background image

Содержание Vert-I-Pack B Series

Страница 1: ...Vert I PakBSeries Single PackageVerticalAir ConditioningSystem 18 000I 24 000I 30 000I 36 000I 42 000I 49 000I 60 000Btu h Installation Operation Manual 929 164 00 10 03 ...

Страница 2: ...ir Conditioned SupplyAir System 11 Indoor Fan Performance 11 Electrical A Grounding 12 B Power Supply 12 Thermostat Mounting and Wiring A Thermostat Location 13 B Thermostat Mounting Wiring 13 C Wire Thermostat Cable to UnitTerminal 13 Condensate Drain Line 14 Installation Final Checklist 14 Test Run 14 Owners Manual Operating Information Identifying your System 15 Important Facts 15 Operating the...

Страница 3: ...ystems DO NOT reduce air intakes or discharge sizes DO insulate ALL conditioned air duct system components DO NOT locate room thermostat near conditioned air diffusers DO locate thermostat on an interior wall DO check that condensate drain line drains freely DO NOT let debris fall and collect in indoor or outdoor blowers DO NOT drill into unit except for 1 in flanges for ducted return units This c...

Страница 4: ... that attaches to the wall sleeve or outside of the building VPAL3 VPSC3 Architectural louver for VPBWP3 plenums Custom colored architectural louver for VPBWP3 plenums VPAL4 Architectural louver for VPBWP4 plenums VPSC4 Custom colored architectural louver for VPBWP4 plenums VPAh5 Architectural louver for VPBWP5 plenums VPSC5 Custom colored architectural louver for VPBWP5 plenums VPAL6 VPSC6 RT3 VP...

Страница 5: ... 1 Ph 60Hz V A ENGINEERING CODE OPTIONS RT Standard Remote Operation ELECTRIC HEATER SIZE B Series 05 5 0 KW 10 10 0 KW 15 15 0 KW 20 20 0 KW 25 25 0 KW C It Matters Section II Dimensional Data Figure 1 V E H B18 24 30 36 Unit Dimensions Inches t 18K 24K 14 00 30K 36K 21 00 18K 24K 7 00 30K 36K 12 00 2 62_ BACK OUTDOOR AIR INTAKE OUTDOOR JAIR EXHAUST 11 53 18K and 24K 8 25 30K and 36K 21 50 _ _1 0...

Страница 6: ... H B60 1 30 00 I 12 00 J 2 5 _ i i Ex o_ lo INDOOR AIR SUPPLY OUTDOOR mR _ _usT _ _ 15 00 _ 9 25 _ V E H B42 BACKVIEW T 22 50 1 I 14 50 2 50 00 Unit Dimensions Inches I _ INDOOR AIR RETURN 1 24 X 30 NOM SERVICE PORT ACCESS CONTROL BOX ACCESS _ 30 50 _ r_l CONDENSATE DRAIN EXIT 2 ABOVE FLOOR Section III Installation The Vert l Pak was designed for installation in residential and light commercial ap...

Страница 7: ...indoor air and outdoor air requirements as listed in the following sections will void unit warranty A Outdoor Air System As a completely self contained system the Vert l Pak unit requires an adequate supply of outdoor air to exchange heat from the outdoor air coil The outdoor air intake and discharge openings are located on the back side of the unit The unit may be installed where the outdoor air ...

Страница 8: ...Air Louver Condensate Drain Pipe Finished Floor 18 50 Wail Framing Brick or Other Exterior Finish Figure 6 VPBWP4 8 14 Wall Plenum OUTDOOR AIR WALL SLEEVE For Models VENHB18 VENH B24 VE VH B30 VE VH B36 CONDENSATE DRAIN PIPE OUTDOOR FINISHED FLOOR WALL FRAMING BRICK OR OTHER EXTERIOR FINISHINC ...

Страница 9: ...R AIR WALL SLEEVE WALL FRAMING For Models VE VH B42 VE VH B49 OUTDOOR BRICK OR OTHER EXTERIOR FINISH Figure 8 VPBWP6 8 14 Wall Plenum OUTDOOR AIR WALL SLEEVE For Model VE VH B60 CONDENSATE DRAIN PIPE OUTDOOR AIR LOUVER FINISHED FLOOR WALL FRAMING BRICK OR OTHER EXTERIOR FINISH ...

