Installation Requirements
Before you begin the installation, make sure that you have the followings:
Phillips screwdriver.
Standard-sized, 19" wide rack with a minimum of 1U height available.
Category 5e or higher RJ-45 Ethernet cables, fiber optical cables and console cable for connecting
network devices.
Site Environment
:
Do not operate it in an area that exceeds an ambient temperature of 50°C.
Do not install the equipment in a dusty environment.
The installation site must be free from leaking or dripping water, heavy dew, and humidity.
The installation site must be well ventilated. Ensure that there is adequate airflow around the
switch.
The switch should be installed at least 1U (44.45mm) away from devices to its sides.
Be sure that the switch is level and stable to avoid any hazardous conditions.
Ensure rack and working platforms are well earthed.