PL3200C
11
Type
Output
[kW]
Airflow*
1
[m
3
/h]
Sound
level*
2
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
PL3210CA
0
1100/1750
46/57
230V~
0,7
1046
22
PL3215CA
0
1700/2750
46/59
230V~
1,0
1556
31
PL3220CA
0
2300/3500
50/60
230V~
1,3
2046
41
Type
Output
step
[kW]
Airflow*
1
[m
3
/h]
∆
t
*3
[°C]
Sound
level*
2
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Voltage [V]
Amperage [A]
(heat)
Length
[mm]
Weight
[kg]
PL3210CE08
5/8
1100/1750
22/13
46/57
230V~
0,65
400V3~/11,5
1046
26
PL3215CE12
8/12
1700/2750
21/13
46/59
230V~
1,0
400V3~/17,3
1556
37
PL3220CE16
10/16
2300/3500
22/13
50/60
230V~
1,3
400V3~/23,1
2046
51
Type
Output*
4
[kW]
Airflow*
1
[m
3
/h]
∆
t
*3,4
[°C]
Water
volume
[l]
Sound
level*
2
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
PL3210CW
8
1050/1700
16/14
1,3
45/55
230V~
0,65
1046
26
PL3215CW
14
1850/2700
17/15
2,1
46/57
230V~
0,7
1556
36
PL3220CW
18
2200/3300
18/16
2,7
49/58
230V~
1,3
2046
48
2
Water heat - PL3200C W
3
Electrical heat - PL3200C E
1
Ambient, no heat - PL3200C A
*
1
) Lowest/highest airflow of totally 3 fan steps.
*
2
) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At
lowest/highest airflow.
*
3
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
4
) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
Protection class for units with electrical heating: IP20.
Protection class for units without heating and units with water heating: IP21.
CE compliant.