Burner relay
▪ A: Standby boiler is controlled according to the program
that is set.
▪ 1: Standby boiler was started manually.
▪ 0: Standby boiler was stopped manually.
4.6 Feed system
4.6.1 Feed system - Times
System menu
Feed system
Times
Start of 1st pellet filling
First start for a filling process. A filling process is only
carried out if the fill level in the pellet container is below
85%.
Start of 2nd pellet filling
Second start for a filling process. This is likewise only
carried out if the pellet container level is below 85%. If you
only want one filling time, then set the second filling time to
the same time as the first filling time.
4.6.2 Feed system - Service
System menu
Feed system
Service
Refill of cyclone from
When set to “0%” the filling process is started according to
the filling times that are set. If there is a shortage of pellets
during the “
Heating
” status, the pellet container is filled
regardless of the current time.
Maximum time until switching of probe
Prerequisite: Feed system, universal suction, with
automatic toggle
Time period, during which the cyclone must reach a fill
level of 100% from a probe. If this time is exceeded, the
change-over unit automatically changes to the next probe.
If all probes are started and the fill level of 100% in the
cyclone is not reached, an error message appears on the
screen.
Probe suction reversal
Prerequisite: Feed system, universal suction, with
automatic toggle
Before switching to the next probe, each probe that was
last used is back-flushed for the time set.
NOTICE! This parameter is not in use for feed system “3
probe switch”!
Suction run-on
When the fill level sensor detects fuel in the cyclone, the
suction turbine remains active for the time set.
Refill cyclone after buffer charging
▪ NO: A filling process of the pellet container is carried
out according to the filling times that are set.
▪ YES: If the boiler shuts down once buffer tank loading is
complete, this parameter can then be used to fill the
cyclone without having to wait for the next filling start
point.
Parameters overview
4
Feed system
Service Manual Lambdatronic P 3200 for pellet boiler (4,3" Touch) | B1620121_en
55