SPLIT TYPE ROOM AIR CONDITIONER

INSTALLATION MANUAL

(P/N 9315140104-01)                                                     ENGLISH

(MODEL: MW18Y3F/MR18Y3F, MW18C3F/MR18C3F)

IMPORTANT!
Please Read Before Starting

This air conditioning system meets strict safety and operating standards.
As the installer or service person, it is an important part of your job to
install or service the system so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

Observe all local, state, and national electrical codes.

Pay close attention to all danger, warning, and caution notices given in
this manual.

WARNING:

This symbol refers to a hazard or unsafe practice which
can result in severe personal injury or death.

CAUTION:

This symbol refers to a hazard or unsafe practice which
can result in personal injury and the potential for product
or property damage.

Hazel alerting symbols

Electrical

Safety / alert

If Necessary, Get Help

These instructions are all you need for most installation sites and mainte-
nance conditions. If you require help for a special problem, contact our
sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper installation
or maintenance service, including failure to follow the instructions in this
document.

SPECIAL PRECAUTIONS

When Wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL
INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.

Do not supply power to the unit until all wiring and tubing are completed
or reconnected and checked.

Highly dangerous electrical voltages are used in this system. Carefully
refer to the wiring diagram and these instructions when wiring. Improper
connections and inadequate grounding can cause 

accidental injury

or death

.

Ground the unit

 following local electrical codes.

Connect all wiring tightly. Loose wiring may cause overheating at con-
nection points and a possible fire hazard.

5 cm or over

The basic installation work procedures are the same as conventional refrigerant (R22) models.

 However, pay careful attention to the following points:

(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant(R22) mod-

els, some of the piping and installation and service tools are special.(See the table below.)

Especially, when replacing a conventional refrigerant(R22) model with a new refrigerant R410A
model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.

(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent

erroneous charging with conventional refrigerant(R22) and for safety. Therefore, check
beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]

(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with

refrigerant(R22) models. Also, when storing the piping ,securely seal the opening by pinching,
taping, etc.

(4) When charging the refrigerant, take into account the slight change in the composition of the gas

and liquid phases, and always charge from the liquid phase side whose composition is stable.

This air conditioner uses new refrigerant HFC (R410A).

When Transporting

Be careful when picking up and moving the indoor and outdoor units.
Get a partner to help, and bend your knees when lifting to reduce strain
on your back. Sharp edges or thin aluminum fins on the air conditioner
can cut your fingers.

When Installing...

...In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the unit’s weight. It
may be necessary to construct a strong wood or metal frame to provide
added support.

...In a Room

Properly insulate any tubing run inside a room to prevent “sweating”
that can cause dripping and water damage to walls and floors.

...In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the outdoor unit. This prevents water damage and abnor-
mal vibration.

...In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air baffle.

...In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than drifting
snow. Provide snow vents.

When Connecting Refrigerant Tubing

Keep all tubing runs as short as possible.

Use the flare method for connecting tubing.

Apply refrigerant lubricant to the matching surfaces of the flare and
union tubes before connecting them, then tighten the nut with a torque
wrench for a leak-free connection.

Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either nar-
row or wide. Therefore, to avoid confusion the refrigerant tubing for your
particular model is specified as either “small” or “large” rather than as
“liquid” or “gas”.

When Servicing

Turn the power OFF at the main circuit breaker panel before opening
the unit to check or repair electrical parts and wiring.

Keep your fingers and clothing away from any moving parts.

Clean up the site after you finish, remembering to check that no metal
scraps or bits of wiring have been left inside the unit being serviced.

After installation, explain correct operation to the customer, using the
operating manual.

Special tools for R410A

Contents of change

Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous
mixing of other refrigerants, the diameter of each port has been changed.

It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.

-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

To increase pressure resistance, the hose material and base size were changed.

A conventional vacuum pump can be used by installing a vacuum pump adapter.

Special gas leakage detector for HFC refrigerant R410A.

Tool name

Gauge manifold

Charge hose

Vacuum pump

Gas leakage detector

Copper pipes

It is necessary to use seamless copper pipes and it is desirable
that the amount of residual oil is less than 40 mg/10m. Do not
use copper pipes having a collapsed, deformed or discolored
portion (especially on the interior surface). Otherwise, the ex-
pansion value or capillary tube may become blocked with con-
taminants.
As an air conditioner using R410A incurs pressure higher than
when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table1.Never use copper pipes thinner than 0.8mm even
when it is available on the market.

Table 1   Thicknesses of Annealed Copper Pipes

Thickness (mm)

Nominal

diameter

1/4

1/2

Outer diameter

(mm)

6.35

12.7

R410A

0.80

0.80

[ref.] R22

0.80

0.80

(1) Do not use the existing (for R22) piping and flare nuts.

• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury,

etc.(Use the special R410A materials.)

(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A)

to enter the refrigerant cycle.

• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value

and cause breakage, injury, etc.

 WARNING

CAUTION

When installing pipes shorter than 3m, sound of the outdoor unit will be transferred to the indoor unit, which will
cause large operating sound or some abnormal sound.

Содержание MR18C3F

Страница 1: ...re the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation fo...

Страница 2: ...e shaped by your hands Be careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than three times OK NO Extend the pipe by unwinding it 2 INSTALLING THE WALL HOOK BRACKET INDOOR UNIT 1 CUTTING THE HOLE IN THE WALL FOR T...

Страница 3: ...ssories are supplied Use them as required INDOOR UNIT ACCESSORIES Connection pipe assembly Connection cord 3 conductor Wall pipe Decorative tape Vinyl tape Wall cap Saddle Drain hose Tapping screws Sealant Name Q ty 1 1 1 1 1 1 1 set 1 1 set 1 ELECTRICAL REQUIREMENT Always make the air conditioner power supply a special branch cir cuit and provide a special switch and receptacle Do not extend the ...

Страница 4: ... with local codes while run ning the wire from the indoor unit to the out door unit size of wire and wiring method etc Every wire must be connected firmly No wire should be allowed to touch refrigerant tubing the compressor or any moving part Loose wiring may cause the terminal to over heat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected...

Страница 5: ...r wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using pliers bend the solid wire to form a loop suitable for the termi nal screw 4 Shape the loop wire properly place it on the terminal board and tighten securely with the terminal screw using a screwdriver B For strand wiring 1 Cu...

Страница 6: ...ir conditioner is run by pressing the test run button the OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly 1 INDOOR UNIT 1 Is operation of each button on the remote control unit normal 2 Does each lamp light normally 3 Do the air flow direction louver operate normally 4 Is the drain normal 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation...

Страница 7: ...t be affected by the heat from a stove etc 1 REMOTE CONTROL UNIT HOLDER INSTALLATION Install the remote control unit with a distance of 23 ft 7 m between the remote control unit and the photocell as the criteria However when installing the remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control ...

Отзывы: