For ceiling
mounted installation, the available mount
angles are restricted to 0°, 15° and 30° only.
•
For wall
mounted installation, the available mount angles
are restricted to 15°, 30° and 45° only.
7. Hang the heater on the brackets and firmly secure in
place with the mounting bracket locking plates by
tightening bolts.
NOTE:
Depending on material and design of ceiling structural
elements, the heater must be secured with the correct
fasteners. The weight of the heater is up to 5.3Kg, the
installation location must be able to hold 5 times the
weight of the heater.
C
ONNECTION TO ELECTRIC MAINS
:
•
The heater is designed for connection to the single-phase
230-240V~ 50Hz electric mains equipped with an earth
wire.
•
Before connection, make sure that specifications of the
electric mains at the connection point meet the single-
phase 230-240V~ 50Hz voltage.
•
Regarding the model IHGB/W12SR
In case of direct connection to the supply line, a bipolar
switch or a bipolar circuit breaker with contact opening
distance of at least 3mm must be fitted upstream from the
supply line. Contact an authorized service technician if you
are unsure if you have a switch or a circuit breaker installed
on the premises.
•
The electric mains should be equipped with an automatic
circuit breaker with C curve type (slow blow fuse) and with
rated current not less than 10A (model 1500W) or 16A
(model 2200W). Contact an authorized service technician if
you are unsure if you have a circuit breaker installed on the
premises
•
The electric mains should be equipped with an automatic
circuit breaker with rated current not less than 16A.
.
•
The heater must not be located immediately below a
power point. Power point should not be located at the back
of the heater. The power point needs to be located outside
the physical footprint of the heater to minimize heat build-
up behind the heater.
•
If the heater is to be mounted on an incline (eg. Vaulted
ceiling), ensure the power point located at that lowest point
of the heater.
W
IRING SCHEMATIC DIAGRAM
:
IHGB/W12SR:
IHGB/W15S, IHGB/W22S:
Model No
“B”
(mm)
MINIMUM DISTANCE
1200W
300±20
1500W
500 ±50
2200W
500 ±50
GB
EN
14
W
all
Ceiling
Correct Installation
Incorrect Installation
IN-L
IN-N
OUT-L
Heating Element
1200W
Heating Element
Switch
1500W
2200W