Maintenance

To ensure performance and reliabilty of the
SW02 unit, inspection and cleaning should be
carried out regularly. Inspection should be
carried out at least twice a year. Clean the unit
when needed.

During inspection the power supply must

always be disconnected.

Cleaning the fan

Cleaning intervals for the fan depends on filter (if
any) and air quality. If the impellers are not
cleaned properly, vibrations/noise can occur and
severly damage the bearings. If the vibrations/
noise remain after cleaning, please contact a
competent electrician.

The SW02 unit and the heating coil

 

can be

vaccumed to remove dust.

Inspection and cleaning of SW02 should be

done from the outside and inside.

Filter

If the heater is equipped with a deep-pleated bag
filter (extra), it should be cleaned when
necessary. 

The filter should be checked at least 4

times a year. To clean the filter, open top or
bottom lid by loosening a pair of screws
underneath the lid and vaccum.

Heating coil

Inspect the coil for water leakage and corrosion.
Dust on the surface of the heating coil can be
vaccumed.

Motor

The motor is normally maintenance free. If noise
or vibrations should occur, inspect the bearing
and replace if necessary. Replacement should be
carried out by a competent electrician.

Safety

-

Ensure that the area around the intake is
kept free from material which could
prevent the air flow through the
appliance!

-

The appliance may have hot surfaces during
operation!

Accessories

See also table page 2.

Fan speed and heat regulation

The fan motors are in standard design prepared
for three fixed fan speed stages, see wiring
diagrams.

CB30N, control panel

Regulates the air flow in three stages. Is delivered
separately in an enclosed casing for wall
mounting. Max input 10 A. Protection class:
splash-proof design (IP44).

SWR20, valve set

The valve set is suitable when there is need for
adjusting the water flow and for shutting the
water flow off for maintenance. The heat supply
is controlled by a thermostat. Pipe dimension of
SWR20 is DN20 (

3

/

4

”).

Consisting parts:
• AV20, stop valve
Stops the water supply to SW02. Consists of a ball
valve which is either closed or open.

• JV20, adjustment valve
Adjusts the water to desired flow. (kv-value for
JV20 0,13 - 0,59.) When maintenance is needed,
the water flow can be stopped with the stop and
the adjustment valves.

• TVV20, 2-way regulation valve
Pressure class PN16, maximum pressure 2 MPa
(20 Bar), maximum pressure drop for TVV20 is
100 kPa (1,0 Bar). The kv-value is adjustable in
three stages:
TVV20

kv 1,6

kv 2,5

kv 3,5

• SD20, actuator on/off 230V~
The heat supply to SW02 is controlled by a room
thermostat. Works on/off. The time span between
closed and open prevents sudden pressure
changes in the pipe system. Protection class:
IP40.

Содержание SW 02

Страница 1: ...SW 02 9 12 GB 15 NO 24 DE 27 PL 18 FR 30 FI 21 RU SE...

Страница 2: ...672 70 35 SD20 672 70 37 RTI2 155x87x43 RTE102 15A 672 70 38 71x71x28 RTEV102V 15A 165x57x60 KRT1900 16A 10A 672 70 40 165x57x60 KUR 672 70 42 165x105x95 SWFT02 SWMSK AV20 JV20 TVV20 SD20 450 520 18...

Страница 3: ...sniv Sound pressure level Lp r ber knat enligt f ljande Avst nd till fl kt 5 meter Riktningsfaktor 2 Ekvivalent absorptionsarea 200 m2 Testm tningarna r utf rda i enlighet med BS148 AMCA standard 210...

Страница 4: ...3 2 3 4 5 6 1 N CB30N SW02 7 8 9 Blue Yellow Green White Grey Black Yellow Brown Yellow SW02 9 N 1 2 3 4 5 6 7 8 9 N 1 2 3 4 5 6 7 8 1 2 3 L1 N L2 230 V 2 4 5 6 1 3 SW02 SW02 SD20 TVV20 CB30N KRT1900...

Страница 5: ...N 2 4 5 6 1 3 1 2 3 Hi Lo 4 5 6 1 3 2 L N L1N L2 230 V SW02 SW02 SD20 TVV20 KUR CB30N RTI2 9 N 1 2 3 4 5 6 7 8 9 N 1 2 3 4 5 6 7 8 L1 N L2 230 V 2 4 5 6 1 3 1 2 3 4 5 SW02 SW02 SD20 TVV20 RTE RTE102 R...

Страница 6: ...8 13 1 49 6 0 15 7 7 12 0 51 8 0 14 6 6 Medium 17 8 39 2 0 21 13 4 14 9 45 3 0 17 9 7 13 0 49 4 0 15 7 6 12 0 51 5 0 14 6 6 11 0 53 5 0 13 5 6 Min 14 7 45 2 0 17 9 4 12 3 50 4 0 14 6 9 10 7 54 0 0 12...

Страница 7: ...7 33 4 0 10 1 9 4 9 35 1 0 05 1 4 4 1 36 8 0 04 1 0 Vattentemperatur Water temperature 60 30 o C t 1 15 o C 0 o C 10 o C 15 o C 20 o C P t 2 q 2 p P t 2 q 2 p P t 2 q 2 p P t 2 q 2 p P t 2 q 2 p q 1 k...

Страница 8: ...eras tryckfallet med faktor K The pressure drop is calculated for an average temperature of 70 C PVV 80 60 For other temperatures the pressure drop is multiplied with the factor K Medeltemp vatten Ave...

Страница 9: ...r ranslutning se sid 2 1 Lossa konsolen fr n apparaten genom att skruva ur de nedre h len helt och de vre s l ngt som kr vs 2 Markera h len med hj lp av den l sa konsolen 3 Borra h len f r skruvarna o...

Страница 10: ...tandard f rberedd att inkopplas f r tre olika fasta fl ktvarvtal se kopplingscheman CB30N man verpanel Reglerar luftfl de i tre steg Levereras i separat kapslad dosa f r montering p v gg Max m rk str...

Страница 11: ...t stopp av fl kten alternativt v xling mellan l gt h gt luftfl de eller f r spars nkning av rumstermostaten med extern termostat Med spars nkning erh lls en l gre temperatur i lokalen under t ex n tte...

Страница 12: ...ensions and pipe dimensions see page 2 1 Loosen the bracket from the appliance by unscrewing the screws from the lower holes completely and the upper as much as necessary 2 Mark holes with help of the...

Страница 13: ...Safety Ensure that the area around the intake is kept free from material which could prevent the air flow through the appliance The appliance may have hot surfaces during operation Accessories See al...

Страница 14: ...changes in the pipe system Protection class IP40 Room thermostats see accessories on page 2 Regulates actuator SD20 to open close the valve when there is a demand for heat The room thermostat can also...

Страница 15: ...Marker huller med hjelp av den l se konsol len 3 Bor hull for skruene og fest konsollen 4 Fest apparatet p konsollen og juster vinkelen 5 Skru i de nedre skruene og dra til samtlige skruer Tilsluttni...

Страница 16: ...10 A Kapslingsklasse IP44 SWR20 ventilsats Ventilsatsen er enkel bruke n r det er n dvendig regulere vannstr mmen eller stenge av for service Vanntilf rselen er termostatstyrt SWR20 har r rdimensjon D...

Страница 17: ...blingsur Digitalt koblingsur for start stopp av viften alter nativt veksling mellom lav og h y luftmengde Kan ogs benyttes for nattsenkning med ekstern 2 trinns termostat D gn uke funksjon Kapslingskl...

Страница 18: ...page 2 1 D montez la console de l a rotherme en desserrant les vis des trous bas et haut 2 R perer l emplacement des trous de vis l aide de la console d mont e 3 Percer les trous de fixation et fixer...

Страница 19: ...ts et les changer si n cessaire Cette op ration doit tre r alis par un lectricien confirm S curit S assurer qu aucun l ment atour de l appareil viendra obstruer le passage de l air Attention L apparei...

Страница 20: ...udains et brusques dans le r seau hydraulique Indice de protection IP40 Thermostats d ambiance voir les accessoires page 2 R gule l lectrovanne SD20 d ouvrir de fermer la vanne lorsqu il y a une deman...

