11
Molded Case Circuit Breakers
BW0 series
Quick reference guide
BW0 series 2, 3-pole IEC and CE marking conformed types
• 400AF
Frame
400A
Pole
2
3
Type
BW402S0
BW403S0
Rated current (A)
250, 300, 350, 400
Rated insulation voltage
(VAC) 690
[IEC 60947-2]
(VDC) 250
Rated breaking capacity (kA)
500VAC 20/10
20/10
[IEC 60947-2]
440VAC 36/18
36/18
(Icu/Ics) *1
415VAC 36/18
36/18
400VAC 36/18
36/18
380VAC 36/18
36/18
240VAC 85/43
85/43
230VAC 85/43
85/43
250VDC 20/10
20/10
Rated operating voltage [UL508] (VAC)
−
−
Dimensions (mm)
a 140
140
b 257
257
Page 28
c 103
103
d 146
146
Mass (kg) Front mounting type
4.6
5.6
Tripping device
Thermal-magnetic
Front mounting, front connection
Internal accessories
Page 16
Alarm switch
(W) BW9W1SHA
BW9W1SHA
Auxiliary switch
(K) BW9K1SHA
BW9K1SHA
Auxiliary alarm switch
(W+K) −
−
Shunt trip
(F) BW9FHA−
BW9FHA−
Undervoltage trip
(R) BW9RHA−
BW9RHA−
External accessories
Page 21
Operating handle N-type
BW9N0HA
BW9N0HA
Operating handle V-type
BW9V0HA
BW9V0HA
Terminal cover Short
BW9BTHA-S3
BW9BTHA-S3
Terminal cover Long
BW9BTHA-L3
BW9BTHA-L3
Insulation barrier Interphase
B-43A
B-43A
Flat terminal
BW9SS0H0-2
BW9SS0H0-3
Block terminal
−
−
Handle locking device
−
−
IEC 35mm rail mounting
−
−
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity
Ics: Rated service short-circuit breaking capacity
Available − Not available
a
d
c
b