Dryer

FFRE1001PW     

7.0 Cu. Ft. D.O.E.  Electric 

• 

Do NOT install in area exposed to dripping water or outdoor weather 

conditions; where gasoline or other flammables are kept or stored; or 

where dryer comes in contact with curtains, drapes or anything that 

will obstruct flow of combustion and ventilation air.

• 

For garage installation, dryer MUST be located minimum 18" above floor.

• 

Floor MUST be solid with 1" maximum slope. Do NOT install on 

carpeted surface.

• 

Dryer MUST exhaust to outside of building, NOT into any concealed 

space.

• 

Exhaust installation requires minimum 4"-diameter rigid or semi-rigid 

metal duct with approved, unobstructed vent hood having swing-out 

damper(s). If installing rigid metal duct (preferred), do not exceed 

MAXIMUM venting run length of 64 ft., allow deductions for elbows 

and vents. If installing semi-rigid metal duct, do not exceed MAXIMUM 

venting run length of 8 ft., always allow deductions for elbows and 

vents. 

(Refer to Product Installation Guide on web for additional 

information.) 

Do NOT use flexible plastic or metal foil duct and use 

shortest run possible.

• 

Leveling legs supplied to level dryer properly and reduce excessive 

noise and vibration.

• 

For manufactured or mobile home installation optional Mobile Home 

Installation Kit (PN # 137067200) required. 

(For specific installation 

details, refer to Product Installation Guide on web.)

Note:  For planning purposes only. Refer to Product Installation Guide  

on the web at frigidaire.com for detailed instructions.

Optional Accessories

• 

Mobile Home Installation Kit – (PN # 137067200).

• 

Drying Rack – (PN # 137067300).

Top Load Dryer Specifications

• 

Product Shipping Weight (approx.) – 143 Lbs.

• 

Designed for HOME USE only, not recommended for commercial 

application. 

• 

An electrical supply with grounded three-prong receptacle is required.

• 

Voltage Rating – 240V / 60 Hz / 30 Amps

• 

Single phase 3- or 4-wire cable, 240 Volt, 60 Hertz AC only electrical 

supply with ground required on separate circuit fused on both sides 

of line. 

(Do not use same circuit as washer.)

• 

Connected Load (kW Rating) @ 240 Volts = 5.4 kW

• 

Amps @ 240 Volts = 24 Amps

• 

Dryer MUST employ a 3-conductor NEMA 10-30 type SRDT or 

4-conductor NEMA 14-30 type SRDT or ST (as required), rated at  

240 volt AC minimum, 30 amp power supply cord marked for  

use with clothes dryers 

(not supplied)

.

• 

Grounding through neutral link prohibited in specific applications and 

certain locales, requiring use of 4-wire system. 

(For detailed electrical 

requirements, refer to Product Installation Guide on web.)

• 

Always consult local and national electric codes.

• 

Dryer can be installed in recess or closet requiring 0" minimum 

installation clearance around sides and back of unit. To achieve  

0" minimum rear clearance, dryer MUST be vented straight back. 

Closet installation requires additional 1" minimum clearance between 

front of unit and vented door. Door MUST be vented with 120 sq. in. 

minimum louvered opening, equally divided, located 3" from top and 

bottom of door. A louvered door with equivalent air openings for full-

length of door is acceptable. Air openings MUST remain unobstructed 

with door installed. 

(For additional installation details, refer to Product 

Installation Guide on web.)

Top Load Laundry - Electric Dryer

Frigidaire Baseline (P Model)

Recess or Closet Installation

Dryer requires 0" minimum installation clearance 

around sides and back of unit. To achieve 0" minimum 

rear clearance, dryer MUST be vented straight back. 

Closet installation requires additional 1" minimum 

clearance between front of unit and vented door. Door 

MUST be vented with 120 sq. in. minimum louvered 

opening, equally divided, located 3" from top and 

bottom of door. A louvered door with equivalent air 

openings for full-length of door is acceptable. 

Air openings MUST remain unobstructed with door 

installed. For additional installation details, refer to 

Product Installation Guide on web.

29"

50"

Side

Reversible 

Door Swing

Vented door

0" min.

1" min.

Side

 60" 

sq. in.

min.

3"

 60" 

sq. in.

min.

3"

0" min.

0" min.

 23"

min.

Front

27"

38 

1

/

2

"

42 

1

/

2

"

Front

13 

1

/

2

"

3

/

4

"

Rear

vent        

240V 

Power 

supply (rear)