Initial startup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen
Page 33
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com
M0930408_en
4
4
Initial startup
4.1
Configuring the boiler
The boiler must be configured to the heating system on initial start-up.
N O T E
Optimum efficiency and consequently efficient operation with low
emissions can only be guaranteed if the system is adjusted by
qualified technicians and the specified factory settings are observed.
Take the following precautions:
U
It is recommended that the system is put into operation by the Fröling
customer service or an authorised installer.
Before you start heating with the boiler for the first time:
U
Adjust the control to the system type
The keypad layout and necessary control steps for modifying the
parameters can be found in the accompanying operating instructions for
the “Lambdatronic P 3200”.
4.2
Setting “Max Level” sensor
In delivery configuration, the factory settings of the sensor are secured
with a seal. Changes to the settings should only be carried out by
qualified technicians.
The monitoring LED (1) should only light up when identifying
materials!
U
If the monitoring LED stays on permanently, the sensitivity is set too
high!
´
Reduce the sensitivity by turning the adjusting screw (2) to the
left
U
If the monitoring LED does not react when pellets are being fed in,
the sensitivity is set too low!
´
Increase the sensitivity of the adjusting screw by turning to the
right
1
2
Содержание P4 Pellet 15
Страница 2: ......