background image

 

 

 

 

 

 

 

   

 

 

 

 

 

 

                       

6

   

SH20N50AT and SH24N20AT Adhere to the following certifications:

CERTIFIED  PER STD. NO. ANSI/ISA 12.12.01,2013

PER STD. NO. IEC 60079-0, 6th Edition PER STD. NO. IEC 60079-15, 4th Edition

PER STD. NO. CAN/CSA C22.2 NO. 213-M1987

PER STD. NO. CENELEC EN 60079-0: 2012 + A11: 2013 

PER STD. NO. CENELEC EN 60079-15: 2010

 

CERTIFICATION  DEMKO 15 ATEX 1364X 

II 3 G Ex nA nC IIC T4 Gc

IECEX UL15.0051X 

DEMKO 15 ATEX 1364X

SH20N50AT & SH24N20AT

Specific Conditions of  Use:

 

•  Provision shall be made to prevent the rated voltage being exceeded by 

the transient disturbances of more than 140% of the peak rated voltage..

•  The equipment must be installed only for use in locations providing 

adequate protection against the entry of solid foreign objects or water 

capable of impairing safety.

•  Only permanently wired cables may enter the cable glands. The user 

shall provide for the required strain relief.

•  Degree of protection will be safeguarded only when sealing and cable 

entry fittings are properlyfitted. The Manufacturer’s instructions must 

be followed.

•  Cable Glands shall be mounted into the enclosurein such a way that they 

are mechanically protected  against impact force.

•  To avoid the buildup of electrostatic charge, regularly clean the unit with 

a damp cloth.

•  The appliance is not to be used by persons (including children) with 

reduced physical, sensory or mental capabilities, or lack of experience 

and knowledge, unless they have been given supervision or instruction. 

Children to be supervised not to  play with the appliance.

NOTICE: To maintain IP44 protection, the Hazardgard 

unit must be installed in accordance to the installation 

instructions stated in this document.

The following additional previous editions of Standards noted under 

the “Standards” section of this Certificate where applied to integral 

Components as itemized below. There are no significant safety related 

changes between these previous editions and the editions noted

under the “Standards” section.
Junction Box, Part No. 25. 10 16

08, manufactured by Rose.

IEC 60079-7:2006-

07, IEC 60079-31:

ATEX & ICEX Standards Specific to Models SH20N50AT & SH24N20AT

 

Отзывы: