(2) Extended Speed Control Instance (factory default)
Output (from master to this option): o31=0 or 21
Instance byte
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
0
-
NetRef NetCtrl -
-
Fault
Reset
Run
Reverse
Run
Forward
1
(Fixed at 00)
2
Speed Reference (lower byte) (r/min)
21
3
Speed Reference (upper byte) (r/min)
Run Forward:
1 = Run forward command
Run Reverse:
1 = Run reverse command
Fault Reset:
1 = Reset the alarm condition
NetCtrl:
1 = Request for enabling run command sent from DeviceNet;
0 = Request for enabling run command sent from other than DeviceNet
NetRef:
1 = Request for enabling speed reference sent from DeviceNet;
0 = Request for enabling speed reference sent from other than DeviceNet
Speed Reference:
Speed reference (in r/min)
Input (from this option to master): o32=0 or 71
Instance byte
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
0 At
Reference
Ref
FromNet
Ctrl
FromNet
Ready Running
Reverse
Running
Forward
-
Faulted
1 Drive
State
2
Speed Actual (lower byte) (r/min)
71
3 Speed
Actual
(upper
byte)
(r/min)
Faulted:
1 = The inverter has (and remains) tripped.
Running Forward:
1 = The motor is running forward.
Running Reverse:
1 = The motor is running backward (in the reverse direction).
Ready:
1 = Ready to run
CtrlFromNet:
1 = Run command sent from DeviceNet being enabled
0 = Run command sent from other than DeviceNet being enabled
RefFromNet:
1 = Speed reference sent from DeviceNet being enabled
0 = Speed reference sent from other than DeviceNet being enabled
At Reference:
1 = The motor is running at the reference speed.
Drive State:
1 = Startup, 2 = Not Ready, 3 = Ready, 4 = Enabled, 5 = Stopping,
6 = Fault stop, 7 = Faulted
Speed Actual:
Actual rotation speed (in r/min)