R-410A SEALED SYSTEM REPAIR
Gas Charging (After Repair)
– Open the valve at the bottom of the cylinder and press the
– Connect the charge hose which you dis-connected from the
vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a scale and reverse
the cylinder so that the system can be charged with liquid.
check valve on the charge set to purge the air. (Be careful of
the liquid refrigerant).
–
–
Stopping partway will allow the gas to be discharged.
If the system has been charged with liquid refrigerant while
operating the air conditioner turn off the air conditioner before
disconnecting the hose.
– Tighten the service port nut.
– Be sure to check for gas leakage.
Lo
Open
Open
3-Way
valve
Gas side
CLOSE
3-Way
valve
OPEN
Outdoor unit
Liquid side
Indoor unit
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
- Weigh in the refrigerant amount listed on the rating plate, adding
additional refrigerant as needed for long line set length.
- If the temperature does not allow full liquid charge, run the system
in air conditioning and throttle refrigerant in at 0.2 oz/min. Allow the
system pressure to stabilize each time.
Содержание MRM09Y1J
Страница 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Страница 37: ...37 OPERATION 18 24kSequenceofOperation...
Страница 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Страница 39: ...39 OPERATION 18 24k Sequence of Operation...
Страница 40: ...40 OPERATION 18 24k Sequence of Operation...
Страница 41: ...41 OPERATION 18 24k Sequence of Operation...
Страница 47: ...47 INSTALLATION...
Страница 48: ...48 INSTALLATION Installation Tools...
Страница 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Страница 113: ...113 WIRING DIAGRAMS Figure 804 36K Indoor Unit Wiring Diagrams Figure 803 24K Indoor Unit Wiring Diagram 6361000043101...
Страница 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Страница 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Страница 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Страница 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Страница 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...
Страница 130: ...130 PARTS CATALOG Outdoor Unit MRMY36J FIgure 907 2 9 10 18 20 21 11 12 14 15 22 23 26 27 32 34 4 1...