background image

1

2

3

4

1

2

3

4

5

G

G

1.

Check if the piping connections are secure.

2.

Check that the stems of 2-way valve and 3-way valve are closed
fully.

3.

Connect the gauge manifold charge hose to the charging port
of the 3-way valve (side with the projection for pushing in the
valve core).

4.

Open the low pressure side valve of the gauge manifold fully.

5.

Operate the vacuum pump and start pump down.

6.

Slowly loosen the flare nut of the 3-way valve and check if air
enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)

OUTDOOR UNIT

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the
outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do
not operate it during the following work.

Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trouble.

Connector cover removal

Remove the two mounting screws.

Installing the connector cover

(1) After inserting the three front hooks, then insert the rear hook.
(2) Tighten the two mounting screws.

Fig. 9

7.

Pump down the system for at least 15 minutes, then check if the
compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

8.

At the end of pump down, close the low pressure side gauge of
the gauge manifold fully and stop the vacuum pump.

9.

Slowly loosen the valve stem of the 3-way valve. When the
compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose
from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)

ELECTRICAL WIRING (OUTDOOR UNIT)

1. Remove the screws, then remove the control box cover.
2. Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut.
3. Connect inter-unit wire harness and power supply to the terminal.

 Refer to the wiring diagram

4. Use the screws to install the control box cover.

WARNING

Be sure to comply with local codes while run-
ning the wire from the indoor unit to the out-
door unit (size of wire and wiring method, etc. ).

Every wire must be connected firmly.

No wire should be allowed to touch refrigerant
tubing, the compressor or any moving part.

Loose wiring may cause the terminal to over-
heat or result in unit malfunction. A fire hazard
may also exist. Therefore, be sure all wiring is
tightly connected.

Connect wires to the matching numbers of
terminals.

NOTE:

Connector trade size for this unit is 1/2” (12.7 mm). The connec-
tor can be bought at a hardware store. Refer to 

How to connect

wiring to the terminals

 for instructions on connecting depend-

ing on the wire type you are using.

The fuse located in the outdoor unit provides power supply pro-
tection and may blow when power is applied if the system has
been incorrectly wired.

G

G

11

G

G

33

22

11

22

33

208/230V

208/230V

208/230V

208/230V

208/230V

208/230V

55

(L)(L)

(N)(N)

44

Indoor unit

Terminal

Grounding line

Control line

(Inter Unit)
Power line

DISCONNECT
SWITCH
(FIELD SUPPLY)

Outdoor unit

Terminal

POWER SUPPL

Y

1 phase, 208/230V

Earth screw

Indoor unit
terminal block

Outdoor unit
terminal block

Disconnect switch

Earth screw

Power supply line

Lock nut

Cord Clamp

Conduit
connector

Power supply

Inter-unit
wire harness

Fig. 11

WARNING

(1) Install the unit where it will not be tilted by more

than 5°.

(2) When installing the outdoor unit where it may ex-

posed to strong wind, fasten it securely.

Tapping screw

Rear hooks

Connector cover

Front hooks

Table 6

Tightening torque

Blank cap (2-way valve)

14.47 to 18.08 ft•lbs (200 to 250 kgf•cm)

Blank cap (3-way valve)

20.25 to 23.15 ft•lbs (280 to 320 kgf•cm)

Charging port cap

9.04 to 11.57 ft•lbs (125 to 160 kgf•cm)

10. Fully open the valve stems of the 2-way valve and 3-way valve

using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.17ft •lbs (30 kgf•cm) until it
stops turning.)

11. Firmly tighten the 2-way valve and 3-way valve blank cap and

the charging port cap.

LO

HI

Fig. 10

Flare nut

3-way valve

-0.1 MPa
(-76 cmHg
-1 bar)

High
pressure
side valve
(closed)

2-way valve

Gauge manifold

Compound pressure gauge

Pressure gauge

Low pressure
side valve

Blank cap

Charge
hose

Vacuum pump

Valve stem

Charge hose

Charging port cap

Charging port

CAUTION

(1) Refrigerant must not be discharged into atmos-

phere.

(2) After connecting the piping , check the joints for

gas leakage with gas leak detector.

Содержание MR18C3F

Страница 1: ...re the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation fo...

Страница 2: ...e shaped by your hands Be careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than three times OK NO Extend the pipe by unwinding it 2 INSTALLING THE WALL HOOK BRACKET INDOOR UNIT 1 CUTTING THE HOLE IN THE WALL FOR T...

Страница 3: ...ssories are supplied Use them as required INDOOR UNIT ACCESSORIES Connection pipe assembly Connection cord 3 conductor Wall pipe Decorative tape Vinyl tape Wall cap Saddle Drain hose Tapping screws Sealant Name Q ty 1 1 1 1 1 1 1 set 1 1 set 1 ELECTRICAL REQUIREMENT Always make the air conditioner power supply a special branch cir cuit and provide a special switch and receptacle Do not extend the ...

Страница 4: ... with local codes while run ning the wire from the indoor unit to the out door unit size of wire and wiring method etc Every wire must be connected firmly No wire should be allowed to touch refrigerant tubing the compressor or any moving part Loose wiring may cause the terminal to over heat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected...

Страница 5: ...r wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using pliers bend the solid wire to form a loop suitable for the termi nal screw 4 Shape the loop wire properly place it on the terminal board and tighten securely with the terminal screw using a screwdriver B For strand wiring 1 Cu...

Страница 6: ...ir conditioner is run by pressing the test run button the OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly 1 INDOOR UNIT 1 Is operation of each button on the remote control unit normal 2 Does each lamp light normally 3 Do the air flow direction louver operate normally 4 Is the drain normal 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation...

Страница 7: ...t be affected by the heat from a stove etc 1 REMOTE CONTROL UNIT HOLDER INSTALLATION Install the remote control unit with a distance of 23 ft 7 m between the remote control unit and the photocell as the criteria However when installing the remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control ...

Отзывы: