Friedrich WallMaster WE10C33-A Скачать руководство пользователя страница 13

ERROR CODEs lIsTING FOR “ws” MODEls 

E1  SHORT  CYCLE  SITUATION:

  Defined  as  a 

compressor that starts and stops more frequently 

than it should (more than 6 times per hour).  

E2  KEYBOARD STUCK ERROR:  

If any key button 

is stuck or pressed for 20 seconds or more, the 

unit considers it stuck. If a key is stuck it will be 

ignored until released. If the 

“Mode”

 key is stuck, 

the unit’s function will default to Cool mode.

E3  FROST  PROBE  OPEN:

  Normal  operation  is 

allowed. Replace probe.

E4  FROST  PROBE  SHORT:

  Normal  operation  is 

allowed. Replace probe.

E5  INDOOR  PROBE  OPEN:

  Control  assumes 

indoor ambient temperature is 90 degrees F and 

unit will operate. Replace probe.

E6  INDOOR  PROBE  SHORT:

  Control  assumes 

ambient temperature is 90 degrees F and unit 

will operate. Replace probe.

(See note and other infomation below)

ERROR CODEs lIsTING FOR “wE/wY” MODEls 

E1  SHORT  CYCLE  SITUATION:

  Defined  as  a 

compressor that starts and stops more frequently 

than it should (more than 6 times per hour).  

E2  KEYBOARD STUCK ERROR:  

If any key button 

is stuck or pressed for 20 seconds or more, the 

unit considers it stuck. If a key is stuck it will be 

ignored until released. If the 

“Mode”

 key is stuck, 

the unit’s function will default to Cool mode.

E3  AMBIENT  (INDOOR)  AIR  PROBE  OPEN 

OR  SHORT:

  Control  will  assume  ambient 

temperature is 90 degrees F when in Cool mode 

and 60 degrees F when in Heat mode. Unit will 

operate (see note below).

E4  EVAPORATOR  TEMPERATURE  PROBE 

OPEN OR SHORT:

 Normal operation is allowed. 

Replace probe (see note below).

E5  CONDENSER  TEMPERATURE  PROBE 

OPEN OR SHORT:

 Normal operation is allowed. 

Replace probe. 

E7  MOTOR OPERATION

E9  HEAT PUMP FAILURE

NOTE:

 All error codes display for probes open or shorted will 

allow unit to operate. Unit may ice up if faulty components 

are not replaced.

Indoor Coil Frost Probe Sensor:

 

Outdoor  Coil  Frost  Probe  Sensor  (on  WY  models):

 

Disables  the  compressor  at  30  degrees  F.  Compressor 

resumes  operation  when  temperature  reaches  43  +/-  5 

degrees F.

Indoor Air Probe Sensor:  

 

 

REBOOT THE CONTROL PANEL

Reboot  the  control  panel  as  follows:  With  the  unit  on, 

simultaneously  hold  down  the 

Mode

  button  and  the 

Temperature  Arrow

          button  for  approximately  10 

seconds. If the panel will reboot, you will hear the fan come 

on and the temperature window will read 60 degrees. If this 

happens, all you need to do is turn the unit off for about 10 

seconds and then turn it back on to finish the reboot cycle. 

If the panel does not reboot, you will most likely need to 

replace the electronic control.

Disables  compressor  at  30  degrees  F+/-  3  degrees  F. 

Compressor resumes operation when indoor coil temperature 

reaches 55 degrees F.

Control  range  is  60  degrees  F  to  90  degrees  F  +/-  3  

degrees F.

12

Содержание WallMaster WE10C33-A

Страница 1: ...WS13C30A WS15C30A Cool Only 115 Volt WE10C33A WE13C33A WE15C33A Cool with Electric Heat 230 Volt WY09C33A WY12C33A Heat Pump with Electric Heat Back Up WallMaster Money Fan Timer Operation Set Hr Sto...

Страница 2: ...ration Repairs Charging 17 20 Hermetic Components Check 21 Reversing Valve Description Operation 22 Testing the Coil and Reversing Valve 23 24 Compressor Checks 25 26 Compressor Replacement 27 28 Rout...

Страница 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Страница 4: ...contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious b...

Страница 5: ...drain from the unit Do not drill holes in the bottom of the drain pan or the underside of the unit Failure to follow these instructions can result in result in damage to the unit and or minor to seri...

Страница 6: ...n 5th DIGIT ALPHABETICAL MODIFIER 6th DIGIT VOLTAGE 1 115 Volts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models 3 3 KW Heat Strip Nominal 8th DIGIT Major Change A K A X 00001 A Jan D Apr G...

Страница 7: ...706 16 0 14 7 3550 2950 8 5 8 5 4 2 290 WSD 116 DEFROST CONTROL Initiated at 30 F outdoor coil temperature for two consecutive minutes and terminated at 43 F outdoor coil temperature During defrost th...

Страница 8: ...can be certain that the AHAM Certification Seal accurately states the unit s cooling and heating capacity rating the amperes and the energy efficiency ratio electrical DATA ELECTRIC SHOCK HAZARD WARN...

Страница 9: ...r Power PM Cool Fan Only Heat Clock Start Time Stop Time Smart Fan Fan Speed Mode Timer On Off Money Saver Set Hour 2 3 4 1 6 5 7 9 8 10 11 12 14 13 Figure2 WY WEModelheat coolcontrolpanel Figure 1 WS...

Страница 10: ...eset or theTimer On Off will not function when desired To Activate Money Saver WY WE models 14 Press the Money Saver button to activate the Money Saver feature The light will indicate the Money Saver...

Страница 11: ...tton once to see the current clock setting Continue pressing the button until you arrive at the current time Hour only Minutes are not shown on the display Make sure that the A M P M setting is correc...

Страница 12: ...ive presses will scroll through all error codes stored Press the Temp Hour button to see the reverse order of the error codes When the end of the stored error codes is reached the temperature Set Poin...

Страница 13: ...PEN OR SHORT Control will assume ambient temperature is 90 degrees F when in Cool mode and 60 degrees F when in Heat mode Unit will operate see note below E4 EVAPORATOR TEMPERATURE PROBE OPEN OR SHORT...

Страница 14: ...illustrations below If the outdoor coil thermister reaches 43 degrees and the compressor has waited the standard delay time of 180 240 seconds the control will 1 Turn off the backup electric heat 2 W...

Страница 15: ...tor Connections The starting winding of a motor can be damaged by a shorted and grounded running capacitor This damage usually can be avoided by proper connection of the running capacitor terminals Fr...

Страница 16: ...sed changed to a Liquid before leaving the condenser coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid It next will pass through the refrigerant dri...

Страница 17: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Страница 18: ...igerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants Failure to follow these procedures could result...

Страница 19: ...FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious in...

Страница 20: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Страница 21: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Страница 22: ...posite port liquid line to the indoor coil Refer to refrigerant flow chart This directs the refrigerant through the filter drier and cooling capillary tube to the indoor coil In the heating mode of op...

Страница 23: ...side of the system The other two are connected to the indoor and outdoor coils Small capillary tubes connect each end of the main valve cylinder to the A and B portsofthepilotvalve Athirdcapillaryisac...

Страница 24: ...the mid position part of the discharge gas from the compressor is directed back to the suction side resulting in excessively high suction pressure Should the valve fail to shift from coooling to heat...

Страница 25: ...excess braze from all tubing so that they will slip into fittings on new valve 5 Remove solenoid coil from new valve The use of a torch requires extreme care and proper judgment Follow all safety reco...

Страница 26: ...ated within the compressor shell usually due to recycling of the motor is slow to dissipate It may take anywhere from a few minutes to several hours for the overload to reset Checking the External Ove...

Страница 27: ...is obtained the compressor is grounded and must be replaced Check the complete electrical system to the compressor and compressor internal electrical system check to be certain that compressor is not...

Страница 28: ...tem will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R 22 and nitrogen and leak test all connections with an electronic or...

Страница 29: ...refrigerant and oil from the system Remove compressor capillary tube and filter drier from the system Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent Use approved...

Страница 30: ...ems Allow all items to dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mecha...

Страница 31: ...d rinse with warm water Allow it to dry thoroughly before reinstalling it in the chassis CLEARANCES Inspect the surrounding area inside and outside to ensure that the unit s clearances have not been c...

Страница 32: ...AMPS AMPS RUNNING AMPERAGE DRAW AMPS INDOOR TEMPERATURES INDOOR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F OUTD...

Страница 33: ...I Power Cord Trips Reset Button Pops Out The LCDI power cord can trip Reset button pops out due to disturbances on your power supply line Press and release RESET listen for click Reset button latches...

Страница 34: ...re sized to meet the cooling load and heater size is then selected to meet the heating load In extreme northern climates room air conditioners may not be able to be used as a primary source of heat Un...

Страница 35: ...o P m e l b o r P Fan motor does not run Inoperative system button Broken loose or incorrect wiring Refer to applicable wiring diagram Repair Open capacitor Test capacitor replace if inoperative Fan s...

Страница 36: ...o appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board e s u a C e l b i s s o P m e l b o r P Noisy operation Poorly installed Refer to Installation Manual f...

Страница 37: ...o M n i e t a r e p O t i n u d e z i s r e v O Inadequate vapor barrier in building structure particularly oors Advise customer e s u a C e l b i s s o P m e l b o r P Unit short cycles Defective the...

Страница 38: ...t undersized Check heat rise across coil If unit operates ef ciently check if insulation can be added to attic or walls If insulation is adequate recommend additional unit or larger one Outdoor t stat...

Страница 39: ...valve Defective electronic control board Replace electronic control board e s u a C e l b i s s o P m e l b o r P Heating insuf cient Heating capillary tube partially restricted Check for partially st...

Страница 40: ...UCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE LOW SUCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE PROBLEM PROBLEM PROBLEM PROBLEM PROBLEM PROBL...

Страница 41: ...AT PUMP ELECTRIC SHOCK HAZARD WARNING Turn off electric power before service or installation Extreme care must be used if it becomes necessary to work on equipment with power applied Failure to do so...

Страница 42: ...al Hot Warm Warm Hot TVB Hot Not enough pressure differential at start of stroke or not enough ow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pre...

Страница 43: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL ONLY MODELS 42...

Страница 44: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL WITH ELECTRIC HEAT MODELS 43...

Страница 45: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL HEAT PUMP WITH ELECTRIC HEAT MODELS 44...

Страница 46: ...per than 16 3 4 deep such as Fedders B sleeve 19 3 4 deep IDK Internal Drain Kit Newconstructionapplications where a condensate drain system has been built into the wall interior 163 4 FeddersB 193 4...

Страница 47: ...onry walls to support the material above the WSD SLEEVE The following considerations should also be given A Adjustable SUB BASE SB 89 or other unit support must be provided for panel wall type constru...

Страница 48: ...e WSD SLEEVE in the wall opening following the instructions given in the INSTALLATION REQUIRE MENTS section Attach the SLEEVE to the INSIDE WALL by driving two 12A x 2 screws in each side of the SLEEV...

Страница 49: ...RD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD 48 INSTALLATION INSTRUCTIONS FOR BAFFLE...

Страница 50: ...e orange backing from the gasket and apply it to the base of the sleeve see g B Once the gasket has been properly applied the sleeve is ready for the air conditioner to be installed per the installati...

Страница 51: ...S THE DRAIN PLATE DOWN TO FORM A WATERTIGHT SEAL AGAINST THE SLEEVE BASE 4 DRILL A 625 DIAMETER HOLE IN THE BOTTOM OF THE BASE PAN AS SHOWN IN THE ILLUSTRATION THIS HOLE ALLOWS CONDENSATE TO ENTER THE...

Страница 52: ...loves etc Failure to do so could result in serious injury CUT SEVER HAZARD EXCESSIVE WEIGHT HAZARD WARNING Use two people to lift or carry the unit and wear proper protective clothing Failure to do so...

Страница 53: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS SUBBASE...

Страница 54: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS ARCHITEC...

Страница 55: ...54 54 MECHANICAL HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD...

Страница 56: ...mproper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units installed i...

Страница 57: ...ox 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 877 599 5665 x 846 FAX 210 357 4490 Email tac friedrich com www friedrich com Printed in the U S...

Страница 58: ...NOTES...

Страница 59: ...NOTES...

Страница 60: ...AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A WM Ser...

Отзывы: