Mounting 

The air curtain unit is installed horizontally 
with the supply air grille facing downwards 
as close to the door as possible. Minimum 
distance from outlet to floor for electrically 
heated units is 1800 mm. For other minimum 
distances, see fig. 4.
     Brackets and torx bit are enclosed in the 
gable end packaging upon delivery. 

Mounting with wall brackets (fig. 6) 

1. Mount the brackets on the wall, see fig.6A 

and dimension drawing fig.1. If the wall is 
uneven the brackets must be compensated 
for this. 

2. Hook on the unit at the lower edge of the 

brackets. (Fig.6B-C)

3. Bend the top of the console over the the 

unit and slide the units screws along the 
rail into the slots on the consoles. (Fig.6D) 
When the bracket is bent once, it must be 
replaced if bent back more than 45 °. 

4. Lock the nuts against the brackets. (Fig.6E)
 

Horizontal mounting on the ceiling 

Threaded rods, hanging brackets and ceiling 
mounting brackets for ceiling mounting are 
available as accessories, see accessories pages 
and separate manuals.
 

Electrical installation 

The installation, which should be preceded 

by an omnipolar switch with a contact 
separation of at least 3 mm, should only 
be wired by a competent electrician and in 
accordance with the latest edition of IEE 
wiring regulations. The control system is pre-
installed in the air curtain. 
 

Unit without heating 

Connected via the built-in control board with 
1,5 m cord and plug.
  

Unit with water heating 

Connected via the built-in control board with 
1,5 m cord and plug.
 

General Instructions 

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

The product may only be used as set out in 
the assembly and operating instructions. The 
guarantee is only valid if the product is used 
in the manner intended and in accordance 
with the instructions. 

  
 

Application 

PL3200C is a compact air curtain with a 
recommended installation height of 3,2 
metres. The air curtain has an integrated 
control system and can be remotely 
controlled.  
    The air curtain is available without heat, 
with electrical heating and with water heating. 
Protection class for units with electrical 
heating: IP20.  
Protection class for units without heating and 
units with water heating: IP21. 
 

Operation

Air is drawn in at the top of the unit and 
blown out downwards so that it shields the 
door opening and minimizes heat loss. To 
achieve the optimum curtain effect the 
unit must extend the full width of the door 
opening.

 The grille for directing exhaust air is 

adjustable and is normally angled outwards to 
achieve the best protection against incoming 
cold air.  

The efficiency of the air curtain depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure.

 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced. 

Содержание PL3200C

Страница 1: ...PL3200C Recommended installation height 3 2 m GB FR...

Страница 2: ...0 153 99 50 209 DN20 3 4 1046 1556 2046 459 42 10 256 min 500 157 87 209 50 DN20 3 4 32 153 min 500 min 500 157 157 min 500 min 500 153 99 50 209 DN20 3 4 L 2 m A W E DN20 3 4 outside thread 1046 1556...

Страница 3: ...PL3200C 3 Fig 2 Fig 3 Open the unit A B C Gland Knock out Knock out Knock out 17 5 17 5 32 5 25 5 20 5 17 5 Gland Gland...

Страница 4: ...PL3200C 4 Fig 4 Fig 5 Minimum distance 30 mm 60 mm min 60...

Страница 5: ...PL3200C 5 min 500 mm Fig 6 Mounting with wall brackets Mounting with wall brackets PL3210C 2 pcs PL3215C 2 pcs PL3220C 3 pcs A B C D 8 3x 7 16 213 37 260 75 35 20...

Страница 6: ...L3210C PL3215C 1 m PA2P20 PL3220C 1 m PA3PF15 PL3210C PL3215C PA3PF20 PL3220C PAMLK PL3200C FHDN20 PL3200C W PA34TR PA2P PA3PF PAMLK FHDN20 PL2DR VOT VOT15 DN15 VOT20 DN20 VOT25 DN25 VKF15LF DN15 VKF1...

Страница 7: ...0 10V HEAT ALARM WATER IR PL3210CA PL3215CA PL3220CA C 3220CA 3215CA 3210CA Red Red Black Blue Brown L N Low Mid b1 c1 Orange Yellow Yellow Yellow Mid Low Blue Black b1 c1 Orange Red Orange White Whi...

Страница 8: ...heat cut out C K1 K1 high power K2 low power L2 PE L1 L N L3 400V 3N Over heat C cut out PL3210CE PL3215CE PL3220CE Only 2 m version K4 K3 K3 high power K4 low power PE 400V3 L2 L1 L3 C Black Brown B...

Страница 9: ...L3210CW PL3215CW PL3220CW Black Brown Blue C 3220CW 3215CW 3210CW Red Black Blue Brown L N Low Mid b1 c1 Orange Orange White Yellow White Mid Low Blue Black b1 c1 Red Orange Red Yellow White Yellow Bl...

Страница 10: ...r alarm pot free contact 5A x 3 5A 16A N H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR C Black Brown Blue Mid Low N L c1 b1 M Left motor Run M Right m...

Страница 11: ...3 h t 3 4 C Water volume l Sound level 2 dB A Voltage motor V Amperage motor A Length mm Weight kg PL3210CW 8 1050 1700 16 14 1 3 45 55 230V 0 65 1046 26 PL3215CW 14 1850 2700 17 15 2 1 46 57 230V 0 7...

Страница 12: ...L3215CW max 2700 16 0 45 0 26 13 4 13 9 33 0 17 6 3 min 1850 10 8 40 0 13 4 0 10 8 35 0 13 4 0 PL3220CW max 3300 18 9 42 0 26 10 2 17 6 34 0 21 7 1 min 2200 12 9 39 0 15 3 6 13 4 36 0 16 4 4 Supply wa...

Страница 13: ...hout heating Connected via the built in control board with 1 5 m cord and plug Unit with water heating Connected via the built in control board with 1 5 m cord and plug General Instructions Read these...

Страница 14: ...air curtain and air flow The direction and speed of the air flow should be adjusted considering the load on the opening Pressure forces affect the air stream and make it bend inwards into the premises...

Страница 15: ...he bottom Fig 3 3 After the service repair and maintenance reattach the front hatch Place the hatch at the lower edge with the bent edge and fasten on top with screws Note that when carrying out work...

Страница 16: ...lt in control system For units with electrical heating also check the following Power supply to electric heater coil check fuses and circuit breaker if any That the overheat protection for the motors...

Страница 17: ...D230 remove the quick connector Black Brown Blue External on off Eg time switch External potential free closure off PL2DR accessory Factory setting dip switches Unit without heating or with electrical...

Страница 18: ...to vent out the heat if the temperature rises above 50 C again during the following 5 minutes overheating alarm is deployed The red LEDs flash and all the buttons are locked 1 Disconnect the electrici...

Страница 19: ...Art no 117959 2013 10 24 CH HH Technical Support tel 46 313368600...

Отзывы: