41
20 – Auto Changeover Set Point Offset (DEAD BAND)
00-04
(01°F* default setting)
Select the difference between the guest-selected set point and the heat and the
cool set point when the Wall Controller is in the automatic temperature control
mode.
This value plus the 1st stage differential defined in steps 02 and 04, defines the
temperature at which the Wall Controller would automatically change heating/
cooling modes.
This feature allows adjusting the deadband between the heat and the cool set
points in automatic changeover mode in order to avoid the system from bouncing
back and forth between heating and cooling under normal operating conditions.
.
Custom Energy Savings Settings
VPXEMWRT2-Thermostat Manual_pkg.indd 41
2017-12-15 3:37 PM