background image

LM2A Wall Mounted Solution

 

 

 

 

 

Page 

13

 of 

20

 

Fuji Electric Europe GmbH

 

Note *1:  All items inside this box are default or option elements of the Wall Mounted solution. Items located out 

of this box are external and not included. 

Note *2:  Install  a  recommended  molded  case  circuit  breaker  (MCCB)  or  residual-current-operated  protective 

device (RCD)/earth leakage circuit breaker (ELCB) (with over current protection function) in the primary 
circuit of the inverter to protect wiring 

Note *3:  To bring the inverter into compliance with the European electrical safety standard IEC/EN 61800-5-1 or 

compliance with Canadian and U.S. standards (CSA certification), be sure to insert the specified fuse 
(see Instruction Manual) in the primary circuit of the inverter. 

Note *4:  In case of not installing the two MC between motor and inverter, please follow the procedure explained 

in 

AN-Lift2-0001 Use of FRENIC-Lift STO inputs in elevator applications

 document. 

Note *5:  Use the metal plates placed on removable terminals to connect the shield by means of metal cable ties 

for example. 

Note *6:  Braking resistor is optional. 
Note *7:  Connect  an  external  power  supply  230  VAC  to  terminals  [1]  and  [2]  of  the  common  terminals  for  the 

contactor coils. 

Note *8:  Jumper to connect/disconnect internal EMC filter. It is a metal plate placed on the EMC terminal. 
Note *9:  Removable  terminals.  For  detailed  information,  refer  to  FRENIC-Lift  LM2A  series  Instruction  Manual, 

section 2.2.4. 

Note *10:  Terminal configuration is set to SOURCE. Changing this configuration will make that the Wall Mounted 

solution do not work properly. 

Note *11:  Wired to terminals (Y3A/C). It is mandatory to set the parameter E22 to value 123 (SCC function) for the 

proper function of the Wall Mounted solution. 

Note *12:  Wired to the terminal (X4). It is mandatory to set the parameter E04 to value 115 (SCCF function) for the 

proper function of the Wall Mounted solution. 

 

2.4  Wiring and terminals 

Follow the procedure below. In the following description, it is assumed that the Wall Mounted solution has already 
been installed. 

2.4.1  Removing the front cover of the Wall Mounted 

[1] 

Loosen up the screws of the Wall Mounted solution. 

[2] 

Hold the right and left ends of the top cover and remove it. 

 

(It is possible to remove the ground connection from the cover to ease the procedure.) 

 

Figure 2.2 Removing the Top Cover of the Wall Mounted Solution 

2.4.2  Mounting the front cover 

After wiring, place, wire the ground cable if it was removed and screw the top cover of the Wall Mounted solution. 

 

2.4.3  Recommended wire sizes 

Terminals for the main circuits should have insulation, insulation tubes, or similar treatment. 

 

 

Содержание FRENIC-Lift FRN0010WLM2A-4E

Страница 1: ...hree phase permanent magnet synchronous motors Read through this manual to become familiar with the handling procedure and correct use Improper handling might result in incorrect operation short life...

Страница 2: ...nted Solution Page 2 of 20 Fuji Electric Europe GmbH Version Changes applied Date Written Checked Approved 1 0 0 First release 11 11 2020 C Arjona J Alonso J Catal 1 0 1 Small text corrections xx 11 2...

Страница 3: ...erminals 13 2 4 1 Removing the front cover of the Wall Mounted 13 2 4 2 Mounting the front cover 13 2 4 3 Recommended wire sizes 13 2 4 4 Terminal arrangement diagrams and screw specifications 14 2 4...

Страница 4: ...Be sure to obtain the latest editions for use Safety precautions Read this manual thoroughly before proceeding with installation connections wiring operation or maintenance and inspection Ensure you h...

Страница 5: ...e to ground the inverter s grounding terminals G Otherwise an electric shock or a fire could occur Qualified electricians should carry out wiring Be sure to perform wiring after turning the power OFF...

Страница 6: ...over of the inverter before turning the power ON Do not remove the cover when the inverter power is ON Otherwise an electric shock could occur Do not operate switches with wet hands Doing so could cau...

Страница 7: ...carrying out regular inspections could result in malfunction or damage and an accident or fire could occur It is recommended that periodic inspections be carryout every one to two years however they...

Страница 8: ...ppearance of Product Unpack the package and check the following 1 An inverter with the ordered options and the following accessories are contained in the package 2 The inverter or any option have not...

Страница 9: ...with non flammable material Do not mount the cabinet upside down or horizontally 2 Clearances Ensure that the minimum clearances indicated in Figure 2 1 and Table 2 1 are maintained at all times By en...

Страница 10: ...KSC KIN 1 2 3 4 X1 220 VAC Control Terminals Control Terminals A1 A1 A2 A2 For details of inverter terminal definitions refer to the FRENIC Lift LM2A series Instruction Manual 2 3 Wall Mounted diagram...

Страница 11: ...3 MCCB or RCD ELCB 2 Common Terminals 1 2 3 4 Main Switch 220 VAC 7 Y3C SCC 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 11 11 1 KIN A2 A2 A1 4 2 KSC A2 KIN A1 R1 R2 R3 R4 14 13 A1 A2 FRN_ _ _ _WLM2A 4E OPT S1 FRENI...

Страница 12: ...1 5 4 9 9 9 9 Braking Resistor 6 L1 R L2 S L3 T Input KIN Fuse 3 MCCB or RCD ELCB 2 Common Terminals 1 2 3 4 Main Switch 220 VAC 7 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 1 KIN A2 A2 A1 4 KIN A1 FRN_ _ _ _WLM2...

Страница 13: ...Note 8 Jumper to connect disconnect internal EMC filter It is a metal plate placed on the EMC terminal Note 9 Removable terminals For detailed information refer to FRENIC Lift LM2A series Instruction...

Страница 14: ...25WLM2A 4E 6 4 6 15 FRN0032WLM2A 4E 6 Terminals for Wall Mounted solution option N3 or S3 In case of options N1 or S1 terminal are located in the inverter L1 R L2 S and L3 T with the same wire size de...

Страница 15: ...ter output for Short circuit U0 V0 W0 For a short circuit for PMS motor These outputs are connected internally to U V W DC reactor connection terminals P2 P3 Terminals for built in DC Reactor connecti...

Страница 16: ...ration Classification Name Configuration WM Version Hardware Switch SW1 Position SOURCE OPT S1 OPT S3 Software Parameter E04 Value 115 E22 Value 123 For detailed information about these functions refe...

Страница 17: ...foreign or dangerous objects are left Input voltage Check that the input voltages of the main and control circuit are correct Measure the input voltages using a multimeter or the like The standard sp...

Страница 18: ...lt your Fuji Electric representative Table 4 2 Replacement Parts Nominal applied motor kW Inverter type Part name Main Switch S1 Input Contactor KIN Short circuit Contactor KSC DC Reactor 4 0 FRN0010W...

Страница 19: ...LM2A Wall Mounted Solution Page 19 of 20 Fuji Electric Europe GmbH 5 2 Frame 2 Power supply voltage Inverter type Three phase 400V FRN0025WLM2A 4E FRN0032WLM2A 4E...

Страница 20: ...nfo france fujielectric europe com www fujielectric europe com United Kingdom Fuji Electric Europe GmbH UK Branch Bedford i Lab Stannard Way Priory Business Park Bedford MK44 3RZ Tel 44 0 1234 834 768...

Отзывы: