The first BImSchV (Ordinance on small and medium-sized heating plants of 26
January 2010, BGBl. I P. 38) stipulates a minimum water heat storage tank volume of
55 litres per kilowatt of rated heat output; a water heat storage tank with a volume of
12 litres per litre of fuel loading chamber is recommended.
Recommended storage tank capacity:
Unit
S3 Turbo
20 – 30
1)
S3 Turbo
40 - 45
Recommended storage tank capacity
2)
[l]
1700
3000
1.Applies for S3 Turbo 18 as well (only available in Italy)
2.Values for calculating the capacity can be found in the technical data or the technical data with partial load inspection (if available)
For the correct dimensions of the storage tank and the line insulation
(e.g. in accordance with ÖNORM M 7510 or guideline UZ37) please consult your installer or
Froling.