FSA GT1-20LS Скачать руководство пользователя страница 6

handle the membrane by the end stems. The membrane is inserted into the housing o-rings first so the 
stem without the o-rings is visible. Replace the membrane cap firmly but do not overtighten. 

(c) Post Filters 

The system is supplied standard with an inline 2.5” GAC filter. These are also available as a DI cartridge or 
a Remineralising cartridge – the installation principle is the same. 

These filters are generally pre-installed. When you need to replace them, simply disconnect the tubing from 
each end and remove the fittings from the filter. Replace the fittings into the new cartridge then re-install. 

If the system is purchased with a DI filter, this GAC filter is removed and there should be a open end of 
tubing at the top of the system which is the outlet. 

(d) De Ionising Post Filters 

For DI Cannister filters – temporarily run a small length of tubing form the systems outlet to flush the water 
from the system before installing the DI system. This ensures that and TDS contamination in the system 
does not expire any of the DI filter media. Flush the system until the TDS shows a > 90 % Reduction in 
TDS compared to the raw inlet water. (minimum 30 minutes). After the flushing is finished, plug the ¼” 
tubing into the DI filter and run a length of tube to your tank/container or float valve. 

Connecting the System 

I. Tubing 

Measure a length of tubing (Blue 3/8”) from the feed water connection to the system. Cut the tubing using 
poly cutters or a sharp box cutter. Ensure that it is a clean straight cut with no rough edges. 

Measure a length of ¼” tubing from the drain valve (located under the membrane) which is marked as ‘to 
drain’ or ‘Flow 1000’ to a suitable drainage point. 

Measure a length of ¼” tubing from the outlet point of the system to your intended usage point or storage. 

II. Power 

The system is supplied with a 3 pin AU plug. Install this into a GPO (10A min). It is advised to also install a 
surge protector to protect the electrical components of the system in the event of a power surge or 
blackout. NOTE: If there is any damage to the cord DO NOT install – contact the manufacturer immediately  

Start Up & Operation 

I. Commissioning 

NOTE: New filtration systems will require a pre-flush before being used. The GT1-20LS system will need to 
run for at least 15 – 20 minutes before first use to clear and residue or fines from the filters. 

  Use a TDS meter to monitor the water to determine when the system is suitable for the intended 

application. 

  When the system is connected correctly, turn on the incoming water supply and allow the first filter 

cartridge to fill with water. Once this has stabilised, turn on the power to the system. 

  Turning the power on will actuate the inlet solenoid valve and the water will then begin to pass 

through the remaining 2 pre-filters then to the membranes. 

o

  The pumps will turn on at this point  

  Once the water reaches the membranes, the drain line should begin to sputter and produce water – 

it is normal for this to be cloudy and discoloured on first use. 

  At this point, the water will then need to slowly pass through the membranes and post filter so the 

system will need to run for several minutes until water will begin to flow. 

Your water is now suitable for use. 

II. General Operation 

The rating of this Reverse Osmosis system is 200GPD as per the membrane specifications meaning this 
system is capable of approx. 0.5L/Min of water production, this will vary depending on water quality and a 
number of factors. The systems are designed to be run in a closed loop configuration where the system 

Содержание GT1-20LS

Страница 1: ...ion Introduction 4 I Site Preparation 4 II Installation Mounting 4 III Installation Free Standing 4 IV Installing Connections Quick Connect 4 V Filter Protection 5 VI Drain Waste 5 VII Cartridge Insta...

Страница 2: ...are listed below If these conditions are not met the system may not be suitable for the application and may not function as specified These systems are designed for filtration on mains water for the r...

Страница 3: ...s which may require treating before the system Bore Water filtration is used when the water meets specific conditions where an RO unit will be suitable to remove elevated salt levels in the water gene...

Страница 4: ...tem to reduce negative effects on the pressure flow and performance of the system It is also recommended that the process water filtered water does not have to travel more than 2m elevation above the...

Страница 5: ...eated Before Spun Spun Before Carbon Highest Micron Before Lowest Micron As an example a common filter set would be 5uM Polyspun 20uM Low Pressure Carbon 0 5uM Chloramine Reduction Carbon You would in...

Страница 6: ...int Measure a length of tubing from the outlet point of the system to your intended usage point or storage II Power The system is supplied with a 3 pin AU plug Install this into a GPO 10A min It is ad...

Страница 7: ...uce water When the outlet shuts off the high pressure switch will trip after a period of time similar to a household pump and then the system will shut down When the outlet is opened and the pressure...

Страница 8: ...r Filter Cartridge Check TDS 6 12 Months GT5 12S Mixed Bed DI Resin Check TDS 6 12 Months 1Kg per refill Pumps Solenoids Switches GT13 38LS 8200L Reverse Osmosis Booster Pump 200GPD 2 000Hr 12 Months...

Страница 9: ...ation 3 Contamination 1 The filters are dry packed the carbons alkaline filters will have fines on them 2 As previously stated Activated Coconut carbon will react with the water when new and will incr...

Страница 10: ...electrician can test the components to see if power is making it to the pumps...

Страница 11: ...of of installation in the form of an invoice and or receipt Filter systems must be maintained as per FSA recommendations including the use of replacement filters fittings and components supplied by FS...

Страница 12: ...f the system is installed on an open circuit a plumber may not be required in this case the system must be installed in accordance with the user manual and determined to be correctly installed by FSA...

Отзывы: