Friedrich D30A Скачать руководство пользователя страница 6

—6—

1.5.1 HOW DOES THE DEHUMIDIFIER WORK?

Moist, humid air is drawn over a cold refrigerated
dehumidifying coil. Moisture in the air condenses on this
coil and drains into a bucket (or through the bucket into a
hose and drain).
Dry, clean air is drawn over the condenser where it is
actually heated several degrees and discharged out the
front grille into the room. (See Figure 3)

It is normal for the surrounding air to become
slightly warmer as the dehumidifier operates.

This warming effect further reduces the relative humidity
of the surrounding air.

1.5.2 LOCATION FOR THE DEHUMIDIFIER

Allow at least 12 inches of space on all sides of the
unit for good air circulation. (See Figure 4)

The dehumidifier must be operated in an enclosed
area to be most effective.

Close all doors, windows and other outside
openings to the room.

Place the dehumidifier in a location that does not
restrict air flow into the rear coil or out the front grille.

The operation of dehumidifier in a basement will have
little or no effect in drying an adjacent enclosed
storage area, such as a closet, unless there is
adequate circulation of air in and out of the area.

Dry

Air Out

Humid

Air In

Fan

Condenser

Evaporator

Motor

Drain
Connection

Compressor

Bucket

12"

12"

Figure 3

Figure 4

1.5 HOW TO OPERATE DEHUMIDIFIER

1.5.3 MICRO SWITCH

The micro switch assembly, which is located on the drain pan of inside unit, automatically shuts off the dehumidifier when the
bucket is full (note, the Auto Shut Off lights, to indicate bucket must be emptied). The bucket replaces in its place, the unit again
turns itself on.

1.5.4 AUTO DEFROST

When frost builds up on the cooling coils, the unit will automatically cycle off until the frost disappears. The fan continues to run.

NOTE: The unit is designed to be operated at temperature above 65°F(18°C) in normal condition. If the dehumidifier is

operated in low temperature conditions, the temperature and humidity conditions of room are low, some frost
can be formed in its evaporator coil and the unit will be operated ON/OFF repeatedly. In this case, please check
on your room temperature condition and stop the unit.

Содержание D30A

Страница 1: ...Dehumidifier Service and Parts Manual D30A D40A D50A D65A 03 03 D30A D40A D50A D65A...

Страница 2: ...ILTER 10 3 1 2 FRONT CASE AND TOP COVER 10 3 1 3 CABINET AND CONTROL BOX 10 3 2 CONTROL PARTS 11 3 2 1 POWER CORD ASSEMBLY 11 3 2 2 SENSOR ASSEMBLY 11 3 2 3 PWB PCB ASSEMBLY MAIN 11 3 2 4 CAPACITOR 11...

Страница 3: ...ing prong or alter the plug in any manner at any circumstances 1 2 FEATURES AND DIMENSIONS 1 2 1 FEATURES Quiet operation High efficiency Adjustable humidistat Automatic defrost Automatic shut off Buc...

Страница 4: ...PROTECTOR FOR COMPRESSOR INTERNAL PROTECTOR FUSE FOR MOTOR CAPACITOR 40 F 200VAC 30 F 270VAC 35 F 270VAC MOTOR ASSEMBLY SINGLE Shaded pole motor 65W 1A Thermal cutoff 266 F 130 C SWITCH ASSEMBLY MICRO...

Страница 5: ...imer button is pressed the Timer indicator lights shift as follows Continuous 2 Hr On Off 4 Hr On Off Continuous Humidity Control This button controls the humidity in the room Press button to raise th...

Страница 6: ...difier in a basement will have little or no effect in drying an adjacent enclosed storage area such as a closet unless there is adequate circulation of air in and out of the area Dry Air Out Humid Air...

Страница 7: ...button to stop the unit manually 1 5 6 DRIER D30A Dryer is used to prevent capillary blockage from moisture in the refrigerant system and H E condenser and evaporator Also dryer is used to remove cor...

Страница 8: ...3 6 5 4 BL M C S O L P COMP Q TY PER SET 1 1 1 1 1 1 1 1 1 RE MARKS S S S S S S S S S LOCATION NO 1 2 3 4 5 6 7 8 9 DESCRIPTION POWER CORD ASSEMBLY MOTOR ASSEMBLY SINGLE P T C ASSEMBLY RE COMPRESSOR...

Страница 9: ...1 RE MARKS S S S S S S S S S LOCATION NO 1 2 3 4 5 6 7 8 9 DESCRIPTION POWER CORD ASSEMBLY MOTOR ASSEMBLY SINGLE CAPACITOR COMPRESSOR ROTARY SET O L P ASSEMBLY PWB PCB ASSEMBLY DISPLAY SENSOR ASSEMBL...

Страница 10: ...ver and cabinet 4 Separate the top cover See Figure 10 3 1 3 CABINET AND CONTROL BOX Upper 1 Remove the bucket air filter and top cover according to the procedure above 2 Remove a screws which fasten...

Страница 11: ...Disconnect housing from micro switch assembly See Figure 14 3 2 3 PWB PCB ASSEMBLY MAIN 1 Disconnect all leads of the motor and the compressor from PWB PCB ASSEMBLY MAIN 2 Remove a screw which fasten...

Страница 12: ...ssembly to heat exchanger and drain pan and lift housing assembly upward after unhooking 2 hooks on the housing See Figure 18 2 Remove a screw that secures housing and orifice and separate the orifice...

Страница 13: ...of each condenser and evaporator See Figure 24 8 Remove 4 screws between condenser and evaporator See Figure 24 3 3 2 P T C OR OVERLOAD PROTECTOR O L P FOR RECIPROCATING COMPRESSOR D30A 1 Discharge t...

Страница 14: ...Open valve A and allow the proper charge to enter the system Valve B is still closed 4 If more charge is required the high side will not take it Close valve A 5 With the unit running open valve B and...

Страница 15: ...B A COMPRESSOR COMPOUND GAUGE MANIFOLD GAUGE SEE INSETS BELOW B A COMPRESSOR EXTERNAL VACUUM PUMP CHARGING CYLINDER HI LOW CAPILLARY TUBE COMPOUND GAUGE MANIFOLD GAUGE SEE INSETS BELOW A B A B C COND...

Страница 16: ...ots on both sides of the bucket are positioned correctly Doors and windows may not be closed tightly Check that all doors windows and other openings are securely closed Make sure there are no curtains...

Страница 17: ...103 5V and 126 5V If not within limits call an electrician Check the wire connections If loose repair or replace the terminal If the wires are disconnected refer to wiring diagram for identification...

Страница 18: ...it Replace compressor Tighten them If knocking sounds continue when running or loose replace the motor If the motor hums or noise appears to be internal while running replace motor assembly The bucke...

Страница 19: ...0A 19 268714 336610 336600 359012 349480 346811 354210 667482 558511 35211A 352113 552111 349600 554030 550140 554160 567502 148380 135500 436500 330870 266011 130411 152302 130910 144410 264110 24995...

Страница 20: ...Z 268714 336610 336600 359012 349480 346811 354210 35211A 352113 349600 554030 148380 235512 135500 436500 330870 266011 130411 152302 130910 144410 264110 249950 162615 131110 550140 567502 554160 55...

Страница 21: ...10 336600 359012 349480 346811 354210 35211A 349600 554030 148380 235512 135500 436500 330870 266011 130411 152302 130910 144410 249950 162615 131110 W0CZZ 268714 264110 352111 552113 567502 554160 55...

Страница 22: ...10 336600 359012 349480 346811 354210 35211A 349600 554030 148380 235512 135500 436500 330870 266011 130411 152302 130910 144410 249950 162615 131110 W0CZZ 268714 264110 567502 552111 352113 554160 55...

Страница 23: ...1A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20812A 352113 TUBE DISCHARGE 5210A21843A 354210 EVAPORATOR ASSEMBLY 5421A20131A 336600 HOUSING ASSEMBLY 3660A10003A 550140 ISOLATOR COMP 5040AR4195A 5...

Страница 24: ...11 MOTOR ASSEMBLY SINGLE 4681A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20781A 352113 TUBE ASSEMBLY DISCHARGE SINGLE 5211A20780A 354210 EVAPORATOR ASSEMBLY 5421A20131A 336600 HOUSING ASSEMBLY 36...

Страница 25: ...11 MOTOR ASSEMBLY SINGLE 4681A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20875A 352113 TUBE ASSEMBLY DISCHARGE SINGLE 5211A20934A 354210 EVAPORATOR ASSEMBLY 5421A20133A 336600 HOUSING ASSEMBLY 36...

Страница 26: ...11 MOTOR ASSEMBLY SINGLE 4681A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20869A 352113 TUBE ASSEMBLY DISCHARGE SINGLE 5211A20931A 354210 EVAPORATOR ASSEMBLY 5421A10033A 336600 HOUSING ASSEMBLY 36...

Страница 27: ...in the U S A Post Office Box 1540 4200 N Pan Am Expressway San Antonio Texas 78295 1540 210 357 4400 FAX 210 357 4480 FRIEDRICH AIR CONDITIONING CO Visit our web site at www friedrich com P NO 3828A20...

Отзывы: