PFW
6
GB
Mounting
1. Please note that the area close to the radiator must
be left free of obstructions, see page 2 for minimum
distance.
2. Mount the wall fixing on the wall. Make sure the
fixing is mounted level. The holes on the wall fixing
can be marked in two ways.
• Hammer a nail in the middle hole on the
fixture and use a spirit level to get it
square. (The distance between the hole in the
middle and the floor should be 240 mm.)
See Fig. 2.
• The holes can also be marked by using the
template on the box. Make sure the template is
flat to the wall surface! See Fig. 3.
Fasten the wall fixing securely on the wall by
screwing the screws in the oval holes (4x).
240 mm
Fig. 2
Using a spirit level to mount the wall fixing.
Fig. 3
Using the packing to mount the wall fixing.
3. Angle the radiator 90
o
outwards and slot the
lower part of the wall fixing into the circular holes
furthest down on the back of the radiator. Raise
radiator and fasten the security chains. The top is
then clipped in place with the snap pins on the wall
fixing. Now the radiator will hang on the wall fixing
by the chains even if the pins are loosened for
example for cleaning. See Fig. 4.
Fig. 4
Mounting of security chains.
4. Connect the radiator to an earthed wall socket.
Water connection
The water pipes (DN15, 1/2” BSP-F outside thread)
are connected at the left hand side (when viewed
from inside of the building) on the backside of the
unit, see fig.on page 2.
Flexible hoses type PEX 15x2,5, length 850mm are
supplied with the unit as standard.
Using flexible hoses makes the maintenance and
service much easier.
The installation should be carried out by a certified
installer.
Mounting of fan convector PF.
horizontal
The chain is
fixed here
Fasten the
chain
here