Страница 10: ... 1227 1131 lO26 VEB36 VHB36 Outdoor 1600 1550 1480 1420 VEB42 VHB42 Outdoor 2100 2000 1900 1800 VEB49 VHB49 Outdoor 2400 2300 2200 2100 VEB60 VHB60 Outdoor 2600 2550 2450 2350 Italics numbers indicate performance outside the required operating windo_ Bold figures indicate the standard rated airflow Figure 9 Typical Ducted Outside Air Configuration INTAKE OUTDOOR AIRINTAKE OUTSIDE WALL FLOOR o CEIL...

Страница 11: ...tly in front of the RA opening a minimum of 7 in clearance is required between the front of the unit and the back side of the door The minimum net free open area required for the RA louver or grille is listed in Table 2 Indoor Fan Performance Table 2 ESP Rated 0 1 0 2 0 3 0 4 0 5 VEB18 VHB18 VEB24 VHB24 VEB30 VHB30 VEB36 VHB36 VEB42 VHB42 VEB49 VHB49 VEB60 VHB60 Indoor Indoor Indoor Indoor Indoor ...

Страница 12: ... unit Refer to Table 4 and Table 5 for required circuits and recommended wire size for each circuit Table 4 Minimum Circuit Maximum Fuse2or Model Compressor Amps Outdoor Fan Amps Indoor Fan Amps Ampacity Minimum Wire Size 1 Breaker Size Amps u _ V E H B18 7 9 1 7 1 7 14 0 12 20 m _ V E H B24 9 3 1 7 1 7 16 7 12 25 _ V E H B30 15 0 2 2 1 8 22 8 10 30 t33 _ _ V E H B36 17 9 3 0 2 5 27 9 8 40 oo o V ...

Страница 13: ...ed 35 C minimum wire If the thermostat is located more than 100 ft from the unit as measured along the control voltage wires use No 18 AWG color coded wires to avoid excessive voltage drop 1 In replacement applications check the existing thermostat wiring for cracked or frayed insulation Replace any wiring in poor condition All wiring must comply with local codes and ordinances 2 Run wiring if nec...

Страница 14: ... supplied secondary drain pan Always refer to local and national codes INSTALLATION FINAL CHECKLIST Is power to the unit ON Are circuit breakers power disconnect inside of the unit ON Is ductwork sealed for airtight an fit Is the condensate drain line installed and run to an appropriate disposal site Test Run Test run in Heating Cooling and Emergency Heat mode as follows Is the thermostat level an...

Страница 15: ...ay cause the auxiliary electric heaters to operate to satisfy the call for heating To minimize energy costs do not increase the HEAT mode temperature set point by more than 2 F at a time Depending on the design of your home and its ventilation ductwork and registers areas of warm or cool air may develop throughout the home Operating the unit with the fan switch ON increases air mixing throughout t...

Страница 16: ...peration For proper operation a condensate drain line must be extended from the drain fitting on the right side of the unit to the perimeter of the home orto a proper drain location The drain line must be sloped towards the outside of the home or drain location and be protected from freezing NOTE In order for condensate to drain freely the unit must be installed level OPERATING THE VERT I PAK THER...

Страница 17: ...e Entrance doors are frequently opened and closed Laundryappliancesare being operated Ashoweris running More than the usual number of people are present in the home More than the normal number of electric lights are in use Drapes or blinds are open on the sunny side of the building or home HEATING CYCLE With the SYSTEM control of your indoor thermostat set to HEAT the heating section of your home ...

Страница 18: ...e extremely careful when handling parts or reaching into the unit REPLACE AI R FI LTER A dirty air filter reduces the efficiency of yourVert l Pak and allows lint and dirt to accumulate on the indoor air coil Lint and dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replaced as it becomes dirty To replace the filter front air return units 1 Slide the ...

Страница 19: ...ke and outdoor air exhaust paths must remain clear Check the OA exhaust frequently Keep it free of all debris snow or ice The OA intake should also be kept free of obstructions Blocking the OA exhaust or OA inta ke opening will reduce the efficiency of your unit could damage it and void your warranty INSPECT AND CLEAN CONDENSATE DRAIN The condensate drain must be routed to a suitable drainage area...

Страница 20: ...arts FRIEDRICH AIR CONDITIONING CO Post 0trice Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 Fax 210 357 4480 www friedrich com Printed in the U S A 920 164 00 10 03 ...

Отзывы: