Assembly and operating instructions

General Instructions 

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

The product may only be used as set out in 
the assembly and operating instructions. The 
guarantee is only valid if the product is used 
in the manner intended and in accordance 
with the instructions. 

 

Application area 

PA2500 is intended for installation heights 
up to 2.5 metres.  The air curtain is available 
without heat, with electrical heating and with 
water heating. Protection class for units with 
electrical heating: IP20.  
Protection class for units without heating and 
units with water heating: IP21. 

Operation 

Air is drawn in at the top of the unit and 
blown out downwards so that it shields the 
door opening and minimizes heat loss. To 
achieve the optimum curtain effect the 
unit must extend the full width of the door 
opening. 

The grille for directing exhaust air is 

adjustable and is normally angled outwards to 
achieve the best protection against incoming 
air. 

The efficiency of the air curtain depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure. 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced. 

 

Mounting

The air curtain unit is installed horizontally 
with the supply air grille facing downwards 
as close to the door as possible. Minimum 
distance from outlet to floor for electrically 
heated units is 1800 mm. For other minimum 
distances, see fig. 4.
 

Mounting with wall brackets (fig. 6) 

1. Mount the brackets on the wall, see fig.6A 

and dimension drawing fig.1. If the wall is 
uneven the brackets must be compensated 
for this. 

2. Hook on the unit at the lower edge of the 

brackets. (Fig.6B)

3. Bend the top of the console over the the 

unit and slide the units screws along the 
rail into the slots on the consoles. (Fig.6C) 
When the bracket is bent once, it must be 
replaced if bent back more than 45 °. 

4. Lock the nuts against the brackets. (Fig.6D)
   

Horizontal mounting on the ceiling  

Threaded rods, hanging brackets and ceiling 
mounting brackets for ceiling mounting are 
available as accessories, see accessories pages 
and separate manuals.
 

Electrical installation  

The installation, which should be preceded by 
an omnipolar switch with a contact separation 
of at least 3 mm, should only be wired by a 
competent electrician and in accordance with 
the latest edition of IEE wiring regulations. 
The control system is pre-installed in the air 
curtain with an integrated control card. SIRe 
is supplied pre-programmed with quick-fit 
connections. Modular cables are connected to 
the control board. See manual for SIRe.
 

Unit without heating or with water heating

Connected via the built-in control board SIRe 
with 1,5 m cord and plug. 
 

Содержание PA2500

Страница 1: ...PA2500 Original instructions 20 SE 25 GB 29 DE 34 ES 39 FR 44 IT 49 NL 54 NO 59 PL 64 RU ...

Страница 2: ...englischer Sprache siehe die entsprechenden Sprachseiten DE Las páginas introductorias contienen básicamente imágenes Consulte la traducción de los textos en inglés que las acompañan en las páginas del idioma correspondiente ES De inleidende pagina s bevatten hoofdzakelijk afbeeldingen Voor een vertaling van de gebruikte Engelse teksten zie de pagina s van de resp taal NL Le pagine introduttive co...

Страница 3: ...0 min 500 min 500 157 157 2 m 345 min 500 min 500 min 500 157 157 157 90 5 10 20 40 22 210 165 184 1026 1536 2026 1050 1560 2050 Cu ø15 53 71 40 min 500 min 500 157 157 PA2500A PA2500W PA2500E 1 2 3 345 min 500 min 500 min 500 157 157 157 90 5 10 20 40 22 210 165 184 1026 1536 2026 1050 1560 2050 Cu ø15 53 71 40 min 500 min 500 157 157 ...

Страница 4: ...PA2500 4 ø17 5 ø17 5 ø32 5 ø25 5 ø20 5 ø17 5 Gland Knock out Knock out Knock out Gland Fig 2 Gland ...

Страница 5: ...PA2500 5 Fig 3 Open the unit A B C TX20 Fig 4 Minimum distance min 60 ...

Страница 6: ...PA2500 6 min 500 mm Fig 6 Mounting with wall brackets Mounting with wall brackets A B C PA2510 2 pcs PA2515 2 pcs PA2520 3 pcs D 20 35 75 210 33 ø8 3x ø5 ø10 162 ...

Страница 7: ...PA34TR15 PA2510 PA2515 1 m PA34TR20 PA2520 1 m PA2P15 PA2510 PA2515 1 m PA2P20 PA2520 1 m PA2PF15 PA2510 PA2515 PA2PF20 PA2520 PAMLK PA2500 PA2EF10 PA2510W PA2EF15 PA2515W PA2EF20 PA2520W PAWAK PA2500W FHDN15 PA2500W PAMLK PA2EF PAWAK FHDN15 ...

Страница 8: ... 5 m SIReCC610 10 m SIReCC615 15 m SIReCC640 40 m SIReCC403 3 m SIReCC405 5 m SIReCC410 10 m SIReCC415 15 Accessories SIRe C SIReB SIReAC SIReAA SIReRTX SIReUR SIReWTA SIReCC SIReCJ4 SIReCJ6 VKF15LF DN15 VKF15NF DN15 VKF20 DN20 VKF25 DN25 VKF32 DN32 SD230 BPV10 SDM24 ST23024 VKF SDM24 ST23024 SD230 BPV10 VKF VLSP VLP ...

Страница 9: ... power L2 PE L1 L N L3 400V 3N ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection SIReB2 Over heat C cut out PA2510E05 PA2515E08 PA2520E10 C4 C3 C1 low power C2 high power L2 PE L1 L3 400V3 M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid PA2500 9 ...

Страница 10: ...power L2 PE L1 L N L3 400V 3N ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection SIReB2 Over heat C cut out PA2510E08 PA2515E12 PA2520E16 C4 C3 L2 PE L1 L3 400V 3 C1 low power C2 high power M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid PA2500 10 ...

Страница 11: ...F2 F3 H1H2 Heating Motor trafo ID pot ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection SIReB2 PA2510WA PA2515WA PA2520WA M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 Mid PA2500 11 ...

Страница 12: ...eating Motor trafo ID pot L2 PE L1 L N L3 400V 3N ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection SIReB2 PA2510E05YD PA2515E08YD L2 PE L1 L N L3 230V 3 230V 3 400V 3 a1 a2 b2 c2 c1 b1 a1 a2 b2 c2 c1 b1 M Blue Black Brown C Right motor C3 Run C2 Lo C1 Mid PA2500 12 ...

Страница 13: ...nal sensor Motor protection SIReB2 Over heat C cut out PA2520E10YD L2 PE L1 L N L3 230V 3 230V 3 400V 3 a1 a2 b2 c2 c1 b1 a1 a2 b2 c2 c1 b1 M Blue Black Brown C Right motor C3 Run C2 Lo C1 Mid C2 C1 L2 PE L1 L3 400V 3 230V 3 400V 3 a1 a2 b2 c2 c1 b1 a1 a2 b2 c2 c1 b1 M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor L2 PE L1 L3 230V 3 PA2500 13 ...

Страница 14: ...wn C Lo Mid Run Right motor L N PE N N F1 F2 F3 H1H2 Heating Motor trafo ID pot ACTUATOR SUPPLY ROOM C1 C 2 Internal sensor Motor protection SIReB2 N F1 F2 F3 OUT PAMLK C NC NO M Blue Black Brown C Lo Mid Run Left motor Only 2 m version PA2500 14 ...

Страница 15: ...M X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReCC6XX max 50 m SIReCC6XX max 50 m SIReUB1 SIReRTX optional L 2m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC PA2500 15 ...

Страница 16: ... C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC SIReCC6XX max 50 m SIReCC6XX max 50 m SIReUB1 SIReRTX optional SD230 SD230 SD230 L 1 5m L 2m PA2500 16 ...

Страница 17: ... 5 43 0 0 07 1 9 19 8 45 8 0 24 19 6 Min 1250 7 2 36 0 0 03 0 6 14 3 51 5 0 18 10 8 PA2520W Max 2600 15 1 41 0 0 08 3 1 24 4 45 6 0 30 34 6 Min 1800 10 6 36 0 0 05 1 5 19 3 49 6 0 24 22 8 Supply water temperature 110 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 110 80 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pres...

Страница 18: ...5 See www frico se for additional calculations 1 Recommended outlet air temperature for good comfort and optimized output 2 Nominal output at given supply and return water temperature Supply water temperature 55 C Room temperature 18 C Outlet air temperature 29 C Water temperature 55 35 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pressure dro...

Страница 19: ...3 dB A Amp motor A Voltage heat V Amp heat A Length mm Weight kg PA2510E05YD 1 7 3 3 5 900 1450 17 10 5 68 42 51 0 5 230V3 400V3 12 6 7 2 1050 19 PA2515E08YD 2 7 5 4 8 1400 2200 17 5 11 69 40 52 0 7 230V3 400V3 20 1 11 5 1560 30 PA2520E10YD 3 4 6 7 10 1800 2900 17 10 5 70 43 53 1 0 230V3 400V3 25 1 14 4 2050 36 1 Ambient no heat PA2500 A Technical specifications Type Output kW Airflow 1 m3 h Sound...

Страница 20: ... Mounting The air curtain unit is installed horizontally with the supply air grille facing downwards as close to the door as possible Minimum distance from outlet to floor for electrically heated units is 1800 mm For other minimum distances see fig 4 Mounting with wall brackets fig 6 1 Mount the brackets on the wall see fig 6A and dimension drawing fig 1 If the wall is uneven the brackets must be ...

Страница 21: ... see Frico valve kit The water coil is connected on the upper side of the unit with ø15 mm smooth copper pipe with a suitable coupling or soldering The connections to the heating coil must be equipped with shut off valves to allow problem free removal Water coil is equipped with a drain valve A vent valve should be connected at a high point in the pipe system Air valves are not included NOTE Care ...

Страница 22: ...e of the terminal box 5 Reattach the front hatch and connect the unit again All motors are equipped with an integral thermal safety cut out This will operate stopping the air curtain should the motor temperature rise too high The cut out will automatically reset when the motor temperature has returned to within the motor s operating limits Temperature control Temperature control of SIRe maintains ...

Страница 23: ... rectified by connecting the appliance to the main supply via a socket without a safety cut out so that the moisture can be eliminated from the element The drying time can vary from a few hours to a few days As a preventive measure the unit should occasionally be run for a short time when it is not being used for extended periods of time Trouble shooting If the fans are not working or do not blow ...

Отзывы: