![Fuji Electric MICREX-SX series SPF Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/fuji-electric/micrex-sx-series-spf/micrex-sx-series-spf_user-manual_2341797012.webp)
2-5
Section 2 Specifications
(4) Thermocouple input unit
Item
Specification
Type
NA0AX06-TC
No. of input channels
6 channels
Resolution
0.1°C or 1°C *1
Thermocouple type
J, K, R, S, E, T, B, N (Collectively set for all channels by the jumper pin in the unit)
Digital output value
12 bits: 0 to 4000 / -2000 to 2000, 14 bits: 0 to 16000 / -8000 to 8000
Temperature measurement range J: -200.0 to 1200.0°C
K: -200.0 to 1200.0°C
T: -190.0 to 380.0°C
E: -190.0 to 1000.0°C
N: -200.0 to 1000.0°C
B: 350.0 to 1800.0°C
R: 0.0 to 1800.0°C
S: 0.0 to 1700.0°C
-328.0 to 2192.0°F
-328.0 to 2192.0°F
-310.0 to 716.0°F
-310.0 to 1832.0°F
-328.0 to 1832.0°F
622.0 to 3272.0°F
32.0 to 3272.0°F
32.0 to 3092.0°F
Cold junction automatic
compensator
Built in the unit
Data type of digital output value INT type
Sampling period
2 seconds (high speed) or 4 seconds (low speed)
(Collectively set for all channels by the program loader.)
Moving average
No moving average / 2 / 4 / 8 times
(Collectively set for all channels by the program loader.)
External wire connections
8-pole terminal block (M1.6, Phoenix-type) x 2, Tightening torque: 0.12 to 0.15 N·m
Status indication
5V power supply display, ON when normal (red)
Isolation method
Transducer (power supply) and photocoupler (signal)
Occupied words
6 words
External power supply
24V DC, 29mA
Internal current consumption
5V DC, 30mA
Mass
Approx. 140g
*1 The resolution is determined by the setting of the “sampling period” in the parameter.
When the resolution is 1°C: Set to “high speed.”
When the resolution is 0.1°C: Set to “low speed.”
Содержание MICREX-SX series SPF