50
Troubleshooting Heating
(Heat pumps)
PROBLEM
TO CORRECT
POSSIBLE CAUSE
Set thermostat to a warmer position.
Replace — do not attempt to adjust.
Check compressor wiring. Check for open internal
or external overload. Check wiring.
Test system switch
Thermostat setting.
Defective thermostat.
Compressor not operating.
Defective system switch.
No heating — fan
operates.
Clean as recommended in Owner’s Manual.
Check if outdoor thermostat is energizing the heating
element at its predetermined temperature setting
Check control setting.
TO CORRECT
POSSIBLE CAUSE
PROBLEM
Restricted filter.
Outdoor thermostat.
(Applicable models.)
Fresh air or exhaust door open.
Insufficient heating.
TO CORRECT
POSSIBLE CAUSE
PROBLEM
Check continuity of switch.
Check applicable wiring diagram.
Inoperative system switch.
Incorrect wiring.
Fan operates in
"constant" position, but
not in "automatic"
(MoneySaver).
TO CORRECT
PROBLEM
POSSIBLE CAUSE
Incorrect differential setting. Replace thermostat.
Check voltage to resistor. If voltage okay, remove
resistor from thermostat bulb block. With current on,
feel resistor for warmth. If no heat can be felt,
replace anticipator.
Defective thermostat.
Heat anticipator (resistor) shorted.
(Applicable models)
Temperature varies from
comfortable to overly
warm.
TO CORRECT
PROBLEM
POSSIBLE CAUSE
Room temperature
uneven.
(Heating cycle)
Disconnect power to unit. Remove resistor from
thermostat bulb block. Plug in unit and allow to
operate. Feel resistor for heat. If no heat is felt,
replace resistor.
Replace thermostat and check.
Refer to appropriate wiring diagram. Resistor is
energized during the "on" cycle of compressor or
fan.
Heat anticipator (resistor) shorted.
(Applicable models.)
Wide differential — partial loss of
thermostat bulb charge.
Incorrect wiring.
TO CORRECT
POSSIBLE CAUSE
PROBLEM
Refer to appropriate wiring diagram.
Check for voltage at "TM" and "TM1" on timer. If
voltage, replace control.
If outside coil temperature is 25° F or below, and
preselected time limit has elapsed, replace the
defrost control.
If the contacts remain closed between terminals "2"
and "3" of the defrost control after preselected time
interval has passed, replace control.
Reinstall and assure that good bulb to coil contact is
made.
Incorrect wiring.
Defrost control timer motor not advanc-
ing.
Defrost control out of calibration.
Defrost control contacts stuck.
Defrost control bulb removed from coil,
or not making good coil contact.
Unit will not defrost.
Содержание SM21J30A4
Страница 56: ...56 WIRING DIAGRAM FOR MODELS RS10J101 RS10J103 RS12J101 RS12J103 RS15J301 RM18J30 RM15J101 RM18J302 RM18J303...
Страница 57: ...57 Wiring Diagram for Models SQ05J10A 1 SQ06J10A 1 SQ07J10A 1 SQ08J10B 1...
Страница 58: ...58 WIRING DIAGRAM FOR MODELS KQ05J10A 1 KQ05J10A 3 KQ06J10A 1 KQ06J10A 3 KQ08J10A 1 617 581 04...
Страница 59: ...59 WIRING DIAGRAM FOR MODEL YQ06J10A 1 617 581 05...
Страница 60: ...60 WIRING DIAGRAM FOR MODEL SC06H10D...
Страница 62: ...62 WIRING DIAGRAM FOR MODELS SL24J30A 1 SL24J30A 3 SL28J30A 1 SL33J30 2...
Страница 63: ...63 Wiring Diagram for KS KM KL Models...
Страница 64: ...64 WIRING DIAGRAM FOR MODELS ES12J33 ES15J33A EM18J34A EL24J35 EL33J35 EK12J33A EK18J34A 2 EK18J34A 3...
Страница 65: ...65 WIRING DIAGRAM FOR MODELS YS13J33 YM18J34A YL24J35A...
Страница 66: ...66 WIRING DIAGRAM FOR MODEL YS09J10A...