Friedrich WallMaster WE10C33-A Скачать руководство пользователя страница 28

Recommended procedure for compressor  

replacement

 

1.    Be  certain  to  perform  all  necessary  electrical  and 

refrigeration  tests  to  be  sure  the  compressor  is 

actually defective before replacing. 

2.    Recover  all  refrigerant  from  the  system  though 

the  process  tubes. 

PROPER  HANDLING  OF 

RECOVERED  REFRIGERANT  ACCORDING  TO 

EPA  REGULATIONS  IS  REQUIRED. 

  Do  not  use 

gauge  manifold  for  this  purpose  if  there  has  been 

a  burnout.  You  will  contaminate  your  manifold  and 

hoses.  Use  a  Schrader  valve  adapter  and  copper 

tubing for burnout failures.

3.     After  all  refrigerant  has  been  recovered,  disconnect  

suction and discharge lines from the compressor and  

remove compressor. Be certain to have both suction  

and discharge process tubes open to atmosphere. 

4.     Carefully pour a small amount of oil from the suction  

stub  of  the  defective  compressor  into  a  clean 

container.  

9.      Evacuate the system with a good vacuum pump capable    

of a final vacuum of 300 microns or less. The system

 

should be evacuated through both liquid line and suction 

line gauge ports. While the unit is being evacuated, seal 

all openings on the defective compressor. Compressor 

manufacturers will void warranties on units received not 

properly sealed. Do not distort the manufacturers tube 

connections.   

10.    Recharge  the  system  with  the  correct  amount  of 

  refrigerant.  The  proper  refrigerant  charge  will  be 

   found on the unit rating plate. The use of an accurate

         measuring device, such as a charging cylinder,

         electronic scales or similar device is necessary.

 

COMPREssOR REPlACEMENT

5.     Using an acid test kit (one shot or conventional kit), test  

the  oil  for  acid  content  according  to  the  instructions  

with the kit. 

6.   If any evidence of a burnout is found, no matter how  

slight, the system will need to be cleaned up following  

proper procedures. 

7.    Install the replacement compressor. 

8.    Pressurize  with  a  combination  of  R-22  and  nitrogen  

      and  leak  test  all  connections  with  an  electronic  or  

      Halide  leak  detector.  Recover  refrigerant  and  repair 

      any leaks found. 

 

Repeat Step 8 to insure no more leaks are present.

Unplug and/or disconnect all electrical power 

to the unit before performing inspections, 

maintenances or service.  

 

Failure to do so could result in electric shock, 

serious injury or death.

WARNING

RISK OF ELECTRIC SHOCK 

Sealed Refrigeration System contains refrigerant 

and oil under high pressure.

Proper safety procedures must be followed, 

and proper protective clothing must be worn 

when working with refrigerants.

Failure  to  follow  these  procedures  could 

result in serious injury or death. 

WARNING

HIGH PRESSURE HAZARD 

Extreme care, proper judgment and all safety 

procedures  must  be  followed  when  testing, 

troubleshooting, handling or working around 

unit while in operation with high temperature 

components.  Wear  protective  safety  aids 

such as: gloves, clothing etc. 

Failure to do so could result in serious burn 

injury.

WARNING

HIGH TEMPERATURES 

The  use  of  a  torch  requires  extreme  care  and  proper 

judgment.  Follow  all  safety  recommended  precautions 

and  protect  surrounding  areas  with  fire  proof  materials. 

Have a fire extinguisher readily available. Failure to follow 

this  notice  could  result  in  moderate  to  serious  property 

damage.

NOTICE

FIRE HAZARD 

The use of nitrogen requires a pressure

regulator. Follow all safety procedures and 

wear protective safety clothing etc. 

Failure to follow proper safety procedures 

result in serious injury or death. 

WARNING

EXPLOSION HAZARD 

Proper safety procedures must be followed, 

and proper protective clothing must be worn 

when working with liquid refrigerant.

Failure to follow these procedures could 

result in minor to moderate injury.

CAUTION

FREEZE HAZARD 

27

Содержание WallMaster WE10C33-A

Страница 1: ...WS13C30A WS15C30A Cool Only 115 Volt WE10C33A WE13C33A WE15C33A Cool with Electric Heat 230 Volt WY09C33A WY12C33A Heat Pump with Electric Heat Back Up WallMaster Money Fan Timer Operation Set Hr Sto...

Страница 2: ...ration Repairs Charging 17 20 Hermetic Components Check 21 Reversing Valve Description Operation 22 Testing the Coil and Reversing Valve 23 24 Compressor Checks 25 26 Compressor Replacement 27 28 Rout...

Страница 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Страница 4: ...contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious b...

Страница 5: ...drain from the unit Do not drill holes in the bottom of the drain pan or the underside of the unit Failure to follow these instructions can result in result in damage to the unit and or minor to seri...

Страница 6: ...n 5th DIGIT ALPHABETICAL MODIFIER 6th DIGIT VOLTAGE 1 115 Volts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models 3 3 KW Heat Strip Nominal 8th DIGIT Major Change A K A X 00001 A Jan D Apr G...

Страница 7: ...706 16 0 14 7 3550 2950 8 5 8 5 4 2 290 WSD 116 DEFROST CONTROL Initiated at 30 F outdoor coil temperature for two consecutive minutes and terminated at 43 F outdoor coil temperature During defrost th...

Страница 8: ...can be certain that the AHAM Certification Seal accurately states the unit s cooling and heating capacity rating the amperes and the energy efficiency ratio electrical DATA ELECTRIC SHOCK HAZARD WARN...

Страница 9: ...r Power PM Cool Fan Only Heat Clock Start Time Stop Time Smart Fan Fan Speed Mode Timer On Off Money Saver Set Hour 2 3 4 1 6 5 7 9 8 10 11 12 14 13 Figure2 WY WEModelheat coolcontrolpanel Figure 1 WS...

Страница 10: ...eset or theTimer On Off will not function when desired To Activate Money Saver WY WE models 14 Press the Money Saver button to activate the Money Saver feature The light will indicate the Money Saver...

Страница 11: ...tton once to see the current clock setting Continue pressing the button until you arrive at the current time Hour only Minutes are not shown on the display Make sure that the A M P M setting is correc...

Страница 12: ...ive presses will scroll through all error codes stored Press the Temp Hour button to see the reverse order of the error codes When the end of the stored error codes is reached the temperature Set Poin...

Страница 13: ...PEN OR SHORT Control will assume ambient temperature is 90 degrees F when in Cool mode and 60 degrees F when in Heat mode Unit will operate see note below E4 EVAPORATOR TEMPERATURE PROBE OPEN OR SHORT...

Страница 14: ...illustrations below If the outdoor coil thermister reaches 43 degrees and the compressor has waited the standard delay time of 180 240 seconds the control will 1 Turn off the backup electric heat 2 W...

Страница 15: ...tor Connections The starting winding of a motor can be damaged by a shorted and grounded running capacitor This damage usually can be avoided by proper connection of the running capacitor terminals Fr...

Страница 16: ...sed changed to a Liquid before leaving the condenser coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid It next will pass through the refrigerant dri...

Страница 17: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Страница 18: ...igerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants Failure to follow these procedures could result...

Страница 19: ...FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious in...

Страница 20: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Страница 21: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Страница 22: ...posite port liquid line to the indoor coil Refer to refrigerant flow chart This directs the refrigerant through the filter drier and cooling capillary tube to the indoor coil In the heating mode of op...

Страница 23: ...side of the system The other two are connected to the indoor and outdoor coils Small capillary tubes connect each end of the main valve cylinder to the A and B portsofthepilotvalve Athirdcapillaryisac...

Страница 24: ...the mid position part of the discharge gas from the compressor is directed back to the suction side resulting in excessively high suction pressure Should the valve fail to shift from coooling to heat...

Страница 25: ...excess braze from all tubing so that they will slip into fittings on new valve 5 Remove solenoid coil from new valve The use of a torch requires extreme care and proper judgment Follow all safety reco...

Страница 26: ...ated within the compressor shell usually due to recycling of the motor is slow to dissipate It may take anywhere from a few minutes to several hours for the overload to reset Checking the External Ove...

Страница 27: ...is obtained the compressor is grounded and must be replaced Check the complete electrical system to the compressor and compressor internal electrical system check to be certain that compressor is not...

Страница 28: ...tem will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R 22 and nitrogen and leak test all connections with an electronic or...

Страница 29: ...refrigerant and oil from the system Remove compressor capillary tube and filter drier from the system Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent Use approved...

Страница 30: ...ems Allow all items to dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mecha...

