Notes regarding positioning the inverter
Positioning the
inverter
IMPORTANT!
Ensure that any covers which were removed previously are refitted before
the inverter is moved to its final position (e.g. fit the side cover before positioning the invert-
er up against a wall).
IMPORTANT!
To prevent the inverter from toppling over, the inverter must be securely
fixed to the base after placing it in the final position.
Fix the inverter in place on the base, using at least 4 screws.
The fixing materials needed for this, such as screws or wall plugs, are not included in the
inverter's scope of supply. The installer is responsible for selecting the right type of fixing.
Air supply and connecting an exhaust duct
The air supply to the inverter must be at least 1200 m³/h (approx. 20 m³/min).
When connecting an exhaust duct, the back pressure it generates must not exceed 150
Pa.
This results in a volumetric flow of about 15 m³/min.