Страница 21: ...21 SW 02 RU SW02 SW02 SW02 SW02 IP44 SW02 RAL9016 NCS0500 230 50 IP44 40 o C C 2 10 2 90o C 16 30 135 o C SW02 2 1 2 3 4 5 2 3 2 30 4 5...

Страница 22: ...22 SW 02 RU 2 4 2 CB30N 3 10 IP44 SWR20 KRT1900 SWR20 DN20 3 4 SWR20 AV20 2 JV20 kV 0 13 5 9 AV20 JV20 JV20 TVV20 2 2000 20 TVV20 100 1 kV 3 TVV20 kv 1 6 kv 2 5 kv 3 5 SD20 230 2...

Страница 23: ...23 SW 02 RU 5 IP40 TVV20 SD20 TVV20 DN20 3 4 TVV20 2 2000 20 TVV20 100 1 kV 3 TVV20 kv 1 6 kv 2 5 kv 3 5 SD20 230 2 SW02 5 IP40 2 2 SW02 C KUR 24 IP55 SWFT02 SW02...

Страница 24: ...blas an der Decke montiert werden SW02 kann mit den Rohranschl ssen nach links oder nach rechts montiert werden Abmessungen und Rohranschlussmasse siehe S 2 1 Um die Konsole vom Ger t zu l sen schraub...

Страница 25: ...hrauben unter dem Deckel Verwenden Sie einen Staubsauger Heizregister berpr fen Sie das Register auf Wasserundichtigkeit und Korrosion Staub auf der Oberfl che des Registers kann einfach abgesaugt wer...

Страница 26: ...ermostat Schaltet Ein Aus Die Zeitspanne zwischen offen und geschlossen verhindert pl tzliche Druckver nderungen im Rohrsystem Schutzart IP40 Raumthermostat Siehe Zubeh r Seite 2 Gibt ein Signal an de...

Страница 27: ...ce SW s dostarczane z nastawialnymi deflektorami do kontroli strugi powietrza w jednym kierunku Deflektory s wykonane z anodyzowanego aluminium Monta Nagrzewnica SW jest dostarczana jako jednostka sk...

Страница 28: ...uwalne s np wibracje ha as to prosz skontaktowa si z serwisem Kiedy jest u ywana sekcja filtracyjna z filtrami workowymi i je eli jako powietrza obiegowego jest normalna to czyszczenie raz w roku powi...

Страница 29: ...wu wody Spos b montowania i pod czenia patrz strona 10 2 drogowy zaw r regulacyjny TVV 20 Klasa ci nienia PN 16 Maksymalne ci nienie 20 bar Maksymalny spadek ci nienia 1 bar Maksymalny spadek ci nieni...

Страница 30: ...lla alemmat rei t kokonaan auki ja muut rei t riitt v ss m rin 2 Merkitse rei t irrotetun konsolin avulla 3 Poraa ruuvien rei t ja asenna konsoli paikalleen 4 Ripusta laite konsoliin ja s d se sopivaa...

Страница 31: ...ri tarkastaa ja tarvittaessa vaihtaa Vaihtoty n saa tehd vain ammattitaitoinen asentaja Turvallisuus Varmista ettei l mmittimen tulo ja poistoaukon ritil ihin ole ker ntynyt roskia jotka est v t ilman...

Страница 32: ...paineiskut putkistossa Kotelointiluokka IP40 Huonetermostaatit Lue lis varustelista sivulta 2 Termostaattien avulla ohjataan venttiilimoottoria avautumaan ja sulkeutumaan l mmitystarpeen mukaan Huonet...

Страница 33: ...33 SW 02...

Страница 34: ...SW 02 34...

Страница 35: ...liance with applicable international standards and regulations We confirm that the following products Fan heater SW02 and accessories KRT RTE SWR20 comply with the following EC directives Declaration...

Страница 36: ...o fr For latest updated information see www frico se United Kingdom Frico UK Tel 44 16 3473 5020 Pharaoh House Fax 44 16 3473 5019 Arnolde Close info uk frico se Medway City Estate www frico co uk UK...

Отзывы: