
Measuring the output voltage
Preparations:
-
Eliminate the short circuit in the char-
ging leads..
-
Operate the device in open circuit.
-
Prepare the output voltage measure-
ment.
-
Voltage Test "ON"
To start measuring the output voltage, set
the "Voltage Test" menu item to "ON".
-
The output voltage (Voltage) is dis-
played for checking.
A tick appears next to the menu item once
the test has been completed.
If the "Device tests" menu item and its
submenus have been used successfully,
the error "551 - Hardware change detec-
ted" is reset.
Other function
tests in the Ser-
vice menu
Checking of function that also has to be performed
-
All housing components, insulation components and protective covers must be
present and undamaged
-
Check that all screw connection torques are correct
Switching the battery charging system back on again
-
Check the characteristics and settings
-
Perform a short circuit test ® like an open circuit, nothing should happen
-
Connect charging leads to the wrong poles ® the battery charging system must
indicate polarity reversal
56
Содержание Selectiva 2040
Страница 2: ......
Страница 5: ...General information 5 ...
Страница 6: ...6 ...
Страница 12: ...12 ...
Страница 13: ...Replacing components 13 ...
Страница 14: ...14 ...
Страница 21: ...1 Fit the front panel of the housing see chapter Closing the device 21 EN ...
Страница 27: ...1 2 2 1 Fit the DC connection plate and secure with two 4x20 TX20 screws Tightening torque 1 5 Nm 27 EN ...
Страница 32: ...1 1 Fit the M4x10 TX20 screw on the device frame AC side Tightening torque 2 5 Nm 32 ...
Страница 34: ...1 Fit the housing cover see chapter Closing the 2 kW device 34 ...
Страница 42: ...42 ...
Страница 43: ...Safety Inspections 43 ...
Страница 44: ...44 ...
Страница 59: ...59 EN ...