Note: All field wiring must comply with NEC and local codes. It is the responsibility of the installer to insure that the electrical codes are met.

Electrical Requirements

Wire Size

Use 

ONLY

 wiring size recommended for single outlet branch circuit.

Fuse/Circuit Breaker

Use 

ONLY

 type and size fuse or HACR circuit breaker indicated on unit's rating plate (See sample on next page). Proper current 

protection to the unit is the responsibility of the owner. 

Grounding

Unit 

MUST

 be grounded from branch circuit to unit, or through separate ground wire provided on permanently connected units.  

Be sure that branch circuit or general purpose outlet is grounded.

Wire Sizing

Use recommended wire size given in tables and install a single branch circuit.  All wiring must comply with local and national 

codes.  NOTE: Use copper conductors only.

CAUTION

Electric shock hazard.

Turn 

OFF electric power before service or installation.

All electrical connections and wiring MUST be installed by a qualified electrician and 

conform to the National Electrical Code and all local codes which have jurisdiction.
Failure to do so can result in property damage, personal injury and/or death.

All 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specific chassis electri

-

cal requirements. See figure 8 for unit wiring and wall thermostat wiring. See page 7 for wire size. Use HACR 

type breakers to avoid nuisance trips. All field wiring must be done in accordance with NEC and local codes.

Sample Nameplate

MODEL NO 1

SERIAL NO *

FRIEDRICH AIR CONDITIONING CO. 

SAN ANTONIO, TEXAS

VOLTS: 24,33,34

VOLTAGE RANGE: 255-197

REFRIG CHARGE: 7 OZS. R22

DESIGN PRESSURE: 575 PSIG HS / 150 PSIG LS

COOLING: BTU/HR 8

SEER: 10               COP: 16

HEAT PUMP BTU/HR: 14

TOTAL COOLING AMPS: 9

TOTAL ELEC. HEAT AMPS: 15

ELECTRIC HEAT WATTS: 18

FOR PERMANENTLY CONNECTED UNITS ONLY:

 

COMP'. PLA 11 LRA 12

MOTOR: FLA 13 HP 19

HEATER AMPS: 17

MIN. CKT AMP ~0 USE ~1 MAX. TIME DELAY FUSE 

OR HACR TYPE CIRCUIT BREAKER.

GENERAL UNIT INFORMATION:

MAX OUTLET AIR TEMPERATURE: 2OO'F

MAX EXTERNAL STATIC PRESSURE ELECTRIC 

HEAT'..5 IN. WATER

"O" CLEARANCE TO COMBUSTIBLE MATERIAL

USE ON SINGLE OUTLET CIRCUIT ONLY

ELECTRICAL SHOCK AND 

MOVING PARTS HAZARD 

CAN CAUSE INJURY OR 

DEATH

PULL OUT DISCONNECT 

HEAD LOCATED ON THE 

FRONT OF THIS UNIT TO 

DISABLE POWER BEFORE 

SERVICING.

 

  

LISTED

 

   120524

HEATING AND

COOLING EQUIPMENT

APPLICABLE PATENTS: US 

6,065,296

NY MEA NO.: 295-00-E

USE ONE OF THE 

FOLLOWING ITEMS 

FROM EACH CATEGORY 

TO COMPLETE THE 

ASSEMBLY

WALL PLENUM:

VPAWP1 -8

VPAWP1 -14

OUTDOOR GRILLE

VPAL2

INDOOR GRILLE

VPRG1

VPRG2

VPRG5

SAMP

LE

WARNING

Electrical Rating Tables

NOTE:  Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for overseas applications

Recommended branch circuit wire sizes*

Nameplate maximum circuit breaker size

AWG  Wire size**

15A

14

20A

12

30A

10

AWG — American Wire Gauge * Single 

circuit from main box. ** Based on copper 

wire, single insulated conductor at 60°C

Содержание VE09K50

Страница 1: ...920 075 09 11 07 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 9 000 18 000 BTU h INSTALLATION OPERATION GUIDE...

Страница 2: ...d Thermostat Wiring Diagrams 11 Chassis Operation Fresh Air Door 12 Low Ambient Protection 12 Room Freeze Protection 12 Emergency Heat Override 12 Emergency Heat Operation 12 Service Servicing Chassis...

Страница 3: ...louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 should be kept 12 24 60 VPAK VPAK VPAK POL...

Страница 4: ...1Ph 60Hz NOMINAL CAPACITY A Series Btu h 09 9 000 12 12 000 DESIGN SERIES A 32 47 Cabinet SERIES V Vertical Series 18 18 000 24 24 000 E Cooling with electric heat H Heat Pump Refer to electrical dat...

Страница 5: ...ge 7 for wire size Use HACR type breakers to avoid nuisance trips All field wiring must be done in accordance with NEC and local codes Sample Nameplate MODEL NO 1 SERIAL NO FRIEDRICH AIR CONDITIONING...

Страница 6: ...ions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis installation Figure 3 Typical Utility Closet Chassis Shown in Closet...

Страница 7: ...ide wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the floor...

Страница 8: ...first stage increases energy efficiency utilizing a factory installed fan that slings the cold condensate onto the hot outdoor coil Part 2 When high outdoor humidity prevents the slinger from disposin...

Страница 9: ...talled in accordance with the VPAWP1 8 1 14 Installation Manual B Place the chassis into the closet with the outdoor side facing the wall plenum opening C Slide the chassis into the wall plenum until...

Страница 10: ...ol box and under the control components in the box to reach the connection terminal for the wiring 4 Make the wire connections appropriately matching the wires as the shown in the wiring diagram 5 Onc...

Страница 11: ...09 NOTE THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM AND SCHEMATIC CONNECTION TERMINAL Electrical Thermostat Wiring Diagram...

Страница 12: ...sh Air Door is an intake system The fresh air door is opened via a slide on the front of the chassis located just above the indoor coil Move the slide left to open and right to close the fresh air doo...

Страница 13: ...f your Vert I Pak and allows lint and dirt to accumulate on the indoor air coil Lint and dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replaced as it...

Страница 14: ...coil Fan motor failure Restricted air flow Non condensables in refrigeration system 07 I D coil temperature 30 Deg F for 2 consecutive minutes Alternately flash set point and error code Continue fan o...

Страница 15: ...pecial color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum DIMENSIONS 31 1 16 high x 25 9 16 wide Same as VPAWP1 8 bu...

Страница 16: ...n contact the Friedrich Air Conditioning Company International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must...

Отзывы: