2.4.4.18. Porucha P7
P7 display
High temperature protection of
evaporator
Whether compressor
operates?
Yes
Check whether the heat
exchanger is dirty, the air-
outlet is blocked and the
indoor fan is running
normal?
No
Check refrigerant system
(such as clogging of
capillary etc.)
No
Clean the heat exchanger and
the air-outlet
Reconnect and retest
No
Whether the
connection is
good?
No
Check the
resistance value of
the sensor via
Appendix 1,Is it
normal?
Check whether the
indoor fan is running
normal
Replace the temperature sensor
No
Yes
Whether the indoor
PCB is normal?
Replace the indoor PCB
No
Yes
Yes / No
Ano / Ne
P7 display
Zobrazeno P7
High temperature protection of evaporator
Vysokoteplotní ochrana výparníku
Whether compressor operates?
Pracuje kompresor?
Whether the connection is good?
Jsou propojení v pořádku?
Reconnect and retest
Znovu zapojte a znovu testujte
Check the resistance value of the sensor via Appendix 1, is it
normal?
Zkontrolujte hodnotu odporu čidla dle
přílohy 1, je v
normě?
Replace the temperature sensor
Vyměňte teplotní čidlo
Whether the indoor PCB is normal?
Je deska vnitřní jednotky v pořádku?
Replace the indoor PCB
Vyměňte desku (PCB) vnitřní jednotky
Check whether the heat exchanger is dirty, the air outlet is
blocked and the indoor fan is running normal?
Zkontrolujte zda-
li není tepelný výměník špinavý či
výstup vzduchu ucpaný a či vnitřní ventilátor funguje
správně?
Clean the heat exchanger and the air-outlet
Vyčistěte tepelný výměník a výt
lak vzduchu
Check whether the indoor fan is running normal
Zkontrolujte zda se vnitřní ventilátor otáčí normálně
Check refrigerant systém (such as clogging as capillary etc.)
Zkontrolujte systém chlazení (např. ucpaná kapilára atd.)