![Fronius Primo GEN24 Скачать руководство пользователя страница 62](http://html1.mh-extra.com/html/fronius/primo-gen24/primo-gen24_operating-instructions-manual_2339203062.webp)
Q Absolute - Constant Reactive Power
Reactive power specification defined by a constant value [Var]. The function is
limited by the maximum apparent power and by "Cos
φ
Minimum"
Parameter
Range of val-
ues
Description
"Q - Reactive
Power (Var)"
-200,000 Var -
200,000 Var
Reactive power setting value in [Var] (set
value)
"Time Constant
(
τ
)"
0.01 s
‑
60 s
Time constant (1 Tau) in seconds [s].
Whenever the set value is changed, this
new set value is not triggered abruptly, but
smoothly in accordance with a PT1 re-
sponse. The time constant describes how
quickly the new set value is reached. (After
three time constants the final value 95 %
is reached)
Q Relative - Constant Reactive Power
Reactive power specification defined by a constant value in percent [%], related
62
Содержание Primo GEN24
Страница 2: ......
Страница 7: ...Country setup 7...
Страница 8: ...8...
Страница 74: ...74...
Страница 75: ...75 EN...
Страница 76: ......