5.2.3 Limit contacts 1 and 2
The two limit contacts of the device are configured using this item. The arrow buttons can be used to determine the values
and the OK button can be used for confirmation purposes. The following settings can be implemented:
- warning value (WA/ VA): set-up of the warning value, the display starts flashing.
- activation value (ON/ VA): value where the limit contact is actuated. The diode indicates which of the limit contacts has
switched.
- switching hysteresis (HY): determination of the percentage switching hysteresis
5.3 Settings of the command values
This setting can be used to display any measuring range (-999… +9999) using the device. This range may deviate signifi
-
cantly from actual values and can be set individually.
5.3.1 Display activation
In order to have the command values displayed, the display has to be activated for the aforementioned beforehand (0=
ON; 1=OFF).
5.3.2 Set-up zero point
This menu item can be used to set the lower command value of the range to be displayed by means of the arrow buttons.
5.3.3 Set-up 100% value
The arrow buttons can be used to set the upper end value of the range to be displayed. The OK button can be used to
confirm the set values.
5.3.4 Position of the decimal point
Here you can specify where the decimal point is to be displayed in the display. You can use the arrow buttons to specify
the position and the OK button to confirm the selection.
5.3.5 Selection of the unit
You can use the arrow buttons to specify which unit is to be displayed on the display. You can confirm your selection by
using the OK button.
5.4 Configuration of the outputs
This menu item is used to configure (signal source and output type) the sensor outputs.
5.4.1 Signal source
The arrow buttons can be used to determine whether the output signal of the sensor is accepted or a command value is
specified by the user (0=internal; 1=external; 2=command value). Confirm your selection by using the OK button.
5.4.2 Output type
You can use the arrow buttons to determine which output type is issued by the device (0=0…10 V; 1=4… 20 mA; 2=0… 20
mA). Confirm your selection by using the OK button.
5.5 Set-up of the limit contacts
The arrow buttons can be used to determine whether the limit contacts are to work as normally closed or normally open
contact (0=normally open contact; 1=normally closed contact). Confirm your selection by using the OK button.
5.6 System settings
Here you can implement basic settings of the device. This includes reset times and MODBUS settings.
5.6.1 Set-up the reset times
5.6.1.1 Automatic menu exits
Upon expiration of which time (seconds) should the menu switch back to display level if the user does not implement any
further entries. Use the arrow buttons to enter the corresponding value and confirm by using the OK button.
5.6.1.2 Reset the code
Select code reset and confirm your selection by using the OK button, in order to reset the code to factory settings (0000).
5.6.2 Setting the display brightness
The display brightness can be set individually in a range between 30… 100% by using the arrow buttons. Confirm the cor
-
responding value by using the OK button.