![Fuji Electric MICREX-SX series SPF Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/fuji-electric/micrex-sx-series-spf/micrex-sx-series-spf_user-manual_2341797009.webp)
2-2
Section 2 Specifications
2-2 Functional/Performance Specifications
2-2-1 Specification list
(1) Analog input unit
Item
Specification
Type
NA0AX06-MR
No. of input channels
6 channels
Input impedance
Voltage: 63.2 k
W
, Current: 250
W
Maximum allowable input
Voltage: ±15V, Current: ±30mA
Input range
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
Resolution
12 bits or 14 bits (Set for individual channels by the program loader.)
Overall accuracy
±1%
Digital output value
12 bits: 0 to 4000 / -2000 to 2000, 14 bits: 0 to 16000 / -8000 to 8000
Sampling period
Synchronized with the scan of the basic unit.
Moving average
1 to 16 times (Set for individual channels by the program loader.)
External wire connections
8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire size
AWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication
5V power supply display, ON when normal (red)
Isolation method
Transducer (power supply) and photocoupler (signal)
Occupied words
6 words
External power supply
24V DC, 53mA
Internal current consumption
5V DC, 25mA
Dimensions
40 (W) x 90 (H) x 80 (D) (mm)
Mass
Approx. 150g
Содержание MICREX-SX series SPF