Frigicoll Kaysun KFC-S-2T-250D Скачать руководство пользователя страница 27

 

 

  DC Fan Coil Unit

 

26 

 

 

effect in the country where the unit is installed. The company shall not be held liable for damage to persons or 
property caused by incorrect electrical connection. 
The power cord type designation is H05RN-R or above/H07RN-F. 
This appliance can be operated by children aged from 8 years and above and persons with reduced physical 
sensory  or  mental  capabilities  or  lack  of  experience  and  knowledge,  if  they  have  been  given  supervision  or 
instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not 
play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. 
The appliance shall be installed in accordance with national wiring regulations. 

Danger! 

Always  install  a  general  automatic  switch  in  a  protected  area  near  the  appliance  with  an  adequate  capacity 
characteristic  delayed  curve  with  sufficient  breaking  power.  There  should  be  a  minimum  distance  of  3mm 
between the contacts. Earth connection is compulsory by law to ensure user safety while the machine is in use. 

Air flow 

255-1530m

3

/h 

Power supply voltage 

220-240V 

Power supply phase 

1 phase 

Power supply frequency 

50Hz 

Circuit breaker / Fuse 

15A / 15A 

Wiring   

s

 

See product wiring nameplate. 

s

 

Check  that  the  voltage  and  the  frequency  of  the  power  supply  correspond  to  220-240V  single  phase  at 
50Hz;that the available power is sufficient for the running the equipment; and that the supply cables are of 
adequate section for the maximum current which will be required. 

s

 

Make sure that the power supply system complies with current national safety regulations.   

s

 

Electrical connections must be made in accordance with the wiring diagrams supplied with the machine. For 
connection  to  the  power  supply  network,  use  double-insulated  flexible  cable,  twin  pole  +  earth,  section 
1.5mm2, type H05RN-F. 

s

 

Pass the power supply cable through the slot beside the air filter. Use the cable clamp provided on the inner 
side of the panel to secure the power supply cable and the connecting cables, and strip only the length of 
cable needed to go into the connector block. In the event that the unit is mounted on a metal surface, earth 
connections must be made in compliance with local regulations. If the optional extra electric heating element 
is fitted, a separate power supply must be provided. Use double-insulated flexible cable, twin pole + earth, 
section 2.5mm2, type H05RN-F. 

Startup instructions 
Caution: 

Machine commissioning or the first startup must be carried out by skilled personnel qualified to work on this type 
of product. 
Before starting up, make sure that the installation and electrical connections have been carried out in accordance 
with the instructions in this manual. Also make sure that there are no unauthorized persons in the vicinity of the 
machine during these operations. 

Pipeline system has been vacuumed before initial start the equipment. 

1.  Remove the connecting pipe’s side cover panel by cross screwdriver.     
2.  Remove the bolts that showed at the figure by slotted screwdriver. Start up the pump to circulate the pipeline 

water and vacuum air from the system until there have water flow out from bolt holes, and then tighten the 
bolts of the system. 

3.  Shutdown the system that showed at the figure by slotted screwed and replaces the side cover panel. 

Содержание Kaysun KFC-S-2T-250D

Страница 1: ...KFC S 2T 250D KFC S 2T 400D KFC S 2T 500D KFC S 2T 900D KFC SE 2T 250D KFC SE 2T 400D KFC SE 2T 500D KFC SE 2T 900D Kaysun reserves the right to discontinue or change specification or designs at any...

Страница 2: ...ture 3 5 Specifications 4 6 Capacity Table 4 7 Dimensions 17 8 Sound Levels 20 9 Service Spaces 10 10 Wiring Diagrams 21 11 Installation 22 11 1 Transport and handling 22 11 2 Storage conditions 22 11...

Страница 3: ...iciency and low operating sound level Due to the DC fan motor the unit operates in lower power consumption and lower operating sound level Meet CE certification requirements The unit can meet the late...

Страница 4: ...Power supply KFC SE 2T 250D KFC S 2T 250D 250 KFC SE 2T 400D KFC S 2T 400D 400 KFC SE 2T 500D KFC S 2T 500D 500 KFC SE 2T 900D KFC S 2T 900D 900 4 Nomenclature K FC S 250 D D Power type Nominal air v...

Страница 5: ...otor Type DC Motor Quantity 1 Fan Type Centrifugal forward curved Blades Quantity 1 Coil Row 3 Max working pressure MPa 1 6 Diameter mm 9 52 Body H3 series Net dimensions W H D mm 550 545 212 Packing...

Страница 6: ...44 37 31 42 35 27 Rated current A 0 4 0 4 Fan motor Type DC Motor DC Motor Quantity 1 1 Fan Type Centrifugal forward curved Blades Quantity 2 2 Coil Row 2 3 Max working pressure MPa 1 6 1 6 Diameter m...

Страница 7: ...motor Type DC Motor Quantity 1 Fan Type Centrifugal forward curved Blades Quantity 3 Coil Row 2 Max working pressure MPa 1 6 Diameter mm 9 52 Body H3 series Net dimensions W H D mm 1250 545 212 Packin...

Страница 8: ...11 39 1 91 1 85 0 41 11 26 2 07 2 07 0 44 12 98 19 2 59 1 17 0 56 18 99 2 57 1 39 0 55 18 79 2 55 1 61 0 55 18 6 2 5 1 81 0 54 17 97 2 41 1 99 0 52 16 8 20 2 92 1 16 0 63 23 4 2 9 1 38 0 62 23 2 2 89...

Страница 9: ...52 1 29 0 44 12 04 1 56 1 52 0 45 12 53 4 15 0 59 0 59 0 13 0 92 0 81 0 81 0 17 2 43 1 02 1 02 0 22 3 73 1 23 1 23 0 27 5 12 1 44 1 44 0 31 6 67 17 0 6 0 6 0 13 0 97 0 81 0 81 0 17 2 44 1 02 1 02 0 22...

Страница 10: ...19 2 87 2 87 0 62 21 86 19 3 46 1 58 0 74 30 25 3 44 1 89 0 74 29 91 3 42 2 2 0 74 29 65 3 4 2 51 0 73 29 37 3 31 2 79 0 71 27 99 20 3 91 1 54 0 84 37 34 3 89 1 86 0 84 37 08 3 87 2 17 0 83 36 72 3 8...

Страница 11: ...1 2 02 1 78 0 58 18 87 2 13 2 13 0 61 20 71 4 15 0 81 0 81 0 17 2 35 1 11 1 11 0 24 4 14 1 41 1 41 0 3 6 18 1 7 1 7 0 37 8 53 1 99 1 99 0 43 11 19 17 0 82 0 82 0 18 2 42 1 11 1 11 0 24 4 14 1 41 1 41...

Страница 12: ...17 0 9 27 09 19 5 23 2 37 1 12 39 96 5 19 2 81 1 12 39 55 5 16 3 25 1 11 39 05 5 02 3 63 1 08 37 22 4 88 4 01 1 05 35 43 20 5 9 2 34 1 27 49 3 5 87 2 78 1 26 48 85 5 83 3 22 1 25 48 35 5 74 3 63 1 24...

Страница 13: ...25 32 3 08 2 59 0 88 25 29 3 14 3 05 0 9 26 22 4 15 1 2 1 2 0 26 2 98 1 63 1 63 0 35 5 22 2 06 2 06 0 44 7 74 2 48 2 48 0 53 10 63 2 9 2 9 0 62 13 87 17 1 22 1 22 0 26 3 13 1 63 1 63 0 35 5 22 2 06 2...

Страница 14: ...5 6 25 1 34 22 35 19 7 35 3 36 1 58 29 58 7 29 4 05 1 57 29 18 7 25 4 75 1 56 28 91 7 22 5 45 1 55 28 7 7 17 6 13 1 54 28 32 20 8 29 3 27 1 78 36 51 8 27 3 98 1 78 36 31 8 21 4 67 1 77 35 9 8 17 5 37...

Страница 15: ...6 4 25 3 88 1 22 18 19 4 6 4 6 1 32 20 83 4 15 1 74 1 74 0 38 2 41 2 4 2 4 0 52 4 17 3 05 3 05 0 66 6 26 3 7 3 7 0 8 8 68 4 34 4 34 0 93 11 41 17 1 76 1 76 0 38 2 44 2 4 2 4 0 52 4 17 3 05 3 05 0 66 6...

Страница 16: ...96 0 29 4 66 3 72 0 27 4 18 3 48 0 25 3 73 KFC SE 2T 400D EWT T Indoor temperature D B 16 18 20 22 TH WF WPD TH WF WPD TH WF WPD TH WF WPD kW m3 h kPa kW m3 h kPa kW m3 h kPa kW m3 h kPa 40 5 3 32 0 5...

Страница 17: ...61 7 43 0 54 8 62 6 95 0 5 7 68 KFC SE 2T 900D EWT T Indoor temperature D B 16 18 20 22 TH WF WPD TH WF WPD TH WF WPD TH WF WPD kW m3 h kPa kW m3 h kPa kW m3 h kPa kW m3 h kPa 40 5 7 42 1 28 17 28 6 6...

Страница 18: ...sed type Dimensions unit mm Size 250D 400D 500D 900D A 800 1000 1200 1500 B 584 784 984 1284 C 500 700 900 1200 D 526 726 926 1226 592 220 14 3 A B 592 115 345 74 D 140 55 203 291 115 258 105 185 207...

Страница 19: ...an Coil Unit 18 Uncased type Dimensions unit mm Size 250D 400D 500D 900D A 550 750 950 1250 B 526 726 926 1226 C 500 700 900 1200 D 532 732 932 1232 212 545 A D 126 345 B 46 105 203 291 185 258 A C 21...

Страница 20: ...7 Sound Levels Model 250D 400D SE H M L 39 31 22 44 37 31 S H M L 39 31 22 44 37 31 Model 500D 900D SE H M L 42 35 27 51 42 35 S H M L 42 35 27 51 42 35...

Страница 21: ...DC Fan Coil Unit 20 8 Service Spaces Cased type a mm 150 b mm 20 Uncased type a mm 200 b mm 80 a a b a a b a a...

Страница 22: ...9 Wiring Diagrams...

Страница 23: ...g material in accordance with current legislation at the appropriate waste reception or recycling site The units may be moved or lifted either by hand or by means of a suitable trolley If the weight o...

Страница 24: ...ned to work with air conditioning and refrigeration systems Incorrect installation could lead to unit malfunctioning and a consequent deterioration in performance For installation follow the instructi...

Страница 25: ...water coils including the optional extras are equipped with air release valves next to the upper union and with water drain valves next to the lower union All the valves can be opened and closed with...

Страница 26: ...l and supplementary coils round can be carried out on site but it is preferable to do it before installation on solid ground Procedure to reverse the coil 1 Remove the casing for casing type 2 Remove...

Страница 27: ...er supply system complies with current national safety regulations s Electrical connections must be made in accordance with the wiring diagrams supplied with the machine For connection to the power su...

Страница 28: ...t the main isolator switch before carrying out maintenance work or checks Make sure that no one accidentally supplies power to the machine lock the main switch in the Off position Scheduled maintenanc...

Страница 29: ...eter and compare with the values shown on the document Replace the fan assembly In case of burnout of the fan motor it is necessary to replace the entire fan assembly Procedure for removal of the fan...

Страница 30: ......

Страница 31: ...DC Fan Coil Unit 30...

Страница 32: ......

Отзывы: