Name
S3 Turbo 40
S3 Turbo 45
Nominal output
kW
40
45
Electrical connection
230V / 50Hz / fused C13A
Power consumption at nominal load
W
53 – 73
66
Power consumption in slumber mode
3
Weight of boiler incl. insulation and control
kg
610
620
Total boiler capacity (water)
l
190
Water pressure drop (ΔT = 10 / 20 K)
mbar
7.0 / 2.1
22.0 / 6.3
Minimum boiler return temperature
°C
60
Maximum permitted operating temperature
90
95
Permitted operating pressure
bar
3
Airborne sound level
dB(A)
< 70
Permitted fuel as per EN ISO 17225
Part 5: Firewood class A2 / D15 L50
Fuel loading door dimensions (width / height)
mm
330 / 370
Fuel loading chamber capacity
l
210
Combustion time
1)
- Beech
h
4.1 - 6.0
3.9 - 5.6
Combustion time
1)
- Spruce
2.9 - 4.2
2.7 - 4.0
1.Values specified for combustion time are guideline values at nominal load and will vary depending on water content (15-25%) and fill level
(80-100%)
Regulation (EU) 2015/1187
Energy efficiency
A+
A+
Rated heat output
kW
40
45
Energy efficiency index of the boiler model
115
116
Seasonal space heating energy efficiency
%
78
79
Energy efficiency index of the boiler in package with
temperature control
117
118
Energy efficiency class of the boiler in package with
temperature control
A+
A+
S3 Turbo 40 - 45
3
Technology
Technical specifications
20
Froeling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.at