SPECIFICATIONS
CEILING AND FLOOR INSTALLED HEAT PUMPS
PERFORMANCE RATINGS
SYSTEM MODEL NO.
S24YF
S36YF
C24YF
INDOOR MODEL
MS24Y3F
MS36Y3F
MC24Y3F
OUTDOOR MODEL
MR24UY3F
MR36Y3F
MR24UY3F
CAPACITY COOLING
Btu
22200
34100
22200
CAPACITY COOLING MIN - MAX
Btu
5000-27300
8500-36000
5000-27300
SENSIBLE HEAT RATIO
0.62
0.67
0.64
CAPACITY HEATING @ 47°F
Btu
24200
38200
24200
CAPACITY HEATING MIN - MAX
Btu
5000-29000
9200-42700
5000-29000
CAPACITY HEATING @ 17°F
Btu
20,100
27,100
20,100
HSPF
8.5
8.5
8.5
SEER
15.0
14.0
15.0
EER
9.8
8.1
10.6
MOISTURE REMOVAL
Pts/h
7.4
7.4
6.4
AIRFLOW (LOW, MED, HIGH)
CFM
371, 436, 518
842, 977, 1089
436, 536, 618
SOUND RATING - INDOOR
dB-A
38, 43, 47
41, 45, 48
38, 43, 45
SOUND RATING - OUTDOOR
dB-A
53
54
53
OPERATING RANGE (HEATING)
°F
0 - 115 (14 - 75)
0 - 115 (14 - 75)
0 - 115 (14 - 75)
EST. YEARLY OPERATING COST
$180
$337
$168
ELECTRICAL DATA
POWER SOURCE
230/208-60-1
230/208-60-1
230/208-60-1
MIN. AMPACITY
A
15.5
23
15.5
COOLING WATTS
W
2250
4220
2100
MAX. TD FUSE/BREAKER
A
20
30
20
REFRIGERATION SYSTEM
REFRIGERANT
R410A
R410A
R410A
COMPRESSOR TYPE
Inverter (Twin Rotary)
Inverter (Twin Rotary)
Inverter (Twin Rotary)
CONNECTIONS
Flare
Flare
Flare
LIQUID LINE O.D.
in
3/8"
3/8"
3/8"
SUCTION LINE O.D.
in
5/8"
5/8"
5/8"
FACTORY PRECHARGE
ft
50'
50'
50'
MAX. LINE LENGTH
ft
165'
165'
165'
MAX. HEIGHT DIFFERENCE
ft
66'
98'
66'
DIMENSIONS & WEIGHT
INDOOR UNIT
W X H X D
in
39" x 7 7/8" x 25 3/4"
65 3/8" x 9 1/2" x 27 1/2"
32 5/8" x 9 5/8" x 32 5/8"
NET WEIGHT
lbs
62
106
75
SHIPPING WEIGHT
lbs
82
134
97
OUTDOOR UNIT
W X H X D
in
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
NET WEIGHT
lbs
141
141
141
SHIPPING WEIGHT
lbs
154
154
154
NOTE: All models have low ambient capabilities built in.
Capacity is reduced as 0 degrees Fahrenheit is approached.
NOTE: All R410A models have 1/2
˝
UNF 20 thread per inch charging and vacuuming ports. An adapter must be used for 1/4
˝
gauges. Adapter part number 67270018 is available through Friedrich parts distributors.
Due to continuing research in new energy-saving technology, speci
fi
cations are subject to change without notice.
16