Preliminary checks before startup 

s

 

Before starting up the unit, make sure that: 

s

 

The unit is positioned correctly; 

s

 

The flow and return pipes of the water system are correctly connected; 

s

 

The pipes are clean and free of air; 

s

 

The unit falls correctly towards the drainage outlet and the trap; 

s

 

The heat-exchangers are clean; 

s

 

The electrical connections are correct; 

s

 

The screws holding the cables are well tightened; 

s

 

The supply voltage is as required; 

s

 

The power consumption of the blower is correct and does not exceed the maximum permitted. 

10.6   Maintenance 
Caution: 

s

 

Maintenance work must only be carried out by qualified technicians authorized to work on air-conditioning 
and refrigeration systems. 

s

 

Use suitable work gloves. 

s

 

Do not use pointed objects through the air intake grilles. 

s

 

Disconnect the power supply before cleaning and maintenance. 

s

 

Use dry cloth to clean the unit. 

s

 

Always  disconnect  the  unit  from  the  mains  power  supply  at  the  main  isolator  switch  before  carrying  out 
maintenance work or checks. Make sure that no one accidentally supplies power to the machine; lock the 
main switch in the Off position. 

Scheduled maintenance 

s

 

Once a month 

Check the state of cleanliness of the air filters. The air filters are made of fibre and can be washed in water. The 
state of cleanliness of the filters must be checked regularly at the start of the operating season and on a monthly 
basis. 

s

 

Every six months 

Check the state of cleanliness of the heat-exchanger and the condensation drain-tube. 
Switch  off  the  unit,  remove  the  casing  of  the  machine  and  check  the  state  of  the  heat-exchanger  and  the 
condensation drain-tube if necessary: 
1.  Remove any obstacle from the surface which may obstruct air flow; 
2.  Clean the dust with a jet of compressed air; 
3.  Wash and brush gently with water; 
4.  Dry with a jet of compressed air; 
5.  Check that there are no obstacles in the condensation drain tube which could prevent the normal flow of 

water. 

Release the air in the water system. 

1.  Remove the casing of the machine (for casing type); 
2.  Start the system and run for a few minutes; 
3.  Stop the system; 

Содержание Kaysun KFC-S-2T-250D

Страница 1: ...KFC S 2T 250D KFC S 2T 400D KFC S 2T 500D KFC S 2T 900D KFC SE 2T 250D KFC SE 2T 400D KFC SE 2T 500D KFC SE 2T 900D Kaysun reserves the right to discontinue or change specification or designs at any...

Страница 2: ...ture 3 5 Specifications 4 6 Capacity Table 4 7 Dimensions 17 8 Sound Levels 20 9 Service Spaces 10 10 Wiring Diagrams 21 11 Installation 22 11 1 Transport and handling 22 11 2 Storage conditions 22 11...

Страница 3: ...iciency and low operating sound level Due to the DC fan motor the unit operates in lower power consumption and lower operating sound level Meet CE certification requirements The unit can meet the late...

Страница 4: ...Power supply KFC SE 2T 250D KFC S 2T 250D 250 KFC SE 2T 400D KFC S 2T 400D 400 KFC SE 2T 500D KFC S 2T 500D 500 KFC SE 2T 900D KFC S 2T 900D 900 4 Nomenclature K FC S 250 D D Power type Nominal air v...

Страница 5: ...otor Type DC Motor Quantity 1 Fan Type Centrifugal forward curved Blades Quantity 1 Coil Row 3 Max working pressure MPa 1 6 Diameter mm 9 52 Body H3 series Net dimensions W H D mm 550 545 212 Packing...

Страница 6: ...44 37 31 42 35 27 Rated current A 0 4 0 4 Fan motor Type DC Motor DC Motor Quantity 1 1 Fan Type Centrifugal forward curved Blades Quantity 2 2 Coil Row 2 3 Max working pressure MPa 1 6 1 6 Diameter m...

Страница 7: ...motor Type DC Motor Quantity 1 Fan Type Centrifugal forward curved Blades Quantity 3 Coil Row 2 Max working pressure MPa 1 6 Diameter mm 9 52 Body H3 series Net dimensions W H D mm 1250 545 212 Packin...

Страница 8: ...11 39 1 91 1 85 0 41 11 26 2 07 2 07 0 44 12 98 19 2 59 1 17 0 56 18 99 2 57 1 39 0 55 18 79 2 55 1 61 0 55 18 6 2 5 1 81 0 54 17 97 2 41 1 99 0 52 16 8 20 2 92 1 16 0 63 23 4 2 9 1 38 0 62 23 2 2 89...

Страница 9: ...52 1 29 0 44 12 04 1 56 1 52 0 45 12 53 4 15 0 59 0 59 0 13 0 92 0 81 0 81 0 17 2 43 1 02 1 02 0 22 3 73 1 23 1 23 0 27 5 12 1 44 1 44 0 31 6 67 17 0 6 0 6 0 13 0 97 0 81 0 81 0 17 2 44 1 02 1 02 0 22...

Страница 10: ...19 2 87 2 87 0 62 21 86 19 3 46 1 58 0 74 30 25 3 44 1 89 0 74 29 91 3 42 2 2 0 74 29 65 3 4 2 51 0 73 29 37 3 31 2 79 0 71 27 99 20 3 91 1 54 0 84 37 34 3 89 1 86 0 84 37 08 3 87 2 17 0 83 36 72 3 8...

Страница 11: ...1 2 02 1 78 0 58 18 87 2 13 2 13 0 61 20 71 4 15 0 81 0 81 0 17 2 35 1 11 1 11 0 24 4 14 1 41 1 41 0 3 6 18 1 7 1 7 0 37 8 53 1 99 1 99 0 43 11 19 17 0 82 0 82 0 18 2 42 1 11 1 11 0 24 4 14 1 41 1 41...

Страница 12: ...17 0 9 27 09 19 5 23 2 37 1 12 39 96 5 19 2 81 1 12 39 55 5 16 3 25 1 11 39 05 5 02 3 63 1 08 37 22 4 88 4 01 1 05 35 43 20 5 9 2 34 1 27 49 3 5 87 2 78 1 26 48 85 5 83 3 22 1 25 48 35 5 74 3 63 1 24...

Страница 13: ...25 32 3 08 2 59 0 88 25 29 3 14 3 05 0 9 26 22 4 15 1 2 1 2 0 26 2 98 1 63 1 63 0 35 5 22 2 06 2 06 0 44 7 74 2 48 2 48 0 53 10 63 2 9 2 9 0 62 13 87 17 1 22 1 22 0 26 3 13 1 63 1 63 0 35 5 22 2 06 2...

Страница 14: ...5 6 25 1 34 22 35 19 7 35 3 36 1 58 29 58 7 29 4 05 1 57 29 18 7 25 4 75 1 56 28 91 7 22 5 45 1 55 28 7 7 17 6 13 1 54 28 32 20 8 29 3 27 1 78 36 51 8 27 3 98 1 78 36 31 8 21 4 67 1 77 35 9 8 17 5 37...

Страница 15: ...6 4 25 3 88 1 22 18 19 4 6 4 6 1 32 20 83 4 15 1 74 1 74 0 38 2 41 2 4 2 4 0 52 4 17 3 05 3 05 0 66 6 26 3 7 3 7 0 8 8 68 4 34 4 34 0 93 11 41 17 1 76 1 76 0 38 2 44 2 4 2 4 0 52 4 17 3 05 3 05 0 66 6...

Страница 16: ...96 0 29 4 66 3 72 0 27 4 18 3 48 0 25 3 73 KFC SE 2T 400D EWT T Indoor temperature D B 16 18 20 22 TH WF WPD TH WF WPD TH WF WPD TH WF WPD kW m3 h kPa kW m3 h kPa kW m3 h kPa kW m3 h kPa 40 5 3 32 0 5...

Страница 17: ...61 7 43 0 54 8 62 6 95 0 5 7 68 KFC SE 2T 900D EWT T Indoor temperature D B 16 18 20 22 TH WF WPD TH WF WPD TH WF WPD TH WF WPD kW m3 h kPa kW m3 h kPa kW m3 h kPa kW m3 h kPa 40 5 7 42 1 28 17 28 6 6...

Страница 18: ...sed type Dimensions unit mm Size 250D 400D 500D 900D A 800 1000 1200 1500 B 584 784 984 1284 C 500 700 900 1200 D 526 726 926 1226 592 220 14 3 A B 592 115 345 74 D 140 55 203 291 115 258 105 185 207...

Страница 19: ...an Coil Unit 18 Uncased type Dimensions unit mm Size 250D 400D 500D 900D A 550 750 950 1250 B 526 726 926 1226 C 500 700 900 1200 D 532 732 932 1232 212 545 A D 126 345 B 46 105 203 291 185 258 A C 21...

Страница 20: ...7 Sound Levels Model 250D 400D SE H M L 39 31 22 44 37 31 S H M L 39 31 22 44 37 31 Model 500D 900D SE H M L 42 35 27 51 42 35 S H M L 42 35 27 51 42 35...

Страница 21: ...DC Fan Coil Unit 20 8 Service Spaces Cased type a mm 150 b mm 20 Uncased type a mm 200 b mm 80 a a b a a b a a...

Страница 22: ...9 Wiring Diagrams...

Страница 23: ...g material in accordance with current legislation at the appropriate waste reception or recycling site The units may be moved or lifted either by hand or by means of a suitable trolley If the weight o...

Страница 24: ...ned to work with air conditioning and refrigeration systems Incorrect installation could lead to unit malfunctioning and a consequent deterioration in performance For installation follow the instructi...

Страница 25: ...water coils including the optional extras are equipped with air release valves next to the upper union and with water drain valves next to the lower union All the valves can be opened and closed with...

Страница 26: ...l and supplementary coils round can be carried out on site but it is preferable to do it before installation on solid ground Procedure to reverse the coil 1 Remove the casing for casing type 2 Remove...

Страница 27: ...er supply system complies with current national safety regulations s Electrical connections must be made in accordance with the wiring diagrams supplied with the machine For connection to the power su...

Страница 28: ...t the main isolator switch before carrying out maintenance work or checks Make sure that no one accidentally supplies power to the machine lock the main switch in the Off position Scheduled maintenanc...

Страница 29: ...eter and compare with the values shown on the document Replace the fan assembly In case of burnout of the fan motor it is necessary to replace the entire fan assembly Procedure for removal of the fan...

Страница 30: ......

Страница 31: ...DC Fan Coil Unit 30...

Страница 32: ......

Отзывы: