24
How to set o40 to o43 and o48 to o51
Specifying the function code type (shown in Table 7.2) and number in a 4-digit hexadecimal notation.
Table 7.2 Function Code Type
Type
Type Code
Function Code
Type
Type Code
Function Code
S 2
02h
Command/function
data
A 9 09h
Motor
2
function
M 3 03h
Monitored
data
o 10 0Ah
Optional
function
F 4
04h
Fundamental
function
J 14 0Eh
Application
function
E 5
05h
Terminal
function
y 15 0Fh
Link
function
C 6 06h
Control
function
W 16 10h
Monitor
2
P
7
07h
Motor 1 function
X 17 11h
Alarm
1
H 8 08h
High performance
function
Z 18 12h
Alarm
2
Example: For F26:
F
⇒
Type Code 04
26
⇒
1A (hexadecimal)
041a
Once you have modified the settings for o40 to o43 and o48 to o51, be sure to restart both the inverter
and this option in order to validate the new settings.
7.3 An Example of Actual I/O Communication Data
Presented herein is an actual communication data in the format of Extended Speed Control Instance, the factory
default format.
(1) Driving pattern example
Given below is an example of the driving pattern for controlling the inverter. Its corresponding I/O data is
shown in (2) on the next page.
Figure 8 Driving Pattern
Forward
Reverse
Time (s)
1800 r/min
300 r/min
1800 r/min
Function code number (hexadecimal)
Function code type (in accordance with Table 7.2)