Thermozone AD Corinte A/E - ADCS
26
GB
curtain. The ventilation should therefore be
balanced.
Vertical mounting
The unit is mounted vertically on the floor
with the exhaust opening facing outwards.
Before installation, decide whether any elec-
trical connections or water connections are to
be made from below.
Leave the protective plastic in place during
installation. Take care to avoid damaging the
surfaces. For installation see Figure 3.
1. Remove the two screws that secure the in-
take grille (A) and remove this.
2. Undo the screws holding the front panel (C)
on the exhuast side (B).
3. Undo the two screws in the front panel and
remove it.
4. Place the edging in level on the floor and se-
cure it through the countersunk holes (see
Fig. 7). Place the air curtain on the edging.
5. A flat bar is included for securing the air
curtain. Fixate the air curtain through the
square-shaped hole. Make sure that the flat
bar is not bent when fixing.
6. Secure the top with an angle bracket or
similar to prevent the air curtain from
toppling over. There is a hole in the centre
of the top of the air curtain with an internal
M8 thread for securing the bracket.
7. Hook the front panel (C) onto the edge on
the intake side (A), close and press it into
the slot on the exhaust side (B).
8. Fasten the two screws in the front panel.
9. Secure the front panel on the exhaust side.
10. Replace the intake grille. (A)
To remove dirt and finger prints, polish the
panels with a suitable cleanser. Any print that
may be on the panels is removed with a suita-
ble solvent.
Horizontal mounting
The unit is mounted with the outlet facing
downwards. Do not remove the protective
plastic until mounting is completed. Take care
not to damage the surfaces.
For optimal performance it is recommended
that a minimum gap of 220 mm to the ceiling
General instructions
Read these instructions carefully before in-
stallation and use. Keep this manual for future
reference.
The guarantee is only valid if the Thermo-
zone units are used in the manner intended
by the manufacturer and in accordance with
the Frico installation and maintenance in-
structions.
Application area
AD Corinte belongs to a new generation of
intelligent air curtains with SIRe integrated
controls, together they can provide fully auto-
matic protection for the entrance, adaptable
to each area of use.
AD Corinte is intended for exclusive shop
entrances and other environments with high
demands in respect of design and soundlevel.
Mounted with one unit on either side of the
opening, thus creating a classic symmetry, the
curtain effect and comfort is optimized.
The Thermozone AD Corinte air curtain is
supplied with or without an electric heater
coil and is intended for permanent installa-
tion above or beside entrance doors and other
openings up to 3,5 metres in height.
Protection class IP20
Operation
Air is drawn in at the top/rear of the unit and
blown out downwards/outwards so that it
shields the door opening and minimizes heat
loss. To achieve the optimum curtain effect
the unit must extend the full height/width of
the door opening.
During installation the exhaust grille is
normally directed outwards slightly so that
the airflow obstructs incoming cold air. (See
fig 1).
The fan speed should be controlled using a
frequency converter.
The efficiency of the air curtain(s) depends
on the air temperature, pressure differences
across the doorway and any wind pressure.
NOTE! Negative pressure in the building
considerably reduces the efficiency of the air
Assembly and operating instructions
Содержание Thermozone AD Corinte A - ADCS
Страница 1: ...AD Corinte A E ADCS 26 GB 23 SE 29 RU ...
Страница 3: ...AD Corinte A E ADCS 3 1 2 80 60 1 2 60 80 3 Ø22 Cu 2200 2450 500 350 Fig 2 ...
Страница 4: ...AD Corinte A E ADCS 4 1 2 3 4 5 6 7 8 9 10 A B C Fig 3 ...
Страница 5: ...AD Corinte A E ADCS 5 Fig 4 ...
Страница 6: ...AD Corinte A E ADCS 6 80 35 ø12 180 35 25 40 Fig 6 Fig 7 360 243 Ø22 Ø10 15 5 10 Fig 5 ...
Страница 8: ...AD Corinte A E ADCS 8 Fig 10 SIRe ...