background image

16

Problem

Possible Cause

Action

Unit does not run

Fuse blown or circuit tripped

Replace fuse, reset breaker. If repeats, check 
fuse or breaker size. Check for shorts in unit 
wiring & components

Power cord not plugged in

Plug it in

System switch in  "OFF" position

Set switch correctly

Inoperative system switch

Test for continuity in each switch position

Loose or disconnected wiring at 
switch or other components

Check wiring & connections. Reconnect per 
wiring diagram

Problem

Possible Cause

Action

Evaporator coil 

freezes up

Dirty fi lter

Clean as recommended in Owner's Manual

Restricted airfl ow

Check for dirty or obstructed coil. Use 
pressure wash or biodegradable cleaning 
agent to clean

Inoperative t-stat

Test for shorted t-stat or stuck contacts

Short of refrigerant

De-ice coil & check for leak

Inoperative fan motor

Test fan motor & replace if inoperative

Partially restricted capillary tube

De-ice coil. Check temp. differential (delta T) 
across coil. Touch test coil return bends for 
same temp. Test for low running current

Problem

Possible Cause

Action

Compressor runs 

continually & does 

not cycle off

Excessive heat load

Unit undersized. Test cooling performance & 
replace with larger unit if needed

Restriction in line

Check for partially iced coil & check 
temperature split across coil

Refrigerant leak

Check for oil at silver soldered connections. 
Check for partially iced coil. Check split across 
coil. Check for low running amperage

T-stat contacts stuck

Check operation of t-stat. Replace if contacts 
remain closed.

T-stat incorrectly wired

Refer to appropriate wiring diagram

Problem

Possible Cause

Action

T-stat does not turn 

unit off

T-stat contacts stuck

Disconnect power to unit. Remove cover 
of t-stat & check if contacts are stuck. If so, 
replace t-stat

T-stat set at coldest point

Turn to higher temp. setting to see if unit 
cycles off

Incorrect wiring

Refer to appropriate wiring diagrams

Unit undersized for area to be 
cooled

Refer to industry standard sizing chart

Содержание WallMaster WE10B33A

Страница 1: ...WS08B10A B WS10B10A B WS14B10A B WS10B30A B WS13B30B WS16B30A B WE10B33A B WE13B33B WE16B33A B WY10B33A B WY13B33A B WM Svc Prts 06 7 06 Service Parts Manual WallMaster Thru the Wall 72...

Страница 2: ...Data 6 Electrical Data 7 Functional Component De nitions 8 Electronic Controls 9 Rotary Controls 10 Refrigeration Sequence of Operation 11 Sealed Refrigeration Repairs 12 13 Refrigerant Charging 13 G...

Страница 3: ...nada This warranty is not applicable to 1 Air filters or fuses 2 Products on which the model and serial numbers have been removed 3 Products which have defects or damage which results from improper in...

Страница 4: ...s and debris Clean both areas with an antibacterial and antifungal cleaner Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly Check the sealant around the...

Страница 5: ...R 6th DIGIT VOLTAGE 1 115 Volts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models ELECTRIC HEAT MODELS 3 3 KW Heat Strip Nominal 8th DIGIT Major Change Serial Number Decade Manufactured L 0 C...

Страница 6: ...00 11000 9100 230 208 6 3 6 7 1404 1379 16 0 14 7 3550 2950 8 9 8 7 3 3 280 111 WE16B33A 15800 15000 11000 9100 230 208 7 8 8 5 1756 1705 16 0 14 7 3550 2950 9 0 8 8 4 2 290 121 WY10B33A 10100 9800 81...

Страница 7: ...ord and be within reach of service cord Do NOT alter the service cord or plug Do NOT use an extension cord Refer to the table above for proper receptacle and fuse type ELECTRIC SHOCK HAZARD Turn off e...

Страница 8: ...ing diagrams and schematics in the back of this service manual Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristics of the fan motor and co...

Страница 9: ...de Mode is active Pressing the TEMP HR button will display 00 Consecutive presses will scroll through all error codes logged Press the TEMP HR button to see the reverse order of all error codes logged...

Страница 10: ...tion as indicated on decorative control panel in Figure 7 Wait three minutes before restarting Warmer Cooler Fan Only Low Heat Med Heat High Heat Low Cool Med Cool High Cool MODE TEMPERATURE Figure 7...

Страница 11: ...ore a change in state can occur 3 Flow is always from a higher pressure area to a lower pressure area 4 The temperature at which a liquid or gas changes state is dependent upon the pressure The refrig...

Страница 12: ...Compressor condenser evaporator capillary tube refrigerant leaks etc 1 Recover the refrigerant from the system at the pro cess tube located on the high side of the system by installing a line tap on...

Страница 13: ...d discharge line for carbon deposits Remove and clean if necessary 4 Reassemble the system including new drier strainer and capillary tube 5 Proceed with processing as outlined under hermetic componen...

Страница 14: ...roke or not enough ow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pressure If no shift use valve with smaller port Body damage Replace valve Hot...

Страница 15: ...t run Inoperative system switch Test switch replace if inoperative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed sw...

Страница 16: ...y tube De ice coil Check temp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does no...

Страница 17: ...bulb Place jumper across t stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram...

Страница 18: ...hort cycles T stat differential too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty l...

Страница 19: ...lace defrost control Defrost control contacts stuck If contacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bu...

Страница 20: ...r continuity of system switch Problem Possible Cause Action Cooling adequate but heating insuf cient Heating capillary tube partially restricted Check for partially starved outer coil Replace heating...

Страница 21: ...21 WIRING DIAGRAM MODELS WS08B10A B WS10B10A B WS14B10A B WS10B30A B WS13B30B...

Страница 22: ...22 WIRING DIAGRAM MODELS WS16B30A B...

Страница 23: ...23 WIRING DIAGRAM MODELS WE10B33A B WE13B33B...

Страница 24: ...24 WIRING DIAGRAM MODELS WE16B33A B...

Страница 25: ...25 WIRING DIAGRAM MODELS WY10B33A B WY13B33A B...

Страница 26: ...ES CHASSIS PARTS 47 48 46 46A 31 12 32 30 7 16 17 14 20 18 19 27 25 13 8 For Heat Cool Models Only 5 45 26 1 41 43 39 Electronic Control Box and Controls 2 41 39 43 6 1 44 Electro Mechanical Control B...

Страница 27: ...R 61871456 1 1 1 110 7 FAN MOTOR 61871457 1 1 110 7 FAN MOTOR 61871458 1 1 1 110 7 FAN MOTOR 61871459 1 1 110 8 HEATER 62101210 1 1 1 1 1 210 9 COIL SOLENOID 25063600 1 1 240 REFRIGERATION SYSTEM PART...

Страница 28: ...1 1 1 1 1 1 1 1 1 1 1 999 43 ESCUTCHEON COOL 62101106 1 1 1 1 1 1 760 43 ESCUTCHEON HTG COOL 62101102 1 1 1 1 1 760 44 KNOBS CRTL 61911600 2 2 2 2 2 761 HOLDER AIR FILTER 60865900 2 2 2 2 2 2 2 2 2 2...

Страница 29: ...PART NO DESCRIPTION APPLICATION CHASSIS PARTS Cont 1 616 036 01 Sleeve Assembly 1 1 1 1 1 1 1 1 1 1 1 2 616 032 00 Panel Weather Inner 1 1 1 1 1 1 1 1 1 1 1 3 616 030 01 Grille Louvered 1 1 1 1 1 1 1...

Страница 30: ...06 7 06 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed i...

Отзывы: