Safety
•
For all installations of electrically heated
products should a residual current circuit
breaker 300 mA for fire protection be used.
•
Keep the areas around the air intake
and exhaust grilles free from possible
obstructions!
•
The unit may have hot surfaces during
operation and when cooling down!
•
The unit must not be fully or partially
covered with clothing, or similar
materials, as overheating can result in a
fire risk! (E)
•
This appliance can be used by children
aged from 8 years and above and persons
with reduced physical, sensory or
mental capabilities or lack of experience
and knowledge if they have been given
supervision or instruction concerning
use of the appliance in a safe way and
understand the hazards involved. Children
shall not play with the appliance. Cleaning
and user maintenance shall not be made
by children without supervision.
Residual current circuit breaker (E)
When the installation is protected by means
of a residual current circuit breaker, which
trips when the appliance is connected,
this may be due to moisture in the heating
element. When an appliance containing a
heater element has not been used for a long
period or stored in a damp environment,
moisture can enter the element.
This should not be seen as a fault, but is
simply rectified by connecting the appliance
to the main supply via a socket without a
safety cut-out, so that the moisture can be
eliminated from the element. The drying
time can vary from a few hours to a few days.
As a preventive measure, the unit should
occasionally be run for a short time when it is
not being used for extended periods of time.
Trouble shooting
If the fans are not working or do not blow properly,
check the following:
• That the intake grille/filter is not dirty.
• Functions and settings of the SIRe control
system, see manual for SIRe.
If there is no heat, check the following:
• Functions and settings of the SIRe control
system, see manual for SIRe.
For units with electrical heating, also check the fol-
lowing:
• Power supply to electric heater coil; check
fuses and circuit-breaker (if any).
• That the overheat protection for the motors
has not been deployed.
For units with water coil, also check the following:
• That the water coil is air free.
• That there is enough water flow.
• That incoming water is heated enough.
If the fault cannot be rectified, please contact
a qualified service technician.
Replacing the water coil (W)
1. Shut off the water supply to the unit.
2. Disconnect the connections to the water
coil.
3. Remove the mounting screws securing the
coil in the unit and lift the coil out.
4. Install the new coil in reverse order to the
above.
Draining the water coil (W)
The drain valve is on the underside of the coil
on the connector side. It can be accessed via
the front hatch.
Содержание PA2500
Страница 1: ...PA2500 Original instructions 20 SE 25 GB 29 DE 34 ES 39 FR 44 IT 49 NL 54 NO 59 PL 64 RU ...
Страница 4: ...PA2500 4 ø17 5 ø17 5 ø32 5 ø25 5 ø20 5 ø17 5 Gland Knock out Knock out Knock out Gland Fig 2 Gland ...
Страница 5: ...PA2500 5 Fig 3 Open the unit A B C TX20 Fig 4 Minimum distance min 60 ...