Friedrich XStar EQ08M11-A Скачать руководство пользователя страница 40

4

INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE

FORM FOR ROOM AIR CONDITIONERS

(AHAM PUB. NO. RAC-1)

A.  This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations 

which do not require specifi c conditions of inside temperature and humidity.

B.  The form is based on an outside design temperature of 95°F dry bulb and 75°F wet bulb. It can be used for areas 

in the continental United States having other outside design temperatures by applying a correction factor for the 

particular locality as determined from the map.

C.  The form includes “day” factors for calculating cooling loads in rooms where daytime comfort is desired (such as 

living rooms, offi ces, etc.)

D.  The numbers of the following paragraphs refer to the corresponding numbered item on the form:
 

1.  Multiply the square feet of window area for each exposure by the applicable factor. The window area is the 

area of the wall opening in which the window is installed.  For windows shaded by inside shades or venetian 

blinds, use the factor for “Inside Shades.”  For windows shaded by outside awnings or by both outside aw-

nings and inside shades (or venetian blinds), use the factor for “Outside Awnings.”  “Single Glass” includes 

all types of single thickness windows, and “Double Glass” includes sealed airspace types, storm windows, 

and glass block.  Only one number should be entered in the right hand column for Item 1, and this number 

should represent 

only the exposure with the largest load.

 

2.  Multiply the total square feet of 

all

 windows in the room by the applicable factor.

 

3a.  Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should 

be considered as being part of the wall.  Outside walls facing due north should be calculated separately from 

outside walls facing other directions.  Walls which are permanently shaded by adjacent structures should be 

considered “North Exposure.”  Do not consider trees and shrubbery as providing permanent shading.  An 

uninsulated frame wall or a masonry wall 8 inches or less in thickness is considered “Light Construction.”  An 

insulated wall or masonry wall over 8 inches in thickness is considered “Heavy Construction.”

 

3b.  Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any uncondi-

tioned spaces by the given factor.  Do not include inside walls which separate other air conditioned rooms.

 

4.  Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly 

describing the particular application (use one line only.)

 

5.  Multiply the total square feet of fl oor area by the factor given.  Disregard this item if the fl oor is directly on the 

ground or over a basement.

 

6.  Multiply the number of people who normally occupy the space to be air conditioned by the factor given. Use 

a minimum of 2 people.

 

7.  Determine the total number of watts for light and electrical equipment, except the air conditioner itself, that 

will be 

in use 

when the room air conditioning is operating.  Multiply the total wattage by the factor given.

 

8.  Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned 

space by the applicable factor.

 

 

NOTE:  

Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated 

value. In such cases, both adjoining rooms should be considered as a single large room, and the room air 

conditioner unit or units should be selected according to a calculation made on this new basis.

 

9.  Total the loads estimated for the foregoing 8 items.

 

10.  Multiply the subtotal obtained in item 9 by the proper correction factor, selected from the map, for the particular 

locality. The result is the total estimated design cooling load in BTU per hour.

E.  For best results, a room air conditioner unit or units having a cooling capacity rating (determined in accordance 

with the NEMA Standards Publication for Room Air Conditioners, CN 1-1960) as close as possible to the estimated 

load should be selected.  In general, a greatly oversized unit which would operate intermittently will be much less 

satisfactory than one which is slightly undersized and which would operate more nearly continuously. 

F.  Intermittent loads such as kitchen and laundry equipment are not included in this form.

39

Содержание XStar EQ08M11-A

Страница 1: ...nditioners 2 0 1 0 X Star ServMan 4 10 115 Volt XQ05M10A XQ06M10A XQ08M10A XQ10M10A Cool Only 115 Volt EQ08M11A Cool with Electric Heat Money Fan Set Hr Stop Start Temperature Fan Cool On Cooler Warme...

Страница 2: ...e the EQ 10 Electronic Control Sequence of Operation 11 Functional Component Definition 12 Components Testing 13 16 Refrigeration Sequence of Operation 17 R 410A Sealed System Repair Considerations 18...

Страница 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Страница 4: ...contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious b...

Страница 5: ...or not following the above Safety Warnings can result in water damage to personal items or property Insure that the unit has a sufficient pitch to the outside to allow water to drain from the unit Do...

Страница 6: ...M Dec 1st Digit Function E Electric Heat X Straight Cool 2nd Digit Q Q Star Chassis Size 3rd and 4th Digit Approximate BTU HR in 1000s Cooling Heating BTU Hr capacity listed in the Specification Perf...

Страница 7: ...eve Height Width Depth with Front Shell Depth to Louvers Minimum Extension Into Room Minimum Extension Outside Window Width Thru the wall Installation Finished Hole Minimum Maximum Height Width Max De...

Страница 8: ...ze fuse circuit breaker Read electrical ratings on unit s rating plate Proper circuit protection is the responsibiity of the homeowner Grounding Unit MUST be grounded from branch circuit through servi...

Страница 9: ...e h t f o g n i t a r e g a r e p m a e h t t a h t e r u s e b t i n u s i h t e t a c o l e r r o or time delay fuse does not exceed the amp rating listed in Figure 1 DO NOT use an extension cord T...

Страница 10: ...example if the outside doorsin your home are opened for an extended period of time or more people enter a room Smart Fan may adjust to a higher fan speed to compensate for the increased heat load Thi...

Страница 11: ...he fan only 4 MoneySaver Press the MoneySaver button to activate the MoneySaver feature This feature cycles the fan with the compres sor so that the fan does not run all the time To adjust temperature...

Страница 12: ...the fan will turn on for a period of 90 seconds for air sampling Operation in MONEY SAVER mode will light both the MONEY SAVER and COOL indicators ELECTRONIC CONTROL SEQUENCE OF OPERATION 11 FAN ONLY...

Страница 13: ...hoot ing refer to the wiring diagrams and schematics in the back of this service manual Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristic...

Страница 14: ...rature set point will appear COMPONENTS TESTING ERROR CODE LISTINGS E1 SHORT CYCLE SITUATION Defined as compressor powered on before the three minute time delay ten times in one hour Investigate and c...

Страница 15: ...mation on thermostat testing THERMOSTAT ADJUSTMENT No attempt should be made to adjust thermostat Due to the sensitivity of the internal mechanism and the sophisticated equipment required to check the...

Страница 16: ...possibility of capacitor failure is much greater when the identified terminal is connected to the S or start terminal The identified terminal should always be connected to the supply line or R termin...

Страница 17: ...the connecting wires have been removed A cold resistance reading of approximately 10 11 ohms for the 1 15 KW heater should be registered Figure Heating Element DRAIN PAN VALVE During the cooling mode...

Страница 18: ...sed changed to a Liquid before leaving the condenser coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid It next will pass through the refrigerant dri...

Страница 19: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Страница 20: ...ad failure SealedRefrigerationSystemcontainsrefrigerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants...

Страница 21: ...FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious in...

Страница 22: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Страница 23: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Страница 24: ...Test NOTE Consult the speci cation and performance section for running amperage The L R A can also be found on the rating plate Select the proper amperage scale and clamp the meter probe around the wi...

Страница 25: ...oint of contact as a good connection is a must and the other probe in turn to each compressor terminal If a reading is obtained the compressor is grounded and must be replaced Check the complete elect...

Страница 26: ...em will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R410 A and nitrogen and leak test all connections with an electronic o...

Страница 27: ...refrigerant and oil from the system Remove compressor capillary tube and filter drier from the system Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent Use approved...

Страница 28: ...ems Allow all items to dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mecha...

Страница 29: ...thoroughly before reinstalling it in the chassis CLEARANCES Inspect the surrounding area inside and outside to ensure that the unit s clearances have not been compromised or altered ROUTINE MAINTENAN...

Страница 30: ...MPS AMPS RUNNING AMPERAGE DRAW AMPS INDOOR TEMPERATURES INDOOR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F OUTDOO...

Страница 31: ...I Power Cord Trips Reset Button Pops Out The LCDI power cord can trip Reset button pops out due to disturbances on your power supply line Press and release RESET listen for click Reset button latches...

Страница 32: ...size is then selected to meet the heating load In extreme northern climates room air conditioners may not be able to be used as a primary source of heat Unit Runs Too Much This may be due to an exces...

Страница 33: ...es not run Inoperative system switch Test switch replace if inoperative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan spe...

Страница 34: ...Check temp differential delta T across coil Touch test coil return bends for same temp Test for low running current n o i t c A e s u a C e l b i s s o P m e l b o r P Compressor runs continually does...

Страница 35: ...If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board...

Страница 36: ...ycles Defective thermistor Replace thermistor or electronic control board T stat differential too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gas...

Страница 37: ...uring ON cycle of compressor or fan n o i t c A e s u a C e l b i s s o P m e l b o r P Does not heat adequately Opened doors or windows Close doors or windows Dirty l a u n a M s r e n w O n i d e d...

Страница 38: ...ELECTRONIC CONTROL COOL ONLY MODELS XQ05M10A XQ06M10A XQ08M10A XQ10M10A 37...

Страница 39: ...ELECTROMECHANICAL CONTROL COOL WITH ELECTRIC HEAT MODEL EQ08M11A 38...

Страница 40: ...thickness is considered Light Construction An insulated wall or masonry wall over 8 inches in thickness is considered Heavy Construction 3b Multiply the total length linear feet of all inside walls b...

Страница 41: ...FEET OF WIDTH 9 SUBTOTAL 10 TOTAL COOLING LOAD BTU per hour to be used for selection of room air conditioner s No Shades 60 80 75 75 110 150 120 0 ____sq ft ____sq ft ____sq ft ____sq ft ____sq ft ___...

Страница 42: ...e unit capacity line intersect read down to the outdoor ambient temperature scale and nd that this unit will deliver the required BTU Hr capacity to approximately 30 F The heat load form on the follow...

Страница 43: ...insulated Sq Ft x 0 10 Built up Roof 1 2 insulated Sq Ft x 0 20 No Insulation Sq Ft x 0 33 FLOOR Area Sq Ft Above Vented Crawl space Insulated 1 Sq Ft x 0 20 Uninsulated Sq Ft x 0 50 Slab on Ground Li...

Страница 44: ...damage which results from improper installation wiring electrical current characteristics or installed in a corrosive atmosphere default or delay in performance caused by war government restrictions...

Страница 45: ...ox 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 877 599 5665 x 846 FAX 210 357 4490 Email tac friedrich com www friedrich com Printed in the U S...

Страница 46: ......

Страница 47: ...Man 4 10 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed i...

Отзывы: