background image

22

01 - Fan Control Mode

Select Fan Control Mode:

00 MANUAL –  

Guest can select automatic or continuous fan mode;

01 * AUTOMATIC –   Fan runs only when there is a demand for heating or

 

air conditioning

* Indicates default setting;

Custom Energy Savings Settings

VPXEMWRT2-Thermostat Manual_pkg.indd   22

2017-12-15   3:37 PM

Содержание VRPXEMWRT2

Страница 1: ...VRPXEMWRT2 Wireless VRP Energy Management Wall Controller with an Occupancy Sensor INSTRUCTION MANUAL PART NO 95200303 Rev 00 VPXEMWRT2 Thermostat Manual_pkg indd 1 2017 12 15 3 37 PM...

Страница 2: ...VPXEMWRT2 Thermostat Manual_pkg indd 2 2017 12 15 3 37 PM...

Страница 3: ...ller 19 Custom Energy Savings Settings 20 Using the Wall Controller Settings Screens 21 01 FAN CONTROL MODE 22 02 1ST STAGE DIFFERENTIAL HEAT 23 03 2ND STAGE DIFFERENTIAL HEAT 24 04 1ST STAGE DIFFEREN...

Страница 4: ...HUMIDITY CONTROL 43 23 TEMPERATURE CALIBRATION 44 Wall Controller Maintenance 45 Replacing Wall Controller Batteries 46 Troubleshooting 47 Error Codes 47 Wall Controller is not controlling the VRP un...

Страница 5: ...nual FOR INSTALLATION OF NETWORKING WALL CONTROLLERS WITH REMOTE MANAGEMENT REFER TO THE NETWORK INSTALLATION MANUAL LOGIN TO THE REMOTE MANAGEMENT WEBSITE TO CONFIRM THE SERVER IS CONNECTED TO THE IN...

Страница 6: ...6 VPXEMWRT2 Thermostat Manual_pkg indd 6 2017 12 15 3 37 PM...

Страница 7: ...should face the bed area of the room Wall Controller MUST NOT BE INSTALLED NEAR OR ON METAL STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING THAT MAY BE IN THE WALL METAL STRUCTURES AND SURFACES SI...

Страница 8: ...stallation Wall Controller and Receiver must not be powered during the pairing procedure remove batteries from the Wall Controller and unplug the Receiver from the VRP unit during the pairing procedur...

Страница 9: ...cure the Wall Controller to the wall Insert two 2 AA cell batteries not supplied into the Wall Controller battery compartment Follow the Wall Controller Configuration instructions Replace the Wall Con...

Страница 10: ...not touching any metal components of the VRP unit Ensure that the Wireless Receiver antenna is facing the Wall Controller on the wall and is oriented so that any metal parts of the VRP unit do not ob...

Страница 11: ...the VRP unit top To maximize the wireless signal strength from the Receiver to the VRPXEMWRT2 Wall Controller the Receiver MUST NOT be installed on the VRP unit Note Depending upon the closet size an...

Страница 12: ...res as shown in Figure 2 Each connection is made with a lever type connector Four connectors will be needed to complete unit wiring Each connector is capable of connecting three wires Figure 1 Figure...

Страница 13: ...gure 3 and close lever as shown in Figure 4 3 Insert two specified twisted paired wires from the CAT6 cable into the remaining lever connector slot as shown in Figure 4 Each twisted paired wire should...

Страница 14: ...he Receiver into a lever connector slot and close the orange lever on the connector Insert the twisted Blue and Brown White Cat 6 wire into the remaining lever connector slot and close the orange leve...

Страница 15: ...Controller configuration settings will appear on the Wall Controller screen In order to properly operate the VRP unit Set the Wall Controller clock Enter the room number Select Energy Savings Preset T...

Страница 16: ...he Up and Down buttons to set the hours Press the Fan button to advance to the minutes setting Use the Up an Down buttons to set the minutes Press the F C button to advance to the next menu Setting th...

Страница 17: ...ignored i e Room number 123 should be entered as 00123 Use the Up and Down buttons to change the digit Press the Fan button advance to the next digit Press the F C button to advance to the next menu...

Страница 18: ...y Savings E 5 Highest Energy Savings Refer to the APPENDIX 1 for Energy Saving Preset details E C Indicates Custom Energy Savings Settings in case the active Wall Controller savings settings differ fr...

Страница 19: ...buttons to change the temperature set point above and below the current room temperature to test if the Wall Controller initiates heating and cooling the VRP unit should turn heating and air condition...

Страница 20: ...screen appears The Wall Controller must be turned on to access the Wall Controller settings NOTE If the Wall Controller is connected to a network the equipment and the energy saving settings configure...

Страница 21: ...ng Press the F C button to advance to the next setting Press the Fan button to return to the previous setting Press the Power button to save and exit Wall Controller settings Custom Energy Savings Set...

Страница 22: ...NUAL Guest can select automatic or continuous fan mode 01 AUTOMATIC Fan runs only when there is a demand for heating or air conditioning Indicates default setting Custom Energy Savings Settings VPXEMW...

Страница 23: ...t the number of degrees the Wall Controller has to sense between the automatic changeover temperature for heat and the room temperature before a call for the 1st stage heating is initiated Custom Ener...

Страница 24: ...ential Heat 10 20 1 0 F 2 0 F 2 0 F default setting Select the difference between 1st stage heating and 2nd stage heating initiation Custom Energy Savings Settings VPXEMWRT2 Thermostat Manual_pkg indd...

Страница 25: ...he number of degrees the Wall Controller has to sense between the automatic changeover temperature for cool and the room temperature before a call for the 1st stage cooling is initiated Custom Energy...

Страница 26: ...at the end of the Incidental Occupancy Threshold period and continue to observe energy saving functions that were in effect before the room became occupied This setting allows ignoring incidental roo...

Страница 27: ...ght Occupancy Threshold selected here the Wall Controller will automatically revert to unoccupied mode and continue to observe energy saving functions that were in effect before the room became occupi...

Страница 28: ...07 NA Custom Energy Savings Settings 28 VPXEMWRT2 Thermostat Manual_pkg indd 28 2017 12 15 3 37 PM...

Страница 29: ...Wall Controller will disable the occupancy sensor and consider the room occupied until the end of the Night Occupancy period This feature ensures that energy saving functions that may affect guest co...

Страница 30: ...hour clock for Night Occupancy to end The time of day the Night Occupancy ends and the Wall Controller switches back to the room sensing settings chosen in the other occupancy modes Custom Energy Sav...

Страница 31: ...31 10 NA Custom Energy Savings Settings VPXEMWRT2 Thermostat Manual_pkg indd 31 2017 12 15 3 37 PM...

Страница 32: ...32 11 NA Custom Energy Savings Settings VPXEMWRT2 Thermostat Manual_pkg indd 32 2017 12 15 3 37 PM...

Страница 33: ...etback is initiated This feature prevents initiating temperature setback prematurely while the guest is still in the room but in an area where occupancy cannot be detected by the occupancy sensor Sett...

Страница 34: ...ct the Minimum Setback Temperature in F This feature allows defi ning the minimum temperature in a room when room is unoccupied and the Wall Controller is in the setback mode Custom Energy Savings Set...

Страница 35: ...etback is initiated This feature prevents initiating temperature setback prematurely while the guest is still in the room but in an area where occupancy cannot be detected by the occupancy sensor Sett...

Страница 36: ...ct the Maximum Setback Temperature in F This feature allows defi ning the maximum temperature in a room when room is unoccupied and the Wall Controller is in the setback mode Custom Energy Savings Set...

Страница 37: ...37 16 NA Custom Energy Savings Settings VPXEMWRT2 Thermostat Manual_pkg indd 37 2017 12 15 3 37 PM...

Страница 38: ...38 17 Minimum Set Point 64 84 66 F default setting Select the minimum set point in F that a guest can select Custom Energy Savings Settings VPXEMWRT2 Thermostat Manual_pkg indd 38 2017 12 15 3 37 PM...

Страница 39: ...39 18 Maxmium Set Point 60 82 78 F default setting Select the maximum set point in F that a guest can select Custom Energy Savings Settings VPXEMWRT2 Thermostat Manual_pkg indd 39 2017 12 15 3 37 PM...

Страница 40: ...perature control mode to maintain the room temperature 01 AUTOMATIC Wall Controller automatically turns on heating or air conditioning to maintain the room temperature at the selected temperature set...

Страница 41: ...ge differential defined in steps 02 and 04 defines the temperature at which the Wall Controller would automatically change heating cooling modes This feature allows adjusting the deadband between the...

Страница 42: ...Wall Controller will be turned off it will not automatically restore the most recent guest settings 02 When room is unoccupied and the Wall Controller is in the setback mode or turned off it will NOT...

Страница 43: ...ther room humidity is below 55 or room temperature is below 72 F Indicates default setting This setting is active only on Wall Controllers with enabled humidity features Changing this setting on a non...

Страница 44: ...44 23 Temperature Calibration 5 0 5 0 0 0 F default setting Calibrate the temperature display 5 0 F 5 0 F Custom Energy Savings Settings VPXEMWRT2 Thermostat Manual_pkg indd 44 2017 12 15 3 37 PM...

Страница 45: ...eration To replace Wall Controller batteries Unscrew the fixing screw and remove the Wall Controller cover Replace the two 2 AA cell batteries not supplied Replace the Wall Controller cover and screw...

Страница 46: ...perature Sensor Hardware Defect ERR 2 Wall Controller Radio Hardware Defect ERR 3 Wall Controller Radio Software Defect ERR 4 No link with the Wireless Receiver ERR 5 Wall Controller Memory Defect VPX...

Страница 47: ...wered but it is not communicating with the Wall Controller turn the Wall Controller off and on to re initiate the linking procedure In case of a Network Installation re link the Wall Controller and th...

Страница 48: ...48 VPXEMWRT2 Thermostat Manual_pkg indd 48 2017 12 15 3 37 PM...

Страница 49: ...pancy End 12 11 10 9 8 7 10 N A 11 N A 12 Setback Delay Heat 0 30 25 20 15 10 13 Minimum Setback Temperature 67 66 65 64 63 62 14 Setback Delay Cool 0 30 25 20 15 10 15 Maximum Setback Temperature 72...

Страница 50: ...Threshold the minimum period of time in minutes for which occupancy needs to be detected in order to enter the Guest Occupancy mode Night Occupancy Threshold the minimum period of time during the Nig...

Страница 51: ...232 075 7 185 825 7 156 318 7 152 806 7 145 110 7 050 026 7 028 912 6 902 117 6 789 739 6 786 421 6 619 555 6 581 846 6 578 770 7 838 803 7 841 542 D556 061 D518 744 RE40 437 CANADIAN PATENTS 2 633 11...

Страница 52: ...HINA Friedrich Air Conditioning Co 10001 Reunion Place Suite 500 San Antonio TX 78216 210 546 0500 1 800 541 6645 Technical Support 1 877 318 1823 OEM www friedrich com VPXEMWRT2 Thermostat Manual_pkg...

Отзывы: