– 14 –
The following steps will explain an example of how to set DI1 to switchover between standby
ON/OFF.
7-12
Digital Output
Each of DO1 to DO5 can be assigned the following functions (events). The functions are
divided into two categories for when they behave as alarms and when they behave as events.
1. DO event settings
Events are divided into those related to alarms and those not related.
For more about the events related to alarms, see "11. Alarm Action Type Codes" (page 18).
Use the following steps events other than alarms.
●
Ramp soak delay start
●
Wire burnout circuit alarm
●
Conditional outputs
Use the following steps to set DO.
2. Setting DO option functions
Allows you to set not just even settings, but option functions for each DO.
The DO events are set by each digit.
3. Setting the alarm menu
●
Hysteresis Function
The hysteresis band is preserved during alarm output.
●
Delay Function
When events (including alarms) occur, the DO does not begin outputting immediately.
Instead, the event continues for a specified period of time before outputting DO.
"
47
"
Delay start(DO4)
Enables delay start with the delay time = dLY4.
Delay start
enable
-
"
48
"
Delay start(DO5)
Enables delay start with the delay time = dLY5.
Delay start
enable
-
1
Display the system menu ("
SYS [h 7
").
2
Display the DI1 parameter ("
di1
") and choose 1 ("
1
").
This chooses to switchover between standby ON and OFF.
3
Press the
key to set the value.
Caution
When “Switchover between local and remote” (DI setting value =3) is used for the
digital input function, the operation before turning off the power of the main unit
affects the DI operation when the power turns on again.
(For the DI operation when the power turns on under each state, see the table
below.)
No
.
Operation before turning off power of the main unit
DI status
while the
power of the
main unit is on
DI behavior while
the power of the
main unit is on
Operation
Operation
status
1
DI On when rEM parameter = LoCL
Remote SV
operation
DI On
Remote SV operation
DI Off
Local SV operation
2
Switches to rEM parameter = rEM by
key operation
DI On
Remote SV operation
DI Off
Remote SV operation
3
Switches desired parameter setting
value via communication during rEM
parameter = rEM
DI On
Remote SV operation
DI Off
Remote SV operation
4
DI Off when rEM parameter = rEM
Local SV
operation
DI On
Remote SV operation
DI Off
Remote SV operation
5
Switches to rEM parameter = LoCL by
key operation
DI On
Remote SV operation
DI Off
Local SV operation
6
Switches desired parameter setting
value via communication during rEM
parameter = LoCL
DI On
Remote SV operation
DI Off
Local SV operation
Type
Setting (DO1 to DO3)
Function
Ramp soak delay start
35
Delay start enable
Type
Setting (DO1 to DO5)
Function
Wire burnout circuit alarm
41
Loop break alarm 1
44
Heater burnout alarm 1
Wire break/short circuit
alarm
47
Load short-circuit alarm
Dis
play
Function Name
Behavior
ON
OFF
J udgmen t
conditio
n
Settings complete
Using them as alarms (1 to 31)
Using them as events (35 to 102)
or timers (32 to 34)
1. Setting the System Menu
2. Setting the Alarm Menu
3. Setting the alarm menu (page 14)
•
Delay
•
Hysteresis
Settings complete
1. Set events for DO1 to DO5
1. DO event settings (page 14)
2. Set DO options
2. Setting DO option functions (page 14)
•
Latch function
•
Input error
•
Non-excitation output
•
Hold reset
3. Setting the Operation Menu
4. Setting the operation menu (page 15)
•
Alarm set value
Type
Setting (DO1 to DO5)
Function
Conditional outputs
51
During auto-tuning
52
Normal
53
During standby
54
During manual mode
55
During remote SV operation
56
During ramp SV
Ramp soak Event Output
60
OFF state
61
RUN state
62
HOLD state
63
GS (Guaranty Soak) State
65
END state
Time Signal
71
Time signal (1st segment)
72
Time signal (2nd segment)
73
Time signal (3rd segment)
74
Time signal (4th segment)
75
Time signal (5th segment)
76
Time signal (6th segment)
77
Time signal (7th segment)
78
Time signal (8th segment)
79
Time signal (9th segment)
80
Time signal (10th segment)
81
Time signal (11th segment)
82
Time signal (12th segment)
83
Time signal (13th segment)
84
Time signal (14th segment)
85
Time signal (15th segment)
86
Time signal (16th segment)
87
Time signal (17th segment)
88
Time signal (18th segment)
89
Time signal (19th segment)
90
Time signal (20th segment)
91
Time signal (21st segment)
92
Time signal (22nd segment)
93
Time signal (23rd segment)
94
Time signal (24th segment)
95
Time signal (25th segment)
96
Time signal (26th segment)
97
Time signal (27th segment)
98
Time signal (28th segment)
99
Time signal (29th segment)
100
Time signal (30th segment)
101
Time signal (31st segment)
102
Time signal (32nd segment)
1
Display the system menu ("
SYS Ch 7
").
2
Set the event you want to specify under the DO1 output event setting type
("
do1T
").
3
Set the option function under the DO1 option function parameter ("
doP1
").
For the contents of this setting, see "2. Setting DO option functions" below.
4
Set DO2 to DO5 as necessary.
5
Press the
key to set the value.
bit
Function
Description
bit0
Event output latch function
Latches (maintains) the DO when the event starts
bit1
Error alarm function
Outputs when the unit receives an input error
(“
UUUU
” or “
LLLL
” is displayed).
Set DO event to “0” when using this function.
bit2
Non-excitation output alarm
function
Reverses the output signal and outputs it through
the DO terminal when the event starts
bit3
Hold reset function
When using an alarm with hold, the hold function
will reset when any of the following operations
occur:
SV change / Alarm type change / Alarm set value
change /Standby cancel / Power reset
bit0 (1 : ON, 0 : OFF)
bit1 (1 : ON, 0 : OFF)
bit2 (1 : ON, 0 : OFF)
bit3 (1 : ON, 0 : OFF)