![Friedrich VERT-I-PAK VEA09 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/friedrich/vert-i-pak-vea09/vert-i-pak-vea09_installation-and-operation-manual_2332907007.webp)
7
920-075-10
Installation
Utility Closet Dimensions
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 3. Three inches minimum clearance
on three sides of the unit must be allowed for return airflow, installation access and service access. See figures 3 & 4 for clearances
and reference dimensions.
Figure 3
Typical Utility Closet
25" x 20" Filter
(Field Supplied)
VPRG4 Access Panel and
Return Air Filter Grille
Electrical
Connection
Rigid Ductwork
Flexible Ductwork
Exterior Wall
VPAWP1-8/1-14
Wall Plenum
Plenum Divider
3/4" FPT Drain
Connection
Optional
Platform
3" Clearance on all three sides
minimum for service and installation.
Power
Disconnect
Thermostat
Wiring
See Figure 8, Page 10
for return air options
Chassis installs
2
3
/
8
" into Plenum
Chassis Shown in Closet, on Optional Platform
Vert-I-Pak Chassis dimensions:
23
1
/
8
" wide x 23
1
/
8
" deep x 32
1
/
4
" high.
VPAWP1-8/1-14 Wall Plenum cut-out
dimensions 24
5
/
8
" wide x 30
7
/
8
" high.
VPRG4 Access Panel cutout dimensions:
27" wide by 55
3
/
4
" high.
See Figure 9 (Pg 11) for proper chassis
installation.
Optional eld
installed dran pan
(refer to local codes)
Figure 4
Top View
Vert-I-Pak 9,000, 12,000, 18,000, BTU/h
Chassis dimensions: 23 1/8" wide x 23 1/8"
deep x 32 1/4" high.
Содержание VERT-I-PAK VEA09
Страница 15: ...15 920 075 10 Error Code Code Translation Action Taken by Unit Possible Cause 1 2 3 4 5 6 7 8 O N Error Codes...
Страница 18: ......