background image

5

 

Do not use flame to check for gas leaks.

Checking Manifold Gas Pressure

Disconnect the range and its individual shut-off valve from the
gas supply piping system during any pressure testing of that
system at test pressures greater than 14" of water column
pressure (approximately 1/2" psig).

The appliance must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 14" of water column pressure
(approximately 1/2" psig).

If it should be necessary to check the manifold gas pressure,
connect manometer (water gauge) or other pressure device to
the top burner right rear orifice.  Using a rubber hose with inside
diameter of approximately 1/4," hold tubing down tight over
orifice.  Turn burner valve on.

For an accurate pressure check have at least two (2) other top
burners burning. Be sure the gas supply (inlet) pressure is at
least one inch above specified range manifold pressure. The
gas supply pressure should never be over 14" water column.
When properly adjusted for Natural Gas the manifold pressure
is 4." (For LP/Propane Gas the manifold pressure is 10.")

 DO NOT allow regulator to turn on pipe

when tightening fittings.

a)

Install an external manual gas shut-off valve to gas supply
line in an accessible location outside of the range. Be sure
you know where and how to shut off the gas supply to the
range.

b)

Install 1/2" flare union adapter to pressure regulator using

NO MORE THAN 15ft./lbs.

 of torque

NOTE:

 Be sure to 

stabilize

 the left side of the pressure

regulator with  adjustable wrench before tightening  ANY
fittings to the pressure regulator (Refer to Fig. 4d).

c)

Tighten the gas supply fitting and/or appliance conduit to
flare union on the right side of the pressure regulator  using

NO MORE THAN 15ft./lbs.

 of torque.Be sure to 

stabilize

“ ON ”

Fig. 4d

Fig. 4e

Fig. 4f

the 1/2" flare union adapter with an adjustable wrench
before tightening  the gas supply fitting and/or appliance
conduit (Refer to Fig. 4e).

d)

Install flare union adapter to external manual shut-off valve.

e)

Attach appliance conduit to flare union on shut-off valve.

f)

Make sure service shut-off valve on pressure regulator
is in the "ON" position 

(See Fig. 4f).

g)

Check for leaks. Turn the gas supply on to the range and
use a liquid leak detector at all joints and conduits to
check for leaks in the system.

30" GAS RANGE INSTALLATION INSTRUCTIONS

(For Models with Sealed Top Burners)

Содержание 316259359

Страница 1: ...jury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach you...

Страница 2: ...llappliances Neverleave the oven door open when the range is unattended Stepping leaning or sitting on the doors ordrawersofthisrangecanresultinseriousinjuriesand can also cause damage to the range Do not store items of interest to children in the cabinets above the range Children could be seriously burned climbing on the range to reach items To eliminate the need to reach over the surface burners...

Страница 3: ...rovided for installation in wood or cement fastened to either the floor or wall When installed to the wall make sure that screws completely penetrate dry wall and are secured in wood or metal When fastening to the floor or wall be sure that screws do not penetrate electrical wiring or plumbing A LocatetheBracketUsingtheTemplate Bracketmay belocatedoneithertheleftorrightsideoftherange Use the infor...

Страница 4: ...essure to the regulator should be no more than 14 inches of water column pressure The inlet pressure to the regulator must be at least 1 inch greater than regulator manifold pressure Examples If regulator is set for natural gas 4 inch manifold pressure inlet pressure must be at least 5 inches if regulator has been convertedforLP Propanegas10inchmanifoldpressure inlet pressure must be at least 11 i...

Страница 5: ...ure is 4 For LP Propane Gas the manifold pressure is 10 DO NOT allow regulator to turn on pipe when tightening fittings a Installanexternalmanualgasshut offvalvetogassupply lineinanaccessiblelocationoutsideoftherange Besure you know where and how to shut off the gas supply to the range b Install1 2 flareunionadaptertopressureregulatorusing NO MORE THAN 15ft lbs of torque NOTE Be sure to stabilize ...

Страница 6: ...connection details first then connect electricity to range Before servicing disconnect electrical supply at circuit breaker fuse or power cord Electric Requirements A dedicated properly grounded and polarizedbranchcircuitprotectedbya15amp circuitbreaker or time delay fuse See serial plate for proper voltage Extension Cord Precautions Becauseofpotentialsafetyhazardsundercertainconditions we strongl...

Страница 7: ...ff Adjust flame until you can quickly turn knob from LITE to LOWEST POSITION without extinguishing the flame Flame should be as small as possible without going out Note Air mixture adjustment is not required on surface burners Test to verify if LOW setting should be adjusted a Push in and turn control to LITE until burner ignites b Push in and quickly turn knob to LOWEST POSITION c If burner goes ...

Страница 8: ... Youridentificationplatealsotellsyoutheratingoftheburners the type of fuel and the pressure the range was adjusted for when it left the factory 11 Air Shutter Broil Burner The approximate flame length of the broil burner is 1 inch distinct inner blue flame To determine if the broil burner flame is proper set the oven to broil Iftheflameisyellowincolor increaseairshutteropeningsize See 2 in illustr...

Отзывы: