Thermozone AD Corinte A/E - ADCS

26

GB

curtain. The ventilation should therefore be 
balanced.

Vertical mounting

The unit is mounted vertically on the floor 
with the exhaust opening facing outwards.

Before installation, decide whether any elec-

trical connections or water connections are to 
be made from below.

Leave the protective plastic in place during 

installation. Take care to avoid damaging the 
surfaces. For installation see Figure 3. 
1. Remove the two screws that secure the in-

take grille (A) and remove this.

2. Undo the screws holding the front panel (C) 

on the exhuast side (B).

3. Undo the two screws in the front panel and 

remove it. 

4. Place the edging in level on the floor and se-

cure it through the countersunk holes (see 
Fig. 7). Place the air curtain on the edging.

5. A flat bar is included for securing the air 

curtain. Fixate the air curtain through the 
square-shaped hole. Make sure that the flat 
bar is not bent when fixing. 

6. Secure the top with an angle bracket or 

similar to prevent the air curtain from 
toppling over. There is a hole in the centre 
of the top of the air curtain with an internal 
M8 thread for securing the bracket.

7. Hook the front panel (C) onto the edge on 

the intake side (A), close and press it into 
the slot on the exhaust side (B).

8. Fasten the two screws in the front panel.
9. Secure the front panel on the exhaust side.
10. Replace the intake grille. (A)
To remove dirt and finger prints, polish the 
panels with a suitable cleanser. Any print that 
may be on the panels is removed with a suita-
ble solvent.

Horizontal mounting

The unit is mounted with the outlet facing 
downwards. Do not remove the protective 
plastic until mounting is completed. Take care 
not to damage the surfaces.

For optimal performance it is recommended 

that a minimum gap of 220 mm to the ceiling 

General instructions

Read these instructions carefully before in-
stallation and use. Keep this manual for future 
reference.

The guarantee is only valid if the Thermo-
zone units are used in the manner intended 
by the manufacturer and in accordance with 
the Frico installation and maintenance in-
structions.

Application area

AD Corinte belongs to a new generation of 
intelligent air curtains with SIRe integrated 
controls, together they can provide fully auto-
matic protection for the entrance, adaptable 
to each area of use.

AD Corinte is intended for exclusive shop 
entrances and other environments with high 
demands in respect of design and soundlevel. 
Mounted with one unit on either side of the 
opening, thus creating a classic symmetry, the 
curtain effect and comfort is optimized.

The Thermozone AD Corinte air curtain is 
supplied with or without an electric heater 
coil and is intended for permanent installa-
tion above or beside entrance doors and other 
openings up to 3,5 metres in height.
Protection class IP20

Operation

Air is drawn in at the top/rear of the unit and 
blown out downwards/outwards so that it 
shields the door opening and minimizes heat 
loss. To achieve the optimum curtain effect 
the unit must extend the full height/width of 
the door opening.

During installation the exhaust grille is 

normally directed outwards slightly so that 
the airflow obstructs incoming cold air. (See 
fig 1).

The fan speed should be controlled using a 

frequency converter.

The efficiency of the air curtain(s) depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure. 
NOTE! Negative pressure in the building 
considerably reduces the efficiency of the air 

Assembly and operating instructions

Содержание Thermozone AD Corinte A - ADCS

Страница 1: ...AD Corinte A E ADCS 26 GB 23 SE 29 RU ...

Страница 2: ...orinte A E ADCS 2 Min 180 M8 116 72 125 225 M8 116 72 125 225 Min 180 Cu ø22 VL A VL B VR A VR B Fig 1 Upper part of the unit seen from above Bottom part of the unit seen from above Opening Connection hatch ...

Страница 3: ...AD Corinte A E ADCS 3 1 2 80 60 1 2 60 80 3 Ø22 Cu 2200 2450 500 350 Fig 2 ...

Страница 4: ...AD Corinte A E ADCS 4 1 2 3 4 5 6 7 8 9 10 A B C Fig 3 ...

Страница 5: ...AD Corinte A E ADCS 5 Fig 4 ...

Страница 6: ...AD Corinte A E ADCS 6 80 35 ø12 180 35 25 40 Fig 6 Fig 7 360 243 Ø22 Ø10 15 5 10 Fig 5 ...

Страница 7: ...AD Corinte A E ADCS 7 1700 2200 1666 2166 75 Ø30 Ø20 3x Left connection Right connection Wall Fig 8 Fig 9 50 75 376 ADCS E Min 220 mm ADCS A W Min 180 mm ADCS E Min 220 mm ADCS A W Min 180 mm ...

Страница 8: ...AD Corinte A E ADCS 8 Fig 10 SIRe ...

Страница 9: ...AD Corinte A E ADCS 9 A B C A C B ADCEH Ø8 Ø12 2x 2 alternatives for securing at the top 1 Ø8 for securing at the air curtain 2 ...

Страница 10: ...Description HxWxD mm L m SIReB Control system Basic SIReAC Control system Competent SIReAA Control system Advanced SIReRTX 673 09 22 External room temperature sensor 70x33x23 SIReUR 673 09 21 Kit for recessed installation 114x70x50 SIReWTA Clamp on sensor SIReCJ4 Joint piece for two pcs RJ11 4p 4c SIReCJ6 Joint piece for two pcs RJ11 6p 6c SIReCC603 673 09 23 Modular cable RJ11 6p 6c 3 SIReCC605 6...

Страница 11: ...ernal ADCS A ADCSA SIReB1 230V Actuator 230V Transformer 230V 200V 170V 145V 120V 100V N Black Blue Supply 230V C2 C1 ROOM Internal sensor Motor protection Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue L N ...

Страница 12: ...IRe Basic SIRe Basic Parallel connection C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V SIReB1 SIReUB1 C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V 230V SIReB1 SIReB1 SIReUB1 ...

Страница 13: ...CK TEMP ON OFF potential free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 ROOM C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE 230V SIReB1 SIReC1X SIReDC SIReUA1 ...

Страница 14: ... L PE N L PE ACTUATOR SUPPLY Pot Unit ID Pot Unit ID EXTERNAL SETBACK TEMP ON OFF potential free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS ROOM 230V 230V 230V SIReB1 SIReB1 SIReB1 SIReC1X SIReDC SIReUA1 ...

Страница 15: ...3 ADCSE 400V3 400V3 SIReB1 230V Actuator 230V Transformer 230V 200V 170V 145V 120V 100V N Black Black Grey Blue Blue Supply 230V C2 C1 ROOM Internal sensor Motor protection Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue L N ...

Страница 16: ...3 ADCSE 230V3 230V3 SIReB1 230V Actuator 230V Transformer 230V 200V 170V 145V 120V 100V N Black Black Grey Blue Blue Supply 230V C2 C1 ROOM Internal sensor Motor protection Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue L1L2 ...

Страница 17: ...230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY Wiring diagrams AD Corinte E Electrical control options SIRe Basic SIRe Basic Parallel connection SIReB1 SIReB1 SIReB1 SIReRTX optional SIReRTX optional SIReUB1 SIReUB1 ...

Страница 18: ...XTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 ROOM C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE 230V Wiring diagrams AD Corinte E Electrical control options SIReAC Competent SIReB1 SIReC1X SIReRTX optional SIReDC SIReUA1 ...

Страница 19: ...TUATOR SUPPLY Pot Unit ID Pot Unit ID EXTERNAL SETBACK TEMP ON OFF potential free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS ROOM 230V 230V 230V SIReAC Competent Parallel connection SIReB1 SIReB1 SIReB1 SIReC1X SIReRTX optional SIReDC SIReUA1 ...

Страница 20: ...8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS ROOM C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE BMS INDICATION OUT potential free contact max 3A 230V 1 2 3 4 5 6 13 14 RPM INDICATION 0 10V DC out max 5 mA EXTERNAL HEAT 0 10V DC IN 21 22 HEAT INDICATION 0 10V DC out max 5 mA ACTUATOR SUPPLY 230V Wiring diagrams AD Corinte E Electrical control options SIReAA Advanced SIReB1 SIReA1X SIReRTX optional S...

Страница 21: ...OUT potential free contact max 3A 230V 1 2 3 4 5 6 13 14 RPM INDICATION 0 10V DC out max 5 mA EXTERNAL HEAT 0 10V DC IN 21 22 HEAT INDICATION 0 10V DC out max 5 mA C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY Pot Unit ID Pot Unit ID 230V 230V 230V SIReAA Adva...

Страница 22: ...cations Thermozone AD Corinte A without heat 1 Type Output kW Airflow m3 h Sound level 5 dB A Output motor W Voltage motor V Amper age motor A Length mm Weight kg ADCS17A 0 1400 3000 40 60 670 230V 2 9 1700 73 ADCS22A 0 1800 4000 42 61 990 230V 4 3 2200 95 ADCS25A 0 2050 4500 43 63 1150 230V 5 0 2450 108 ADCS17 is available only for horizontal mounting ADCS25 is available only for vertical mountin...

Страница 23: ...ompleted Take care not to damage the surfaces For optimal performance it is recommended that a minimum gap of 220 mm to the ceiling General instructions Read these instructions carefully before in stallation and use Keep this manual for future reference The guarantee is only valid if the Thermo zone units are used in the manner intended by the manufacturer and in accordance with the Frico installa...

Страница 24: ...ide the unit when con nected from below Secure the wiring inside the unit with cable ties to prevent it being sucked into the fans or in contact with the heating elements The control system is pre installed in the aircurtain with an integrated control card see fig 8 SIRe is supplied pre programmed with quick release connections Modular cables are connected to the con trol board Base by opening the...

Страница 25: ... this may be due to moisture in the heating ele ment When an appliance containing a heater element has not been used for a long period or stored in a damp environment moisture can enter the element This should not be seen as a fault but is simply rectified by connecting the appliance to the mains supply via a socket without a safety cut out so that the moisture can be eliminated from the element T...

Страница 26: ...B Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no 208032 2013 04 05 HH SÄ ...

Отзывы: