check the settings of dP01 to dP30 w Check the password function Normal control The controller does not have to be restarted Input type Measurement range C Measurement range F Smallest input increment C Input code Resistance bulb JIS IEC Pt 100Ω 0 to 150 32 to 302 0 1 1 0 to 300 32 to 57...

Страница 19: ...thout hold alarm may turn ON when starting up Caution When alarm action code is changed alarm set value may also become dif ferent from previous settings When alarm action type code is changed turn off the power once and then re start the controller before starting control Aln AL1 to AL5 show the alarm set values ALnh AL1h to AL5h show the alarm set values ALnL AL1L to AL5L show the alarm set valu...

Страница 20: ... mV input voltage input current input 0 3 FS 1digit Indication resolution 0 3 FS or less Digital Output Relay contact output DO1 to DO3 1a contact 220V AC 30V DC 3A resistance load Transistor Output DO4 DO5 Open collector 30V DC 100mA max 2 contacts Judged ON 1V DC or less Digital input Contact or Transistor type Max 5 inputs 30V DC 3mA 1 input Judged ON 1kΩ or less contact or 5V DC or less transi...