background image

Remark to SDI-12 ‘Break’ signal

Since the 

RAINE-HYDRO

 does not have a sleeping mode it does not need to be ‘awakened’. This means that 

it 

ignores the “Break“ command. Therefore all regulations associated to the ‘break’ command do not have to 
be considered.

9.1  

Total Precipitation

For the measurement of the precipitation amount from data set to data set via the serial protocols the di

 erence 

of the total precipitation amount to the previous value must be calculated. 

Note: The value over

fl

 ow of the precipitation total must be taken into account in the calculation of the 

di

 erence. The value over

fl

 ow occurs at 60000 g of collected liquid. This results in a value over

fl

 ow at 

3000 mm for sensors with a collecting surface of 200 cm² and a value over

fl

 ow at 1500 mm for sensors 

with a collecting surface of 400 cm². 

9.2 Pulse 

Output

Each pulse corresponds to a prede

fi

 ned amount of measured precipitation. The resolution factor range is 

0.01...200 mm per pulse. This resolution factor can be con

fi

 gured with the 

rain[e]

 Commander along with the 

closing time / pulse width. The duty cycle is 1:1 - in other words the closing time has the same length as the pause 
time.
If more pulses have to be returned than possible with the given resolution and closing time, the remaining pulses 
will be queued and returned as soon as there are no new pulses added. This means e. g. that if a closing time of 
200 ms and a resolution factor of 0.01 is chosen - equivalent to 300 pulses per minute - and it is raining with an 
intensity of 4 mm/min for two minutes and 1.9 mm/min thereafter - equivalent to 190 pulses per minute, the pulse 
output will return 300 pulses in each of the 

fi

 rst two minutes and another 200 pulses will be queued. In the third 

minute again 300 pulses will be returned - 190 for the intensity in that minute and 110 from the queue. Accordingly 
280 pulses will be returned in the fourth minute and 190 pulses in the following minutes, since there are no further 
pulses left in the queue.

10 

Inspection and Troubleshooting

Visual checks for contamination should be done on a regular basis - depending  on the environment and
seasonal situation (spider and bird population, pollen, leaf fall). According to chapter 6 of the “VDI Guidelines
- Environmental meteorology - Meteorological measurements - Precipitation, VDI 3786 Part 7 (December
2010)” we recommend monthly checks. In areas with high air pollution weekly checks might be necessary to
ensure correct measuring results.

All water-bearing parts should be cleaned regularly. Rinsing should be su

  cient to clean the sensor from most

contamination. Dirt clinging to the collecting funnel or outlet pipe has to be removed carefully. Slight pollution of
the collecting vessel is not critical. The collecting vessel can be cleaned with water and a mild cleaning agent.

Make sure the instrument is in a stable and perpendicular position and check the ring, the funnel surface and
the sensor for damages.

Keep the measurement site free from overgrowing vegetation.

The bird protection has to be removed before the frost period.

Please be careful while cleaning the collecting vessel to prevent it from taking damage. The 

RAINE-HYDRO

 and the collecting vessel must not be cleaned with steel brushes or similar 

tools or aggressive detergents.

24

SDI-RAINE-HYDRO 

USER MANUAL

700-SDI-RAINE-HYDRO Rev1   03 Mar 2021 

Part# 21184

Содержание SDI-RAINE-HYDRO

Страница 1: ...t and 0 001 mm h intensity Measurement of precipitation amount and intensity Signal outputs 2 independently configurable pulse outputs SDI 12 All metal housing weatherproof and long durability The com...

Страница 2: ...Start p 11 6 6 Available In and Outputs p 11 6 7 Factory Settings p 11 7 Connecting Diagram p 12 Connecting Diagram p 12 6 8 T Terminal Assignment p 12 8 Configuration Software rain e Commander p 13...

Страница 3: ...event the ingress of unwanted liquids into the devices 7 Funnel heating and drain heating can be very hot if the heating is operated with the housing open There is a risk of being burnt It is therefor...

Страница 4: ...ing edge Protective covering Fastening screw Mounting pedestal Pole tube Mounting screws Connector heating power Connector sensor Fig 1a Fig 1b 4 Dimensions in mm 11 5 8 8 SDI RAINE HYDRO USER MANUAL...

Страница 5: ...essary The pulses from the reed contact generated by tipping the collecting vessel are used for error correction during periods of high intensity precipitation Furthermore the self emptying system all...

Страница 6: ...s SDI 12 Counts the amount of precipitation in steps of 0 01 mm for x minutes and divides the result by x minutes Variance SDI 12 Variance of measured values over 4 s The two pulse outputs can be conf...