Страница 31: ...d rinse with warm water Allow it to dry thoroughly before reinstalling it in the chassis CLEARANCES Inspect the surrounding area inside and outside to ensure that the unit s clearances have not been c...

Страница 32: ...AMPS AMPS RUNNING AMPERAGE DRAW AMPS INDOOR TEMPERATURES INDOOR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F OUTD...

Страница 33: ...I Power Cord Trips Reset Button Pops Out The LCDI power cord can trip Reset button pops out due to disturbances on your power supply line Press and release RESET listen for click Reset button latches...

Страница 34: ...re sized to meet the cooling load and heater size is then selected to meet the heating load In extreme northern climates room air conditioners may not be able to be used as a primary source of heat Un...

Страница 35: ...o P m e l b o r P Fan motor does not run Inoperative system button Broken loose or incorrect wiring Refer to applicable wiring diagram Repair Open capacitor Test capacitor replace if inoperative Fan s...

Страница 36: ...o appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board e s u a C e l b i s s o P m e l b o r P Noisy operation Poorly installed Refer to Installation Manual f...

Страница 37: ...o M n i e t a r e p O t i n u d e z i s r e v O Inadequate vapor barrier in building structure particularly oors Advise customer e s u a C e l b i s s o P m e l b o r P Unit short cycles Defective the...

Страница 38: ...t undersized Check heat rise across coil If unit operates ef ciently check if insulation can be added to attic or walls If insulation is adequate recommend additional unit or larger one Outdoor t stat...

Страница 39: ...valve Defective electronic control board Replace electronic control board e s u a C e l b i s s o P m e l b o r P Heating insuf cient Heating capillary tube partially restricted Check for partially st...

Страница 40: ...UCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE LOW SUCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE PROBLEM PROBLEM PROBLEM PROBLEM PROBLEM PROBL...

Страница 41: ...AT PUMP ELECTRIC SHOCK HAZARD WARNING Turn off electric power before service or installation Extreme care must be used if it becomes necessary to work on equipment with power applied Failure to do so...

Страница 42: ...al Hot Warm Warm Hot TVB Hot Not enough pressure differential at start of stroke or not enough ow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pre...

Страница 43: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL ONLY MODELS 42...

Страница 44: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL WITH ELECTRIC HEAT MODELS 43...

Страница 45: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL HEAT PUMP WITH ELECTRIC HEAT MODELS 44...

Страница 46: ...per than 16 3 4 deep such as Fedders B sleeve 19 3 4 deep IDK Internal Drain Kit Newconstructionapplications where a condensate drain system has been built into the wall interior 163 4 FeddersB 193 4...

Страница 47: ...onry walls to support the material above the WSD SLEEVE The following considerations should also be given A Adjustable SUB BASE SB 89 or other unit support must be provided for panel wall type constru...

Страница 48: ...e WSD SLEEVE in the wall opening following the instructions given in the INSTALLATION REQUIRE MENTS section Attach the SLEEVE to the INSIDE WALL by driving two 12A x 2 screws in each side of the SLEEV...

Страница 49: ...RD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD 48 INSTALLATION INSTRUCTIONS FOR BAFFLE...

Страница 50: ...e orange backing from the gasket and apply it to the base of the sleeve see g B Once the gasket has been properly applied the sleeve is ready for the air conditioner to be installed per the installati...

Страница 51: ...S THE DRAIN PLATE DOWN TO FORM A WATERTIGHT SEAL AGAINST THE SLEEVE BASE 4 DRILL A 625 DIAMETER HOLE IN THE BOTTOM OF THE BASE PAN AS SHOWN IN THE ILLUSTRATION THIS HOLE ALLOWS CONDENSATE TO ENTER THE...

Страница 52: ...loves etc Failure to do so could result in serious injury CUT SEVER HAZARD EXCESSIVE WEIGHT HAZARD WARNING Use two people to lift or carry the unit and wear proper protective clothing Failure to do so...

Страница 53: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS SUBBASE...

Страница 54: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS ARCHITEC...

Страница 55: ...54 54 MECHANICAL HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD...

Страница 56: ...mproper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units installed i...

Страница 57: ...ox 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 877 599 5665 x 846 FAX 210 357 4490 Email tac friedrich com www friedrich com Printed in the U S...

Страница 58: ...NOTES...

Страница 59: ...NOTES...

Страница 60: ...AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A WM Ser...

Отзывы: