2. Location in the compressed air system
A.
Maximum working pressure - 250 psig,
17.6 kgf/cm
2
. Do not exceed unit’s Maximum Working
Pressure.
1) For maximum capacity, install unit in air system
at highest pressure possible (e.g. before pressure
reducing valves)
2) For maximum capacity, install unit at coolest com-
pressed air temperature possible. Maximum inlet
compressed air temperature: 180°F, 82°C. If inlet
air exceeds this temperature, precool the air by
extending the piping between the compressor and
the dryer.
B. Air Outlet - Connect air outlet to downstream air lines.
C. By-pass piping - If servicing the unit without interrupt-
ing the air supply is desired, piping should include inlet
and outlet isolation valves and an air by-pass valve.
D. Condensate drain - It is advisable to connect drain
outlet to the condensate drainage system.
NOTE: Drain discharge is at system pressure. Drain line
should be anchored to prevent whipping.
1.4 Electrical connections
A. Dryer is designed to operate on power supply (voltage)
listed on serial number tag located on the back of the
dryer.
B. Dryer is supplied with an electrical cord. Install in re-
ceptacle of proper voltage.
NOTE: Models 50 and 75 (115v only) - Install plug
in receptacle rated for 20 amps. Units are sup-
plied with 20 amp plug.
NOTE: Refrigeration system is designed to run continu-
ously and should NOT be wired to cycle on/off with the air
compressor.
1.0 INSTALLATION
1.1 Location
A. Air compressor intake - Locate air compressor so that
contaminants potentially harmful to the dryer are not
drawn into the air system.
B. Free air flow - Do not block either side of the cabinet.
Observe minimum installation clearances as shown.
1.2 Mounting
Dryer is suitable for floor or shelf mounting.
1.3 Piping connections
A. Air Inlet - Connect compressed
air line from air compressor to
air inlet using strainer supplied.
1. Install strainer (included in
shipping carton) prior to
dryer inlet using pipe nipple
supplied or other piping as
required.
NOTE: Observe flow direction arrows on strainer.
NOTE: Install strainer where it is easily accessible for clean-
ing.
NOTE: Use vibration dampener, if vibration exists in air line
at inlet to dryer.
24"
12"
wall
6"
36"
Plug