Страница 7: ...length of 100 mm is recommended if a wooden pole is used Use a wrench 13 mm to tighten the screws in the mounting pedestal evenly Do not damage the measuring edge To improve the operating security in...

Страница 8: ...in the open direction anti clockwise Lift the casing with caution Mind the heater s terminal plug The measuring edge of the upper part of the housing is quite sharp There is a risk of cuts It is there...

Страница 9: ...ring spring with the site of the magnet facing towards the reed contact Fig 7 Insert the other axis into the other bearing Test for flawless tipping Fig 6 Inner workings of the RAINE HYDRO without col...

Страница 10: ...commended that on the measuring edge not be pressed on and or that gloves are worn Inserting the dirt trap spiral Insert the enclosed dirt trap spiral in the fun nel The spiral should be held in such...

Страница 11: ...er according to the device configuration T Overview status LED green on main board System start Permanent lighting of the LED for approx 3 seconds In operation Fast flashing of the LED 6 6 Available O...

Страница 12: ...Assignment All unused wires must be connected to unused pins or insulated to avoid malfunctions 7 Connecting Diagram Connecting Diagram 12 SDI RAINE HYDRO USER MANUAL 700 SDI RAINE HYDRO Rev1 03 Mar 2...

Страница 13: ...he Setup area the user must first select the COM port to which the RAINE HYDRO is connected from the drop down menu and retrieve the settings from the rain e gear wheel icon After retrieving the data...

Страница 14: ...ut OFF Pulse Output not isolated ON Operating Mode Heating ON OFF Standard Resolution Pulse Output isolated ON Resolution 0 10 mm m Closing Time 300 ms High Resolution Pulse Output isolated ON Resolut...

Страница 15: ...in SDI 12 Address 0 9 A Z a z Load Cell Adjustment Fig 15 The Load Cell Adjustment screen may be used to adjust the load cell It will give the number of cycles the program has carried out the mean val...

Страница 16: ...ing Test OK Malfunction Working Heating Temperature Sensor Bottom OK Malfunction Working Temperature Sensor Bottom Temperature Sensor Top OK Malfunction Working Temperature Sensor Top Status 6 9 Inter...

Страница 17: ...LF aI Send Identification allccccccccmmmmmmvvvxx xx CR LF aAb Change Address b CR LF aM Start Measurement atttn CR LF aMC Start Measurement and Request CRC atttn CR LF aC Start Concurrent Measurement...

Страница 18: ...returns its address and CR LF Syntax Command Answer a a CR LF a Sensor address a Sensor address End of command CR LF End of answer Example Command Answer 0 0 CR LF 1 1 CR LF Send Identification aI Th...

Страница 19: ...ensors described in the SDI 12 documentation the RAINE HYDRO measures continuously Thus the measured values from the continuous measurement are stored in a buffer while the string is being processed T...

Страница 20: ...ailable measured data In contrast to standard sensors described in the SDI 12 documentation the RAINE HYDRO measures continuously Thus the values during continuous measuring are stored in bu erwhileth...

Страница 21: ...ds C M or V are requested from the sensor with aD0 and aD1 The sensor uses the respective arithmetic sign or to separate the values If the data was requested with a CC or MC command it will be returne...

Страница 22: ...cksum End of command CR LF End of answer Additional Measurements With the following commands additional information can be generated by the RAINE HYDRO and requested with aD0 The additional measuremen...

Страница 23: ...at as the command aM see above The RAINE HYDRO answers to the command aV with a0039 Syntax Command Answer aV a0039 CR LF a Sensor address a Sensor address V Command Start Verification 003 Seconds the...

Страница 24: ...to 190 pulses per minute the pulse output will return 300 pulses in each of the first two minutes and another 200 pulses will be queued In the third minute again 300 pulses will be returned 190 for th...

Страница 25: ...ommander 11 Maintenance and Repair For technical assistance contact FTS Support at 1 800 548 4264 E mail 12 Equipment and Spare Parts PART RAINE CBL 10M RAINE WS 1M RAINE WS 1 5M RAINE WS 2M RAINE DEF...

Страница 26: ...o download the latest updates 1 Open an account with a valid e mail address and your own password 2 The system will send an activation link to your e mail address 3 Click on the activation link to cre...

Страница 27: ...mounting 60 mm Weight approx 2 5 kg Standards WMO No 8 VDI 3786 Bl 7 EN 61000 2 4 EN 61000 4 2 3 4 5 6 11 NAMUR NE 21 Protection class load cell IP67 Current consumption typ 6 9 mA at 12 V power supp...

Отзывы: